Cable spreading room fire protection: sample DWG of a clean agent system
The fire protection of a cable spreading room, drawn as one sheet. On the left the agent store holds a bank of cylinders with a release solenoid and a check valve; the discharge pipe passes through a sealed penetration in the fire-rated wall and feeds three nozzles in the room. Two cable trays enter through penetration seals. The room is watched three ways: an aspirating unit with four sampling points on the ceiling, two multi-criteria smoke detectors and linear heat cable along the trays, all wired to a releasing panel outside. The panel drives a delay timer, a pre-discharge alarm, a door hold-open, a fire damper, an agent released lamp, a manual release and an abort switch, and a pressure relief vent protects the walls. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.
Grátis para usar e modificar nos seus próprios projetos, inclusive comerciais. O ZIP traz o desenho de exemplo, um modelo, uma tabela de estilos de plotagem e um README; não precisa de nenhum add-in. Os dados do desenho são inventados, então ele não serve para projeto nem para obra. Fornecido como está, sem garantia. Termos da biblioteca (CXL-1.0)
Este exemplo usa estes recursos
Os símbolos são blocos das nossas próprias bibliotecas, com os atributos preenchidos. A folha e o carimbo vêm do nosso modelo de carimbo ISO A3. Baixe-os para desenhar os seus próprios esquemas.
O que vem no ZIP
- Cable-Spreading-Room-Fire-Protection-Sample.dwg
Desenho de exemplo (DWG, formato AutoCAD 2018) - Process-Template-ISO-A3.dwt
Modelo (DWT) em que o desenho foi feito - CADXChange-Monochrome.ctb
Tabela de estilos de plotagem (CTB) que imprime todas as cores em preto - README.txt
README com a lista de layers e como usar os arquivos
O modelo
O modelo de processo tem 14 layers com cores, espessuras e tipos de linha (linhas principais, secundárias e de utilidades, sinais elétricos e pneumáticos, equipamentos, limites, setas de fluxo, tags, números de linha, texto e mais), os estilos de texto ISO-2.5 a ISO-5, o estilo de cota ISO-25 e um layout ISO A3 com carimbo e tabela de revisões. Os nomes dos layers seguem uma convenção comum, não uma norma; renomeie-os para combinar com as regras da sua empresa.
Layers definidos
Todos os layers do modelo com cor, espessura e tipo de linha, e quantos objetos deste exemplo estão em cada um. Os layers que o exemplo não usa continuam definidos, prontos para o seu desenho.
| Layer | Cor | Espessura | Tipo de linha | Uso | Objetos aqui |
|---|---|---|---|---|---|
| Layers de processo | |||||
| PROC-PIPE-MAIN | 5 | 0.50 mm | Continuous | Linhas principais de processo | 11 |
| PROC-PIPE-SEC | 4 | 0.35 mm | Continuous | Linhas de processo secundárias e derivações | 5 |
| PROC-PIPE-UTIL | 30 | 0.35 mm | Continuous | Linhas de utilidades (vapor, condensado, água de resfriamento, ar) | não usado aqui |
| PROC-SIGNAL | 3 | 0.18 mm | DASHED | Linhas de sinal elétrico | 31 |
| PROC-PNEU | 6 | 0.18 mm | DASHDOT | Linhas de sinal pneumático e capilar | não usado aqui |
| SYMBOL | 7 | 0.25 mm | Continuous | Símbolos (o layer que as bibliotecas de símbolos usam) | 31 |
| PROC-EQUIP | 7 | 0.35 mm | Continuous | Contornos de equipamentos desenhados fora das bibliotecas de símbolos | 21 |
| PROC-BOUNDARY | 1 | 0.18 mm | DASHDOT | Limites de pacote, skid e bateria | não usado aqui |
| PROC-FLOW | 7 | 0.18 mm | Continuous | Setas de fluxo e marcas de sentido de fluxo | 2 |
| PROC-TAG | 7 | 0.18 mm | Continuous | Tags de equipamentos e instrumentos | não usado aqui |
| PROC-LINE-NO | 7 | 0.18 mm | Continuous | Números de linha e especificações de linha | não usado aqui |
| PROC-TEXT | 7 | 0.18 mm | Continuous | Texto geral | 32 |
| PROC-NOTES | 7 | 0.18 mm | Continuous | Notas e legendas | 12 |
| PROC-DIM | 3 | 0.18 mm | Continuous | Cotas | não usado aqui |
| Layers de folha e de símbolos | |||||
| 0 | 7 | padrão | Continuous | Layer padrão, deixe vazio | não usado aqui |
| FRAME | 7 | padrão | Continuous | Borda da folha | 5 |
| TITLEBLOCK | 7 | padrão | Continuous | Carimbo e tabela de revisões | 1 |
| VIEWPORT | 8 | padrão | Continuous | Moldura da viewport do layout (não plota) | 2 |
| DRAWING-AREA | 8 | padrão | Continuous | Limite da área de desenho no modelo (não plota) | 2 |
Estilos definidos
Os estilos de texto, o estilo de cota e os tipos de linha que o modelo define, para você não precisar configurá-los em cada desenho novo.
| Tipo | Nome | Configurações |
|---|---|---|
| Estilo de texto | ISO | isocp.shx, 15°, altura variável |
| Estilo de texto | ISO-2.5 | isocp.shx, 15°, 2.5 mm de altura |
| Estilo de texto | ISO-3.5 | isocp.shx, 15°, 3.5 mm de altura |
| Estilo de texto | ISO-5 | isocp.shx, 15°, 5 mm de altura |
| Estilo de texto | TB-en | Arial, usada pelo carimbo |
| Estilo de cota | ISO-25 | Texto 2.5 mm, setas 2.5 mm, linhas de extensão 1.25 mm além da linha de cota e 0.625 mm do objeto, linhas de cota 3.75 mm entre si, 0 casas decimais |
| Tipo de linha | Continuous | Linha contínua |
| Tipo de linha | DASHED | Tracejada |
| Tipo de linha | DASHDOT | Traço-ponto |
| Tipo de linha | CENTER | Linha de centro |
| Tipo de linha | PHANTOM | Linha fantasma |
| Tipo de linha | HIDDEN | Linha oculta |
Configuração da folha e do desenho
Como a folha está configurada, para os seus desenhos serem impressos do mesmo jeito.
- Folha
- ISO A3 paisagem, 420 × 297 mm.
- Layout
- Um layout chamado ISO-A3, plotado em 1:1 em papel A3 sem margem, então a folha não tem margem de impressora.
- Borda
- 20 mm da borda esquerda (lado da encadernação) e 10 mm das outras bordas; a área de desenho interna é de 390 × 277 mm.
- Espaço modelo
- As unidades são milímetros. A área de desenho aparece em 1:1, então 1 mm no desenho é 1 mm no papel.
- Carimbo
- 160 × 79 mm no canto inferior direito, com uma tabela de revisões de quatro linhas acima dos campos de empresa, projeto, título e aprovação.
- Tamanho do texto
- 2,5 mm para rótulos e notas, 3,5 mm e 5 mm para títulos.
- Escala do tipo de linha
- 1, então os traços são dimensionados para plotar em 1:1.
- Estilo de plotagem
- Nenhum definido. Escolha o CTB do ZIP na configuração de página para plotagens em preto e branco.
Campos do carimbo
Os atributos do carimbo.
| Atributo | Campo na folha | Valor neste exemplo |
|---|---|---|
| COMPANY | COMPANY | CADXChange |
| PROJECT | PROJECT | Power Plant |
| AREA | AREA | Cable spreading room |
| SYSTEM | SYSTEM | Fire protection |
| CLIENT | CLIENT | Sample |
| TITLE | DRAWING TITLE | Cable spreading room fire protection |
| DRAWING_NO | DRAWING NO. | F-503 |
| CONTRACT_NO | CONTRACT NO. | — |
| REV | REV | A |
| DRAWN | DRAWN | — |
| CHECKED | CHECKED | — |
| APPROVED | APPROVED | — |
| DATE | DATE | 2026-11-25 |
| SCALE | SCALE | NTS |
| SHEET | SHEET | 1 |
| SHEET_OF | OF | 1 |
Tabela de revisões: R1 a R4, cada uma com REV, DATA, DESCRIÇÃO e POR (16 atributos, vazios neste exemplo).
Blocos no desenho
A lista de equipamentos do desenho: nome do bloco, símbolo e quantas vezes foi inserido.
| Símbolo | Bloco | Inseridos |
|---|---|---|
| PFP_SAMPLING_POINT | 4 | |
| PFP_CABLE_SEAL | 3 | |
| PFP_NOZZLE_360 | 3 | |
| PFP_LHC | 2 | |
| PFP_SMOKE_MULTI | 2 | |
| PFP_BANK_8 | 1 | |
| PFP_SOLENOID | 1 | |
| PFP_MOD_SOLENOID | 1 | |
| PFP_CHECK_MANIFOLD | 1 | |
| PFP_DISCH_PS | 1 | |
| PFP_PIPE_SEAL | 1 | |
| PFP_ASPIRATING | 1 | |
| PFP_DOOR_DOUBLE | 1 | |
| PFP_RELIEF_VENT | 1 | |
| PFP_RELEASE_PANEL | 1 | |
| PFP_TIME_DELAY | 1 | |
| PFP_PREDISCH_ALARM | 1 | |
| PFP_DOOR_HOLD | 1 | |
| PFP_AGENT_LAMP | 1 | |
| PFP_FIRE_DAMPER | 1 | |
| PFP_MANUAL_RELEASE | 1 | |
| PFP_ABORT | 1 |
Lista de equipamentos
Uma linha por símbolo inserido, lida dos atributos dos blocos do desenho: o que aparece na folha e os atributos da lista que foram preenchidos mas não aparecem.
| Tag | Descrição | Mostrado na folha | Preenchido, não mostrado |
|---|---|---|---|
| CS-1 | Cable penetration sealPFP_CABLE_SEAL | RATING_H = 2PENETRANT = Cable traySIZE_MM = 600 x 100SEAL_SYSTEM = Intumescent mortarZONE = Transformer areaLOCATION = Transformer area | |
| CS-2 | Cable penetration sealPFP_CABLE_SEAL | RATING_H = 2PENETRANT = Cable traySIZE_MM = 600 x 100SEAL_SYSTEM = Intumescent mortarZONE = Transformer areaLOCATION = Transformer area | |
| CB-1 | Cylinder bank, 8PFP_BANK_8 | AGENT = HFC-227eaFILL_KG = 8 x 90VOLUME_L = 8 x 120PRESSURE_BAR = 42DISCHARGE_S = 10ZONE = Transformer areaLOCATION = Transformer area | |
| SOL-1 | Release solenoidPFP_SOLENOID | ADDRESS = -LOOP = -ZONE = Transformer areaFUNCTION = Releases the pilot cylinderVOLTAGE_V = 24CIRCUIT = Release circuit 1LOCATION = Transformer area | |
| SCM-1 | Solenoid control modulePFP_MOD_SOLENOID | ADDRESS = 213LOOP = 1ZONE = Transformer areaFUNCTION = Drives the release solenoidVOLTAGE_V = 24CIRCUIT = Release circuit 1LOCATION = Transformer area | |
| CM-1 | Check valve, manifoldPFP_CHECK_MANIFOLD | SIZE_DN = 80PRESSURE_RATING = PN63ACTUATION = Spring returnSERVICE = Clean agentMATERIAL = SteelSUPERVISED = NoZONE = Transformer area | |
| DPS-1 | Discharge pressure switchPFP_DISCH_PS | SETTING = 5 barCONTACTS = 1 NOENCLOSURE = IP65SERVICE = Agent discharge feedbackZONE = Transformer areaLOOP = 1ADDRESS = 212 | |
| PS-1 | Pipe penetration sealPFP_PIPE_SEAL | RATING_H = 2PENETRANT = Steel pipe DN80SIZE_MM = DN80SEAL_SYSTEM = Intumescent collarZONE = Transformer areaLOCATION = Transformer area | |
| NZ-1 | Discharge nozzle, 360PFP_NOZZLE_360 | AGENT = HFC-227eaFLOW_KGS = 5ORIFICE_MM = 8COVERAGE_M2 = 50MOUNTING = CeilingZONE = Transformer area | |
| NZ-2 | Discharge nozzle, 360PFP_NOZZLE_360 | AGENT = HFC-227eaFLOW_KGS = 5ORIFICE_MM = 8COVERAGE_M2 = 50MOUNTING = CeilingZONE = Transformer area | |
| NZ-3 | Discharge nozzle, 360PFP_NOZZLE_360 | AGENT = HFC-227eaFLOW_KGS = 5ORIFICE_MM = 8COVERAGE_M2 = 50MOUNTING = CeilingZONE = Transformer area | |
| ASP-1 | Aspirating unitPFP_ASPIRATING | DETECTOR_TYPE = Aspirating smokeZONE = Transformer areaLOOP = 1ADDRESS = 205COVERAGE_M2 = 600MOUNTING = WallRESPONSE = Under 60 sENCLOSURE = IP54 | |
| SP-1 | Sampling pointPFP_SAMPLING_POINT | DETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = - | |
| SP-2 | Sampling pointPFP_SAMPLING_POINT | DETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = - | |
| SP-3 | Sampling pointPFP_SAMPLING_POINT | DETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = - | |
| SP-4 | Sampling pointPFP_SAMPLING_POINT | DETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = - | |
| LH-1 | Linear heat cablePFP_LHC | CABLE_TYPE = Digital linear heatLENGTH_M = 40ALARM_TEMP_C = 70ZONE = Transformer areaLOOP = 1ADDRESS = 201MOUNTING = Clipped along the tray | |
| LH-2 | Linear heat cablePFP_LHC | CABLE_TYPE = Digital linear heatLENGTH_M = 40ALARM_TEMP_C = 70ZONE = Transformer areaLOOP = 1ADDRESS = 201MOUNTING = Clipped along the tray | |
| SD-1 | Smoke detector, multi-criteriaPFP_SMOKE_MULTI | DETECTOR_TYPE = Multi-criteria smokeZONE = Transformer areaLOOP = 1ADDRESS = 202COVERAGE_M2 = 40MOUNTING = CeilingRESPONSE = Under 30 sENCLOSURE = IP40 | |
| SD-2 | Smoke detector, multi-criteriaPFP_SMOKE_MULTI | DETECTOR_TYPE = Multi-criteria smokeZONE = Transformer areaLOOP = 1ADDRESS = 202COVERAGE_M2 = 40MOUNTING = CeilingRESPONSE = Under 30 sENCLOSURE = IP40 | |
| CS-3 | Cable penetration sealPFP_CABLE_SEAL | RATING_H = 2PENETRANT = Cable traySIZE_MM = 600 x 100SEAL_SYSTEM = Intumescent mortarZONE = Transformer areaLOCATION = Transformer area | |
| DR-1 | Fire door, doublePFP_DOOR_DOUBLE | RATING_H = 2MATERIAL = SteelTHICKNESS_MM = 60TEST_STANDARD = Local codeLOCATION = Transformer areaZONE = Transformer area | |
| RV-1 | Pressure relief ventPFP_RELIEF_VENT | ZONE = Transformer areaLOCATION = Transformer area | |
| RP-1 | Releasing control panelPFP_RELEASE_PANEL | ZONES = 2LOOPS = 1SUPPLY_V = 24 V DCBATTERY_AH = 12COMMUNICATION = Hardwired to FACP-1LOCATION = Fire control roomADDRESS_RANGE = - | |
| TD-1 | Time delayPFP_TIME_DELAY | ADDRESS = -LOOP = -ZONE = Transformer areaFUNCTION = Pre-discharge delay, 30 sVOLTAGE_V = 24CIRCUIT = Release circuit 1LOCATION = Transformer area | |
| PD-1 | Pre-discharge horn, strobePFP_PREDISCH_ALARM | SOUND_DB = 100CANDELA = 75VOLTAGE_V = 24MOUNTING = CeilingCIRCUIT = Sounder circuit 1ZONE = Transformer areaENCLOSURE = IP54 | |
| DH-1 | Door hold-openPFP_DOOR_HOLD | ADDRESS = -LOOP = -ZONE = Transformer areaFUNCTION = Releases the door on alarmVOLTAGE_V = 24CIRCUIT = Door circuit 1LOCATION = Transformer area | |
| AL-1 | Agent released lampPFP_AGENT_LAMP | SOUND_DB = -CANDELA = -VOLTAGE_V = 24MOUNTING = Above the doorCIRCUIT = Lamp circuit 1ZONE = Transformer areaENCLOSURE = IP54 | |
| FD-1 | Fire damperPFP_FIRE_DAMPER | RATING_H = 2SIZE_MM = 600 x 400ACTUATION = Motorised, closes on releaseRELEASE_TEMP_C = 72ZONE = Transformer areaLOCATION = Transformer area | |
| MR-1 | Manual release stationPFP_MANUAL_RELEASE | TYPE = Break glass, dual actionZONE = Transformer areaLOOP = 1ADDRESS = 210ENCLOSURE = IP54MOUNTING_HEIGHT_M = 1.4FUNCTION = Starts the discharge sequence | |
| AB-1 | Abort switchPFP_ABORT | TYPE = Hold-to-runZONE = Transformer areaLOOP = 1ADDRESS = 211ENCLOSURE = IP54MOUNTING_HEIGHT_M = 1.4FUNCTION = Holds the time delay |
Fabricante, modelo e observações ficam vazios em todos os blocos, prontos para os seus dados. Os valores são exemplos.
Como usar
- Abra o desenho de exemplo para ver como layers, textos e o carimbo são usados, ou abra antes no navegador, sem instalar nada.
- Comece o seu desenho a partir do modelo (NOVO, depois escolha o arquivo DWT). Copie o arquivo CTB para a sua pasta de estilos de plotagem se quiser plotagens em preto e branco.
- Insira blocos da biblioteca de símbolos no seu desenho. Os blocos do exemplo são cópias; eles não mudam quando uma biblioteca muda.
Perguntas frequentes
- Posso usar o desenho em um projeto real?
- Como ponto de partida para a organização e os layers, sim. As potências, os ajustes e as bitolas de cabo são inventados, então o esquema precisa ser conferido e adaptado ao seu projeto antes de ser usado em projeto ou obra.
- Por que os layers têm cores?
- As cores e as espessuras seguem os layers: os circuitos de potência são vermelhos e grossos, o comando é ciano, o sinal é verde. A tabela de estilos de plotagem do ZIP imprime tudo em preto e mantém as espessuras, então também dá para plotar em preto e branco.
- Quais programas de CAD abrem o arquivo?
- O desenho e o modelo estão no formato do AutoCAD 2018, que o AutoCAD 2018 e posteriores abrem, assim como outros programas de CAD que leem esse formato. O visualizador no navegador não exige nenhuma instalação.