Switchboard arc flash protection and PD monitoring: sample DWG

The arc flash protection and partial discharge monitoring of an 11 kV switchboard. Four panels, an incomer, two feeders and a bus section, each have a busbar, a breaker and a cable compartment with its own zone mark and light sensor. The twelve sensor fibres are grouped into four channels on the arc flash relay. The relay trips the incomer and the bus section only when the current check from the incomer sees an overcurrent, and a mark shows the light-only mode used for tests. Below the panels one earth voltage sensor per panel feeds a partial discharge host, which reports through a gateway to SCADA. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Grátis para usar e modificar nos seus próprios projetos, inclusive comerciais. O ZIP traz o desenho de exemplo, um modelo, uma tabela de estilos de plotagem e um README; não precisa de nenhum add-in. Os dados do desenho são inventados, então ele não serve para projeto nem para obra. Fornecido como está, sem garantia. Termos da biblioteca (CXL-1.0)

Este exemplo usa estes recursos

Os símbolos são blocos das nossas próprias bibliotecas, com os atributos preenchidos. A folha e o carimbo vêm do nosso modelo de carimbo ISO A3. Baixe-os para desenhar os seus próprios esquemas.

O que vem no ZIP

  • Switchboard-Arc-Flash-Monitoring-Sample.dwg
    Desenho de exemplo (DWG, formato AutoCAD 2018)
  • Process-Template-ISO-A3.dwt
    Modelo (DWT) em que o desenho foi feito
  • CADXChange-Monochrome.ctb
    Tabela de estilos de plotagem (CTB) que imprime todas as cores em preto
  • README.txt
    README com a lista de layers e como usar os arquivos

O modelo

O modelo de processo tem 14 layers com cores, espessuras e tipos de linha (linhas principais, secundárias e de utilidades, sinais elétricos e pneumáticos, equipamentos, limites, setas de fluxo, tags, números de linha, texto e mais), os estilos de texto ISO-2.5 a ISO-5, o estilo de cota ISO-25 e um layout ISO A3 com carimbo e tabela de revisões. Os nomes dos layers seguem uma convenção comum, não uma norma; renomeie-os para combinar com as regras da sua empresa.

Layers definidos

Todos os layers do modelo com cor, espessura e tipo de linha, e quantos objetos deste exemplo estão em cada um. Os layers que o exemplo não usa continuam definidos, prontos para o seu desenho.

LayerCorEspessuraTipo de linhaUsoObjetos aqui
Layers de processo
PROC-PIPE-MAIN50.50 mmContinuousLinhas principais de processo3
PROC-PIPE-SEC40.35 mmContinuousLinhas de processo secundárias e derivações51
PROC-PIPE-UTIL300.35 mmContinuousLinhas de utilidades (vapor, condensado, água de resfriamento, ar)não usado aqui
PROC-SIGNAL30.18 mmDASHEDLinhas de sinal elétrico14
PROC-PNEU60.18 mmDASHDOTLinhas de sinal pneumático e capilarnão usado aqui
SYMBOL70.25 mmContinuousSímbolos (o layer que as bibliotecas de símbolos usam)35
PROC-EQUIP70.35 mmContinuousContornos de equipamentos desenhados fora das bibliotecas de símbolos24
PROC-BOUNDARY10.18 mmDASHDOTLimites de pacote, skid e baterianão usado aqui
PROC-FLOW70.18 mmContinuousSetas de fluxo e marcas de sentido de fluxo1
PROC-TAG70.18 mmContinuousTags de equipamentos e instrumentosnão usado aqui
PROC-LINE-NO70.18 mmContinuousNúmeros de linha e especificações de linhanão usado aqui
PROC-TEXT70.18 mmContinuousTexto geral40
PROC-NOTES70.18 mmContinuousNotas e legendas12
PROC-DIM30.18 mmContinuousCotasnão usado aqui
Layers de folha e de símbolos
07padrãoContinuousLayer padrão, deixe vazionão usado aqui
FRAME7padrãoContinuousBorda da folha5
TITLEBLOCK7padrãoContinuousCarimbo e tabela de revisões1
VIEWPORT8padrãoContinuousMoldura da viewport do layout (não plota)2
DRAWING-AREA8padrãoContinuousLimite da área de desenho no modelo (não plota)2

Estilos definidos

Os estilos de texto, o estilo de cota e os tipos de linha que o modelo define, para você não precisar configurá-los em cada desenho novo.

TipoNomeConfigurações
Estilo de textoISOisocp.shx, 15°, altura variável
Estilo de textoISO-2.5isocp.shx, 15°, 2.5 mm de altura
Estilo de textoISO-3.5isocp.shx, 15°, 3.5 mm de altura
Estilo de textoISO-5isocp.shx, 15°, 5 mm de altura
Estilo de textoTB-enArial, usada pelo carimbo
Estilo de cotaISO-25Texto 2.5 mm, setas 2.5 mm, linhas de extensão 1.25 mm além da linha de cota e 0.625 mm do objeto, linhas de cota 3.75 mm entre si, 0 casas decimais
Tipo de linhaContinuousLinha contínua
Tipo de linhaDASHEDTracejada
Tipo de linhaDASHDOTTraço-ponto
Tipo de linhaCENTERLinha de centro
Tipo de linhaPHANTOMLinha fantasma
Tipo de linhaHIDDENLinha oculta

Configuração da folha e do desenho

Como a folha está configurada, para os seus desenhos serem impressos do mesmo jeito.

Folha
ISO A3 paisagem, 420 × 297 mm.
Layout
Um layout chamado ISO-A3, plotado em 1:1 em papel A3 sem margem, então a folha não tem margem de impressora.
Borda
20 mm da borda esquerda (lado da encadernação) e 10 mm das outras bordas; a área de desenho interna é de 390 × 277 mm.
Espaço modelo
As unidades são milímetros. A área de desenho aparece em 1:1, então 1 mm no desenho é 1 mm no papel.
Carimbo
160 × 79 mm no canto inferior direito, com uma tabela de revisões de quatro linhas acima dos campos de empresa, projeto, título e aprovação.
Tamanho do texto
2,5 mm para rótulos e notas, 3,5 mm e 5 mm para títulos.
Escala do tipo de linha
1, então os traços são dimensionados para plotar em 1:1.
Estilo de plotagem
Nenhum definido. Escolha o CTB do ZIP na configuração de página para plotagens em preto e branco.

Campos do carimbo

Os atributos do carimbo.

AtributoCampo na folhaValor neste exemplo
COMPANYCOMPANYCADXChange
PROJECTPROJECT11 kV Switchboard S1
AREAAREASwitch room
SYSTEMSYSTEMCondition monitoring
CLIENTCLIENTSample
TITLEDRAWING TITLESwitchboard arc flash and PD monitoring
DRAWING_NODRAWING NO.M-502
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Tabela de revisões: R1 a R4, cada uma com REV, DATA, DESCRIÇÃO e POR (16 atributos, vazios neste exemplo).

Blocos no desenho

A lista de equipamentos do desenho: nome do bloco, símbolo e quantas vezes foi inserido.

SímboloBlocoInseridos
Arc point sensorPMN_ARC_POINT12
Busbar compartment zonePMN_ARC_ZONE_BUS4
Breaker compartment zonePMN_ARC_ZONE_CB4
Cable compartment zonePMN_ARC_ZONE_CABLE4
Partial discharge, TEVPMN_SG_PD_TEV4
Trip outputPMN_ARC_TRIP_OUT2
Arc flash relayPMN_ARC_RELAY1
Current check inputPMN_ARC_CT_INPUT1
Light-only mode markPMN_ARC_LIGHT_ONLY1
Partial discharge hostPMN_SG_PD_HOST1
Edge gatewayPMN_SYS_EDGE_GW1

Lista de equipamentos

Uma linha por símbolo inserido, lida dos atributos dos blocos do desenho: o que aparece na folha e os atributos da lista que foram preenchidos mas não aparecem.

TagDescriçãoMostrado na folhaPreenchido, não mostrado
BB-1Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-1Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 1
CB-1Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-2Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 2
CC-1Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-3Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 3
BB-2Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-4Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 4
CB-2Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-5Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 5
CC-2Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-6Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 6
BB-3Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-7Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 7
CB-3Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-8Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 8
CC-3Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-9Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 9
BB-4Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-10Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 10
CB-4Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-11Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 11
CC-4Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-12Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 12
AFR-1Arc flash relayPMN_ARC_RELAYSENSITIVITY_LUX = -TRIP_TIME_MS = 7COMPARTMENT = All panelsOUTPUT = 2 trip, 1 alarmCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 13
CI-1Current check inputPMN_ARC_CT_INPUTSENSITIVITY_LUX = -TRIP_TIME_MS = -COMPARTMENT = IncomerOUTPUT = Current checkCURRENT_CHECK = 2.5 x InLOCATION = 11 kV switchboard S1ADDRESS = 14
TO-1Trip outputPMN_ARC_TRIP_OUTSENSITIVITY_LUX = -TRIP_TIME_MS = 3COMPARTMENT = Q1 and Q3OUTPUT = Trip coil, 110 V DCCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 15
TO-2Trip outputPMN_ARC_TRIP_OUTSENSITIVITY_LUX = -TRIP_TIME_MS = 3COMPARTMENT = Q1 and Q3OUTPUT = Trip coil, 110 V DCCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 16
LO-1Light-only mode markPMN_ARC_LIGHT_ONLYSENSITIVITY_LUX = -TRIP_TIME_MS = -COMPARTMENT = All panelsOUTPUT = Alarm onlyCURRENT_CHECK = NoLOCATION = 11 kV switchboard S1ADDRESS = 17
PDT-1Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 18
PDT-2Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 19
PDT-3Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 20
PDT-4Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 21
PDH-1Partial discharge hostPMN_SG_PD_HOSTCHANNELS = 8SUPPLY_V = 24 V DCCOMMUNICATION = EthernetOUTPUTS = 2MOUNTING = WallLOCATION = 11 kV switchboard S1ADDRESS = 22
EG-1Edge gatewayPMN_SYS_EDGE_GWFUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = 11 kV switchboard S1ADDRESS = 23

Fabricante, modelo e observações ficam vazios em todos os blocos, prontos para os seus dados. Os valores são exemplos.

Como usar

  1. Abra o desenho de exemplo para ver como layers, textos e o carimbo são usados, ou abra antes no navegador, sem instalar nada.
  2. Comece o seu desenho a partir do modelo (NOVO, depois escolha o arquivo DWT). Copie o arquivo CTB para a sua pasta de estilos de plotagem se quiser plotagens em preto e branco.
  3. Insira blocos da biblioteca de símbolos no seu desenho. Os blocos do exemplo são cópias; eles não mudam quando uma biblioteca muda.

Perguntas frequentes

Posso usar o desenho em um projeto real?
Como ponto de partida para a organização e os layers, sim. As potências, os ajustes e as bitolas de cabo são inventados, então o esquema precisa ser conferido e adaptado ao seu projeto antes de ser usado em projeto ou obra.
Por que os layers têm cores?
As cores e as espessuras seguem os layers: os circuitos de potência são vermelhos e grossos, o comando é ciano, o sinal é verde. A tabela de estilos de plotagem do ZIP imprime tudo em preto e mantém as espessuras, então também dá para plotar em preto e branco.
Quais programas de CAD abrem o arquivo?
O desenho e o modelo estão no formato do AutoCAD 2018, que o AutoCAD 2018 e posteriores abrem, assim como outros programas de CAD que leem esse formato. O visualizador no navegador não exige nenhuma instalação.