Transformer online monitoring system: sample DWG of a system diagram
The online monitoring of one power transformer, drawn as a system diagram. At field level fourteen sensors sit on the transformer: dissolved gas, moisture, partial discharge by UHF and acoustic methods, bushings, winding and top oil temperature, tap changer, cooling, oil level, gas relay, pressure relief, vibration and core earth current. Four collectors bring their signals to the monitoring IED. At station level the IED reaches a switch, a GPS time source, an edge gateway to SCADA, a server and a workstation, lights an alarm beacon, and sends a hard-wired alarm contact to the fire alarm panel. A legend, the three alarm level marks, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.
Grátis para usar e modificar nos seus próprios projetos, inclusive comerciais. O ZIP traz o desenho de exemplo, um modelo, uma tabela de estilos de plotagem e um README; não precisa de nenhum add-in. Os dados do desenho são inventados, então ele não serve para projeto nem para obra. Fornecido como está, sem garantia. Termos da biblioteca (CXL-1.0)
Este exemplo usa estes recursos
Os símbolos são blocos das nossas próprias bibliotecas, com os atributos preenchidos. A folha e o carimbo vêm do nosso modelo de carimbo ISO A3. Baixe-os para desenhar os seus próprios esquemas.
O que vem no ZIP
- Transformer-Online-Monitoring-System-Sample.dwg
Desenho de exemplo (DWG, formato AutoCAD 2018) - Process-Template-ISO-A3.dwt
Modelo (DWT) em que o desenho foi feito - CADXChange-Monochrome.ctb
Tabela de estilos de plotagem (CTB) que imprime todas as cores em preto - README.txt
README com a lista de layers e como usar os arquivos
O modelo
O modelo de processo tem 14 layers com cores, espessuras e tipos de linha (linhas principais, secundárias e de utilidades, sinais elétricos e pneumáticos, equipamentos, limites, setas de fluxo, tags, números de linha, texto e mais), os estilos de texto ISO-2.5 a ISO-5, o estilo de cota ISO-25 e um layout ISO A3 com carimbo e tabela de revisões. Os nomes dos layers seguem uma convenção comum, não uma norma; renomeie-os para combinar com as regras da sua empresa.
Layers definidos
Todos os layers do modelo com cor, espessura e tipo de linha, e quantos objetos deste exemplo estão em cada um. Os layers que o exemplo não usa continuam definidos, prontos para o seu desenho.
| Layer | Cor | Espessura | Tipo de linha | Uso | Objetos aqui |
|---|---|---|---|---|---|
| Layers de processo | |||||
| PROC-PIPE-MAIN | 5 | 0.50 mm | Continuous | Linhas principais de processo | 9 |
| PROC-PIPE-SEC | 4 | 0.35 mm | Continuous | Linhas de processo secundárias e derivações | não usado aqui |
| PROC-PIPE-UTIL | 30 | 0.35 mm | Continuous | Linhas de utilidades (vapor, condensado, água de resfriamento, ar) | não usado aqui |
| PROC-SIGNAL | 3 | 0.18 mm | DASHED | Linhas de sinal elétrico | 30 |
| PROC-PNEU | 6 | 0.18 mm | DASHDOT | Linhas de sinal pneumático e capilar | não usado aqui |
| SYMBOL | 7 | 0.25 mm | Continuous | Símbolos (o layer que as bibliotecas de símbolos usam) | 26 |
| PROC-EQUIP | 7 | 0.35 mm | Continuous | Contornos de equipamentos desenhados fora das bibliotecas de símbolos | não usado aqui |
| PROC-BOUNDARY | 1 | 0.18 mm | DASHDOT | Limites de pacote, skid e bateria | 2 |
| PROC-FLOW | 7 | 0.18 mm | Continuous | Setas de fluxo e marcas de sentido de fluxo | 1 |
| PROC-TAG | 7 | 0.18 mm | Continuous | Tags de equipamentos e instrumentos | não usado aqui |
| PROC-LINE-NO | 7 | 0.18 mm | Continuous | Números de linha e especificações de linha | não usado aqui |
| PROC-TEXT | 7 | 0.18 mm | Continuous | Texto geral | 33 |
| PROC-NOTES | 7 | 0.18 mm | Continuous | Notas e legendas | 13 |
| PROC-DIM | 3 | 0.18 mm | Continuous | Cotas | não usado aqui |
| Layers de folha e de símbolos | |||||
| 0 | 7 | padrão | Continuous | Layer padrão, deixe vazio | não usado aqui |
| FRAME | 7 | padrão | Continuous | Borda da folha | 5 |
| TITLEBLOCK | 7 | padrão | Continuous | Carimbo e tabela de revisões | 1 |
| VIEWPORT | 8 | padrão | Continuous | Moldura da viewport do layout (não plota) | 2 |
| DRAWING-AREA | 8 | padrão | Continuous | Limite da área de desenho no modelo (não plota) | 2 |
Estilos definidos
Os estilos de texto, o estilo de cota e os tipos de linha que o modelo define, para você não precisar configurá-los em cada desenho novo.
| Tipo | Nome | Configurações |
|---|---|---|
| Estilo de texto | ISO | isocp.shx, 15°, altura variável |
| Estilo de texto | ISO-2.5 | isocp.shx, 15°, 2.5 mm de altura |
| Estilo de texto | ISO-3.5 | isocp.shx, 15°, 3.5 mm de altura |
| Estilo de texto | ISO-5 | isocp.shx, 15°, 5 mm de altura |
| Estilo de texto | TB-en | Arial, usada pelo carimbo |
| Estilo de cota | ISO-25 | Texto 2.5 mm, setas 2.5 mm, linhas de extensão 1.25 mm além da linha de cota e 0.625 mm do objeto, linhas de cota 3.75 mm entre si, 0 casas decimais |
| Tipo de linha | Continuous | Linha contínua |
| Tipo de linha | DASHED | Tracejada |
| Tipo de linha | DASHDOT | Traço-ponto |
| Tipo de linha | CENTER | Linha de centro |
| Tipo de linha | PHANTOM | Linha fantasma |
| Tipo de linha | HIDDEN | Linha oculta |
Configuração da folha e do desenho
Como a folha está configurada, para os seus desenhos serem impressos do mesmo jeito.
- Folha
- ISO A3 paisagem, 420 × 297 mm.
- Layout
- Um layout chamado ISO-A3, plotado em 1:1 em papel A3 sem margem, então a folha não tem margem de impressora.
- Borda
- 20 mm da borda esquerda (lado da encadernação) e 10 mm das outras bordas; a área de desenho interna é de 390 × 277 mm.
- Espaço modelo
- As unidades são milímetros. A área de desenho aparece em 1:1, então 1 mm no desenho é 1 mm no papel.
- Carimbo
- 160 × 79 mm no canto inferior direito, com uma tabela de revisões de quatro linhas acima dos campos de empresa, projeto, título e aprovação.
- Tamanho do texto
- 2,5 mm para rótulos e notas, 3,5 mm e 5 mm para títulos.
- Escala do tipo de linha
- 1, então os traços são dimensionados para plotar em 1:1.
- Estilo de plotagem
- Nenhum definido. Escolha o CTB do ZIP na configuração de página para plotagens em preto e branco.
Campos do carimbo
Os atributos do carimbo.
| Atributo | Campo na folha | Valor neste exemplo |
|---|---|---|
| COMPANY | COMPANY | CADXChange |
| PROJECT | PROJECT | 220 kV Substation |
| AREA | AREA | Transformer area |
| SYSTEM | SYSTEM | Condition monitoring |
| CLIENT | CLIENT | Sample |
| TITLE | DRAWING TITLE | Transformer online monitoring system |
| DRAWING_NO | DRAWING NO. | M-501 |
| CONTRACT_NO | CONTRACT NO. | — |
| REV | REV | A |
| DRAWN | DRAWN | — |
| CHECKED | CHECKED | — |
| APPROVED | APPROVED | — |
| DATE | DATE | 2026-11-25 |
| SCALE | SCALE | NTS |
| SHEET | SHEET | 1 |
| SHEET_OF | OF | 1 |
Tabela de revisões: R1 a R4, cada uma com REV, DATA, DESCRIÇÃO e POR (16 atributos, vazios neste exemplo).
Blocos no desenho
A lista de equipamentos do desenho: nome do bloco, símbolo e quantas vezes foi inserido.
| Símbolo | Bloco | Inseridos |
|---|---|---|
| PMN_TR_MONITORED | 1 | |
| PMN_TR_DGA_MULTI | 1 | |
| PMN_TR_MOISTURE | 1 | |
| PMN_TR_PD_UHF | 1 | |
| PMN_TR_PD_AE | 1 | |
| PMN_TR_BUSHING | 1 | |
| PMN_TR_WINDING_FO | 1 | |
| PMN_TR_TOP_OIL_TEMP | 1 | |
| PMN_TR_COOLING | 1 | |
| PMN_TR_OLTC | 1 | |
| PMN_TR_OIL_LEVEL | 1 | |
| PMN_TR_BUCHHOLZ | 1 | |
| PMN_TR_PRV_MON | 1 | |
| PMN_TR_VIBRATION | 1 | |
| PMN_TR_CORE_GND | 1 | |
| PMN_TR_IED | 1 | |
| PMN_SYS_BEACON | 1 | |
| PMN_SYS_SWITCH | 1 | |
| PMN_SYS_TIME_SYNC | 1 | |
| PMN_SYS_EDGE_GW | 1 | |
| PMN_SYS_WORKSTATION | 1 | |
| PMN_SYS_SERVER | 1 | |
| PFP_FACP | 1 | |
| PMN_LEVEL_WARNING | 1 | |
| PMN_LEVEL_ALARM | 1 | |
| PMN_LEVEL_TRIP | 1 |
Lista de equipamentos
Uma linha por símbolo inserido, lida dos atributos dos blocos do desenho: o que aparece na folha e os atributos da lista que foram preenchidos mas não aparecem.
| Tag | Descrição | Mostrado na folha | Preenchido, não mostrado |
|---|---|---|---|
| T1 | Transformer, monitoredPMN_TR_MONITORED | TYPE = Power transformerRATING = 180 MVA, 220/110 kVLOCATION = Transformer T1 areaADDRESS = - | |
| DGA-1 | Oil gas monitor, multi-gasPMN_TR_DGA_MULTI | GAS = H2, CO, CH4, C2H2, C2H4, C2H6RANGE = H2 5-2000 ppmALARM_1 = H2 100 ppmALARM_2 = C2H2 5 ppmOUTPUT = IEC 61850, 4-20 mALOCATION = Transformer T1 areaADDRESS = 1 | |
| MST-1 | Oil moisture sensorPMN_TR_MOISTURE | MEASURAND = Moisture in oilRANGE = 0-100 % RSALARM_1 = 20 % RSALARM_2 = 30 % RSOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 2 | |
| PDU-1 | Partial discharge, UHFPMN_TR_PD_UHF | METHOD = UHFFREQUENCY_BAND = 300-1500 MHzSENSITIVITY_PC = 5CHANNELS = 2OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 3 | |
| PDA-1 | Partial discharge, acousticPMN_TR_PD_AE | METHOD = AcousticFREQUENCY_BAND = 20-300 kHzSENSITIVITY_PC = 10CHANNELS = 4OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 4 | |
| BSH-1 | Bushing monitorPMN_TR_BUSHING | MEASURAND = Capacitance and tan deltaRANGE = tan delta 0-2 %ALARM_1 = 0.7 %ALARM_2 = 1.0 %OUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 5 | |
| WT-1 | Winding temp, fibre opticPMN_TR_WINDING_FO | RANGE_C = 0-200ALARM_C = 110SENSOR_TYPE = Fibre opticOUTPUT = RS-485MONITORED_ITEM = HV winding hot spotLOCATION = Transformer T1 areaADDRESS = 6 | |
| OT-1 | Top oil temperaturePMN_TR_TOP_OIL_TEMP | RANGE_C = -20-120ALARM_C = 85SENSOR_TYPE = PT100OUTPUT = 4-20 mAMONITORED_ITEM = Top oilLOCATION = Transformer T1 areaADDRESS = 7 | |
| CL-1 | Cooler status monitorPMN_TR_COOLING | MEASURAND = Fan and pump statusRANGE = -ALARM_1 = Fan faultALARM_2 = Pump faultOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 8 | |
| OLTC-1 | Tap changer monitorPMN_TR_OLTC | MEASURAND = Motor current and positionRANGE = 0-5 AALARM_1 = 3.5 AALARM_2 = 4.5 AOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 9 | |
| OL-1 | Oil level monitorPMN_TR_OIL_LEVEL | MEASURAND = Conservator oil levelRANGE = 0-100 %ALARM_1 = 20 %ALARM_2 = 10 %OUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 10 | |
| BR-1 | Gas relay monitorPMN_TR_BUCHHOLZ | MEASURAND = Gas relay alarm and tripRANGE = -ALARM_1 = Gas collectedALARM_2 = Oil surgeOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 11 | |
| PR-1 | Pressure relief monitorPMN_TR_PRV_MON | MEASURAND = Pressure relief deviceRANGE = -ALARM_1 = -ALARM_2 = OperatedOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 12 | |
| VB-1 | Vibration sensorPMN_TR_VIBRATION | MEASURAND = Tank vibrationRANGE = 0-50 mm/sALARM_1 = 15 mm/sALARM_2 = 25 mm/sOUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 13 | |
| CG-1 | Core ground currentPMN_TR_CORE_GND | RATIO = 1000:1ACCURACY = 1INNER_DIAMETER_MM = 60CIRCUIT = Core earth strapTYPE = Split coreLOCATION = Transformer T1 area | |
| IED-1 | Transformer monitoring IEDPMN_TR_IED | CHANNELS = 24SUPPLY_V = 110 V DCCOMMUNICATION = IEC 61850OUTPUTS = 4MOUNTING = Marshalling kioskLOCATION = Transformer T1 areaADDRESS = 14 | |
| AB-1 | Alarm beacon columnPMN_SYS_BEACON | FUNCTION = Local alarm beaconPORTS = 1SUPPLY_V = 24 V DCPROTOCOL = Dry contactMOUNTING = PoleLOCATION = Transformer T1 areaADDRESS = 15 | |
| SW-1 | Network switchPMN_SYS_SWITCH | FUNCTION = Ethernet switchPORTS = 8SUPPLY_V = 24 V DCPROTOCOL = IEC 61850MOUNTING = DIN railLOCATION = Transformer T1 areaADDRESS = 16 | |
| TS-1 | Time synchronisationPMN_SYS_TIME_SYNC | FUNCTION = GPS time sourcePORTS = 2SUPPLY_V = 24 V DCPROTOCOL = PTP, IRIG-BMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 17 | |
| EG-1 | Edge gatewayPMN_SYS_EDGE_GW | FUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 18 | |
| WS-1 | Monitoring workstationPMN_SYS_WORKSTATION | FUNCTION = Operator workstationPORTS = 2SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = DeskLOCATION = Transformer T1 areaADDRESS = 19 | |
| SV-1 | ServerPMN_SYS_SERVER | FUNCTION = Monitoring serverPORTS = 4SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 20 | |
| FACP-1 | Fire alarm control panelPFP_FACP | ZONES = 8LOOPS = 2SUPPLY_V = 230 V AC, 24 V DCBATTERY_AH = 24COMMUNICATION = Serial link to gatewayLOCATION = Fire control roomADDRESS_RANGE = 1-250 | |
| LV-1 | Level mark, warningPMN_LEVEL_WARNING | TYPE = WarningRATING = Level 1LOCATION = Transformer T1 areaADDRESS = 21 | |
| LV-2 | Level mark, alarmPMN_LEVEL_ALARM | TYPE = AlarmRATING = Level 2LOCATION = Transformer T1 areaADDRESS = 22 | |
| LV-3 | Level mark, tripPMN_LEVEL_TRIP | TYPE = TripRATING = Level 3LOCATION = Transformer T1 areaADDRESS = 23 |
Fabricante, modelo e observações ficam vazios em todos os blocos, prontos para os seus dados. Os valores são exemplos.
Como usar
- Abra o desenho de exemplo para ver como layers, textos e o carimbo são usados, ou abra antes no navegador, sem instalar nada.
- Comece o seu desenho a partir do modelo (NOVO, depois escolha o arquivo DWT). Copie o arquivo CTB para a sua pasta de estilos de plotagem se quiser plotagens em preto e branco.
- Insira blocos da biblioteca de símbolos no seu desenho. Os blocos do exemplo são cópias; eles não mudam quando uma biblioteca muda.
Perguntas frequentes
- Posso usar o desenho em um projeto real?
- Como ponto de partida para a organização e os layers, sim. As potências, os ajustes e as bitolas de cabo são inventados, então o esquema precisa ser conferido e adaptado ao seu projeto antes de ser usado em projeto ou obra.
- Por que os layers têm cores?
- As cores e as espessuras seguem os layers: os circuitos de potência são vermelhos e grossos, o comando é ciano, o sinal é verde. A tabela de estilos de plotagem do ZIP imprime tudo em preto e mantém as espessuras, então também dá para plotar em preto e branco.
- Quais programas de CAD abrem o arquivo?
- O desenho e o modelo estão no formato do AutoCAD 2018, que o AutoCAD 2018 e posteriores abrem, assim como outros programas de CAD que leem esse formato. O visualizador no navegador não exige nenhuma instalação.