Switchboard arc flash protection and PD monitoring: sample DWG

The arc flash protection and partial discharge monitoring of an 11 kV switchboard. Four panels, an incomer, two feeders and a bus section, each have a busbar, a breaker and a cable compartment with its own zone mark and light sensor. The twelve sensor fibres are grouped into four channels on the arc flash relay. The relay trips the incomer and the bus section only when the current check from the incomer sees an overcurrent, and a mark shows the light-only mode used for tests. Below the panels one earth voltage sensor per panel feeds a partial discharge host, which reports through a gateway to SCADA. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Kendi projelerinizde, ticari olanlar dahil, ücretsiz kullanabilir ve değiştirebilirsiniz. ZIP içinde örnek çizim, bir şablon, bir plot stili tablosu ve bir README bulunur; eklenti gerekmez. Çizimdeki veriler uydurmadır, bu yüzden tasarım ya da inşaat için kullanılamaz. Olduğu gibi sunulur, garanti verilmez. Kütüphane koşulları (CXL-1.0)

Bu örnek şu kaynakları kullanıyor

Semboller, öznitelikleri doldurulmuş olarak kendi kütüphanelerimizden gelen bloklardır. Pafta ve anteti, ISO A3 antet şablonumuzdan gelir. Kendi şemalarınızı çizmek için bunları indirin.

ZIP'in içinde ne var

  • Switchboard-Arc-Flash-Monitoring-Sample.dwg
    Örnek çizim (DWG, AutoCAD 2018 biçimi)
  • Process-Template-ISO-A3.dwt
    Çizimin üzerinde hazırlandığı şablon (DWT)
  • CADXChange-Monochrome.ctb
    Tüm renkleri siyah basan plot stili tablosu (CTB)
  • README.txt
    Layer listesi ve dosyaların kullanımını anlatan README

Şablon

Proses şablonunda renkleri, çizgi kalınlıkları ve çizgi tipleriyle 14 layer vardır (ana, ikincil ve yardımcı hatlar, elektrik ve pnömatik sinyaller, ekipman, sınırlar, akış okları, etiketler, hat numaraları, yazı ve daha fazlası); ayrıca ISO-2.5'ten ISO-5'e yazı stilleri, ISO-25 ölçü stili ve antet ile revizyon tablosu olan bir ISO A3 layout'u bulunur. Layer adları yaygın bir düzendir, bir standart değildir; şirketinizin kurallarına uysun diye yeniden adlandırın.

Tanımlı layer'lar

Şablondaki her layer; rengi, çizgi kalınlığı ve çizgi tipiyle, ve bu örneğin kaç nesnesinin üzerinde olduğuyla. Örneğin kullanmadığı layer'lar da tanımlı kalır, kendi çiziminiz için hazırdır.

LayerRenkÇizgi kalınlığıÇizgi tipiKullanımBuradaki nesneler
Proses layer'ları
PROC-PIPE-MAIN50.50 mmContinuousAna proses hatları3
PROC-PIPE-SEC40.35 mmContinuousİkincil ve branşman proses hatları51
PROC-PIPE-UTIL300.35 mmContinuousYardımcı hatlar (buhar, kondensat, soğutma suyu, hava)burada kullanılmıyor
PROC-SIGNAL30.18 mmDASHEDElektrik sinyal hatları14
PROC-PNEU60.18 mmDASHDOTPnömatik ve kapiler sinyal hatlarıburada kullanılmıyor
SYMBOL70.25 mmContinuousSemboller (sembol kütüphanelerinin kullandığı layer)35
PROC-EQUIP70.35 mmContinuousSembol kütüphaneleri dışında çizilen ekipman konturları24
PROC-BOUNDARY10.18 mmDASHDOTPaket, skid ve sınır limitleriburada kullanılmıyor
PROC-FLOW70.18 mmContinuousAkış okları ve akış yönü işaretleri1
PROC-TAG70.18 mmContinuousEkipman ve enstrüman etiketleriburada kullanılmıyor
PROC-LINE-NO70.18 mmContinuousHat numaraları ve hat spesifikasyonlarıburada kullanılmıyor
PROC-TEXT70.18 mmContinuousGenel yazı40
PROC-NOTES70.18 mmContinuousNotlar ve lejantlar12
PROC-DIM30.18 mmContinuousÖlçülendirmeburada kullanılmıyor
Pafta ve sembol layer'ları
07varsayılanContinuousVarsayılan layer, boş bırakınburada kullanılmıyor
FRAME7varsayılanContinuousPafta kenarı5
TITLEBLOCK7varsayılanContinuousAntet ve revizyon tablosu1
VIEWPORT8varsayılanContinuousLayout viewport çerçevesi (basılmaz)2
DRAWING-AREA8varsayılanContinuousModel çizim alanı sınırı (basılmaz)2

Tanımlı stiller

Şablonun tanımladığı yazı stilleri, ölçü stili ve çizgi tipleri; böylece her yeni çizimde kurmanız gerekmez.

TürAdAyarlar
Yazı stiliISOisocp.shx, 15°, değişken yükseklik
Yazı stiliISO-2.5isocp.shx, 15°, 2.5 mm yükseklik
Yazı stiliISO-3.5isocp.shx, 15°, 3.5 mm yükseklik
Yazı stiliISO-5isocp.shx, 15°, 5 mm yükseklik
Yazı stiliTB-enArial, antette kullanılır
Ölçü stiliISO-25Yazı 2.5 mm, oklar 2.5 mm, uzatma çizgileri ölçü çizgisinin 1.25 mm ötesine uzanır ve nesneden 0.625 mm uzakta durur, ölçü çizgileri arası 3.75 mm, 0 ondalık
Çizgi tipiContinuousSürekli çizgi
Çizgi tipiDASHEDKesikli
Çizgi tipiDASHDOTÇizgi-nokta
Çizgi tipiCENTEREksen çizgisi
Çizgi tipiPHANTOMHayalet çizgi
Çizgi tipiHIDDENGizli çizgi

Pafta ve çizim ayarı

Paftanın nasıl ayarlandığı; böylece kendi çizimleriniz de aynı şekilde basılır.

Pafta
ISO A3 yatay, 420 × 297 mm.
Layout
ISO-A3 adlı tek bir layout; kenar boşluksuz A3 ortamında 1:1 basılır, yani paftada yazıcı kenar boşluğu yoktur.
Çerçeve
Sol kenardan 20 mm (cilt tarafı) ve diğer kenarlardan 10 mm; içerideki çizim alanı 390 × 277 mm'dir.
Model uzayı
Birim milimetredir. Çizim alanı 1:1 gösterilir; yani çizimdeki 1 mm kâğıtta 1 mm'dir.
Antet
Sağ altta 160 × 79 mm; şirket, proje, başlık ve onay alanlarının üstünde dört satırlık bir revizyon tablosu bulunur.
Yazı boyutu
Etiketler ve notlar için 2,5 mm, başlıklar için 3,5 mm ve 5 mm.
Çizgi tipi ölçeği
1; yani çizgi aralıkları 1:1 basım için boyutlandırılmıştır.
Plot stili
Ayarlanmamış. Siyah-beyaz baskı için sayfa yapısında ZIP'teki CTB'yi seçin.

Antet alanları

Antetin öznitelikleri.

ÖznitelikPaftadaki alanBu örnekteki değer
COMPANYCOMPANYCADXChange
PROJECTPROJECT11 kV Switchboard S1
AREAAREASwitch room
SYSTEMSYSTEMCondition monitoring
CLIENTCLIENTSample
TITLEDRAWING TITLESwitchboard arc flash and PD monitoring
DRAWING_NODRAWING NO.M-502
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revizyon tablosu: R1–R4, her biri REV, TARİH, AÇIKLAMA ve YAPAN alanlarıyla (16 öznitelik, bu örnekte boş).

Çizimdeki bloklar

Çizimin ekipman listesi: blok adı, sembol ve kaç kez yerleştirildiği.

SembolBlokYerleştirilen
Arc point sensorPMN_ARC_POINT12
Busbar compartment zonePMN_ARC_ZONE_BUS4
Breaker compartment zonePMN_ARC_ZONE_CB4
Cable compartment zonePMN_ARC_ZONE_CABLE4
Partial discharge, TEVPMN_SG_PD_TEV4
Trip outputPMN_ARC_TRIP_OUT2
Arc flash relayPMN_ARC_RELAY1
Current check inputPMN_ARC_CT_INPUT1
Light-only mode markPMN_ARC_LIGHT_ONLY1
Partial discharge hostPMN_SG_PD_HOST1
Edge gatewayPMN_SYS_EDGE_GW1

Ekipman listesi

Yerleştirilen her sembol için bir satır; çizimdeki blokların özniteliklerinden okunur: paftada gösterilenler ve doldurulmuş ama gösterilmeyen liste öznitelikleri.

EtiketAçıklamaPaftada gösterilenDoldurulmuş, gösterilmeyen
BB-1Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-1Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 1
CB-1Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-2Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 2
CC-1Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-3Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 3
BB-2Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-4Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 4
CB-2Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-5Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 5
CC-2Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-6Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 6
BB-3Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-7Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 7
CB-3Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-8Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 8
CC-3Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-9Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 9
BB-4Busbar compartment zonePMN_ARC_ZONE_BUSZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-10Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 10
CB-4Breaker compartment zonePMN_ARC_ZONE_CBZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-11Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 11
CC-4Cable compartment zonePMN_ARC_ZONE_CABLEZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1
AS-12Arc point sensorPMN_ARC_POINTSENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 12
AFR-1Arc flash relayPMN_ARC_RELAYSENSITIVITY_LUX = -TRIP_TIME_MS = 7COMPARTMENT = All panelsOUTPUT = 2 trip, 1 alarmCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 13
CI-1Current check inputPMN_ARC_CT_INPUTSENSITIVITY_LUX = -TRIP_TIME_MS = -COMPARTMENT = IncomerOUTPUT = Current checkCURRENT_CHECK = 2.5 x InLOCATION = 11 kV switchboard S1ADDRESS = 14
TO-1Trip outputPMN_ARC_TRIP_OUTSENSITIVITY_LUX = -TRIP_TIME_MS = 3COMPARTMENT = Q1 and Q3OUTPUT = Trip coil, 110 V DCCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 15
TO-2Trip outputPMN_ARC_TRIP_OUTSENSITIVITY_LUX = -TRIP_TIME_MS = 3COMPARTMENT = Q1 and Q3OUTPUT = Trip coil, 110 V DCCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 16
LO-1Light-only mode markPMN_ARC_LIGHT_ONLYSENSITIVITY_LUX = -TRIP_TIME_MS = -COMPARTMENT = All panelsOUTPUT = Alarm onlyCURRENT_CHECK = NoLOCATION = 11 kV switchboard S1ADDRESS = 17
PDT-1Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 18
PDT-2Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 19
PDT-3Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 20
PDT-4Partial discharge, TEVPMN_SG_PD_TEVMETHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 21
PDH-1Partial discharge hostPMN_SG_PD_HOSTCHANNELS = 8SUPPLY_V = 24 V DCCOMMUNICATION = EthernetOUTPUTS = 2MOUNTING = WallLOCATION = 11 kV switchboard S1ADDRESS = 22
EG-1Edge gatewayPMN_SYS_EDGE_GWFUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = 11 kV switchboard S1ADDRESS = 23

Üretici, model ve açıklamalar her blokta boş bırakılmıştır, verileriniz için hazırdır. Değerler örnektir.

Nasıl kullanılır

  1. Layer'ların, yazıların ve anteti nasıl kullanıldığını görmek için örnek çizimi açın; ya da önce tarayıcıda açın, hiçbir şey kurmanız gerekmez.
  2. Kendi çiziminize şablondan başlayın (NEW, sonra DWT dosyasını seçin). Siyah-beyaz baskı istiyorsanız CTB dosyasını plot stilleri klasörünüze kopyalayın.
  3. Sembol kütüphanesinden bloklarınızı çiziminize ekleyin. Örnekteki bloklar kopyadır; kütüphane değiştiğinde değişmezler.

Sık sorulan sorular

Çizimi gerçek bir projede kullanabilir miyim?
Yerleşim ve layer düzeni için bir başlangıç noktası olarak evet. Anma değerleri, ayarlar ve kablo kesitleri uydurmadır; bu yüzden şema, tasarım ya da inşaat için kullanılmadan önce projenize göre kontrol edilip değiştirilmelidir.
Layer'lar neden renkli?
Renkler ve çizgi kalınlıkları layer'ları izler: güç devreleri kırmızı ve kalın, kumanda camgöbeği, sinyal yeşildir. ZIP'teki plot stili tablosu her şeyi siyah basar ve çizgi kalınlıklarını korur; yani siyah-beyaz da basabilirsiniz.
Hangi CAD programları açar?
Çizim ve şablon, AutoCAD 2018 ve sonrasının açtığı AutoCAD 2018 biçimindedir; bu biçimi okuyan diğer CAD programları da açar. Tarayıcı görüntüleyici hiçbir kurulum gerektirmez.