The fire protection of a battery energy storage site, drawn as a layout. Six battery containers stand in two rows, each with its own water connection on a fire water ring main, and a 3 m separation mark shows the clear distance between neighbours. A signal trunk runs under the yard to the fire alarm panel, the annunciator, the emergency power off, the remote shutdown and the battery management interface. On the right a typical container is opened up: four battery racks, thermal runaway, off-gas and electrolyte vapour detectors under the roof, a deflagration vent, an explosion-proof exhaust fan with a make-up air louver, and water mist nozzles fed from the container's water connection. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Kendi projelerinizde, ticari olanlar dahil, ücretsiz kullanabilir ve değiştirebilirsiniz. ZIP içinde örnek çizim, bir şablon, bir plot stili tablosu ve bir README bulunur; eklenti gerekmez. Çizimdeki veriler uydurmadır, bu yüzden tasarım ya da inşaat için kullanılamaz. Olduğu gibi sunulur, garanti verilmez. Kütüphane koşulları (CXL-1.0)

Bu örnek şu kaynakları kullanıyor

Semboller, öznitelikleri doldurulmuş olarak kendi kütüphanelerimizden gelen bloklardır. Pafta ve anteti, ISO A3 antet şablonumuzdan gelir. Kendi şemalarınızı çizmek için bunları indirin.

ZIP'in içinde ne var

  • Battery-Storage-Fire-Protection-Layout-Sample.dwg
    Örnek çizim (DWG, AutoCAD 2018 biçimi)
  • Process-Template-ISO-A3.dwt
    Çizimin üzerinde hazırlandığı şablon (DWT)
  • CADXChange-Monochrome.ctb
    Tüm renkleri siyah basan plot stili tablosu (CTB)
  • README.txt
    Layer listesi ve dosyaların kullanımını anlatan README

Şablon

Proses şablonunda renkleri, çizgi kalınlıkları ve çizgi tipleriyle 14 layer vardır (ana, ikincil ve yardımcı hatlar, elektrik ve pnömatik sinyaller, ekipman, sınırlar, akış okları, etiketler, hat numaraları, yazı ve daha fazlası); ayrıca ISO-2.5'ten ISO-5'e yazı stilleri, ISO-25 ölçü stili ve antet ile revizyon tablosu olan bir ISO A3 layout'u bulunur. Layer adları yaygın bir düzendir, bir standart değildir; şirketinizin kurallarına uysun diye yeniden adlandırın.

Tanımlı layer'lar

Şablondaki her layer; rengi, çizgi kalınlığı ve çizgi tipiyle, ve bu örneğin kaç nesnesinin üzerinde olduğuyla. Örneğin kullanmadığı layer'lar da tanımlı kalır, kendi çiziminiz için hazırdır.

LayerRenkÇizgi kalınlığıÇizgi tipiKullanımBuradaki nesneler
Proses layer'ları
PROC-PIPE-MAIN50.50 mmContinuousAna proses hatları23
PROC-PIPE-SEC40.35 mmContinuousİkincil ve branşman proses hatlarıburada kullanılmıyor
PROC-PIPE-UTIL300.35 mmContinuousYardımcı hatlar (buhar, kondensat, soğutma suyu, hava)burada kullanılmıyor
PROC-SIGNAL30.18 mmDASHEDElektrik sinyal hatları33
PROC-PNEU60.18 mmDASHDOTPnömatik ve kapiler sinyal hatlarıburada kullanılmıyor
SYMBOL70.25 mmContinuousSemboller (sembol kütüphanelerinin kullandığı layer)36
PROC-EQUIP70.35 mmContinuousSembol kütüphaneleri dışında çizilen ekipman konturları4
PROC-BOUNDARY10.18 mmDASHDOTPaket, skid ve sınır limitleriburada kullanılmıyor
PROC-FLOW70.18 mmContinuousAkış okları ve akış yönü işaretleri1
PROC-TAG70.18 mmContinuousEkipman ve enstrüman etiketleriburada kullanılmıyor
PROC-LINE-NO70.18 mmContinuousHat numaraları ve hat spesifikasyonlarıburada kullanılmıyor
PROC-TEXT70.18 mmContinuousGenel yazı30
PROC-NOTES70.18 mmContinuousNotlar ve lejantlar14
PROC-DIM30.18 mmContinuousÖlçülendirmeburada kullanılmıyor
Pafta ve sembol layer'ları
07varsayılanContinuousVarsayılan layer, boş bırakınburada kullanılmıyor
FRAME7varsayılanContinuousPafta kenarı5
TITLEBLOCK7varsayılanContinuousAntet ve revizyon tablosu1
VIEWPORT8varsayılanContinuousLayout viewport çerçevesi (basılmaz)2
DRAWING-AREA8varsayılanContinuousModel çizim alanı sınırı (basılmaz)2

Tanımlı stiller

Şablonun tanımladığı yazı stilleri, ölçü stili ve çizgi tipleri; böylece her yeni çizimde kurmanız gerekmez.

TürAdAyarlar
Yazı stiliISOisocp.shx, 15°, değişken yükseklik
Yazı stiliISO-2.5isocp.shx, 15°, 2.5 mm yükseklik
Yazı stiliISO-3.5isocp.shx, 15°, 3.5 mm yükseklik
Yazı stiliISO-5isocp.shx, 15°, 5 mm yükseklik
Yazı stiliTB-enArial, antette kullanılır
Ölçü stiliISO-25Yazı 2.5 mm, oklar 2.5 mm, uzatma çizgileri ölçü çizgisinin 1.25 mm ötesine uzanır ve nesneden 0.625 mm uzakta durur, ölçü çizgileri arası 3.75 mm, 0 ondalık
Çizgi tipiContinuousSürekli çizgi
Çizgi tipiDASHEDKesikli
Çizgi tipiDASHDOTÇizgi-nokta
Çizgi tipiCENTEREksen çizgisi
Çizgi tipiPHANTOMHayalet çizgi
Çizgi tipiHIDDENGizli çizgi

Pafta ve çizim ayarı

Paftanın nasıl ayarlandığı; böylece kendi çizimleriniz de aynı şekilde basılır.

Pafta
ISO A3 yatay, 420 × 297 mm.
Layout
ISO-A3 adlı tek bir layout; kenar boşluksuz A3 ortamında 1:1 basılır, yani paftada yazıcı kenar boşluğu yoktur.
Çerçeve
Sol kenardan 20 mm (cilt tarafı) ve diğer kenarlardan 10 mm; içerideki çizim alanı 390 × 277 mm'dir.
Model uzayı
Birim milimetredir. Çizim alanı 1:1 gösterilir; yani çizimdeki 1 mm kâğıtta 1 mm'dir.
Antet
Sağ altta 160 × 79 mm; şirket, proje, başlık ve onay alanlarının üstünde dört satırlık bir revizyon tablosu bulunur.
Yazı boyutu
Etiketler ve notlar için 2,5 mm, başlıklar için 3,5 mm ve 5 mm.
Çizgi tipi ölçeği
1; yani çizgi aralıkları 1:1 basım için boyutlandırılmıştır.
Plot stili
Ayarlanmamış. Siyah-beyaz baskı için sayfa yapısında ZIP'teki CTB'yi seçin.

Antet alanları

Antetin öznitelikleri.

ÖznitelikPaftadaki alanBu örnekteki değer
COMPANYCOMPANYCADXChange
PROJECTPROJECTBattery Storage Station
AREAAREABattery yard
SYSTEMSYSTEMFire protection
CLIENTCLIENTSample
TITLEDRAWING TITLEBattery storage fire protection layout
DRAWING_NODRAWING NO.F-502
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revizyon tablosu: R1–R4, her biri REV, TARİH, AÇIKLAMA ve YAPAN alanlarıyla (16 öznitelik, bu örnekte boş).

Çizimdeki bloklar

Çizimin ekipman listesi: blok adı, sembol ve kaç kez yerleştirildiği.

SembolBlokYerleştirilen
Water supply connectionPFP_WATER_CONN7
Battery containerPFP_BATT_CONTAINER6
Battery rackPFP_BATT_RACK4
Separation distance, 3 mPFP_SEP_3M2
BMS interfacePFP_BMS_INTERFACE2
Thermal runaway detectorPFP_TR_DETECTOR2
Suppression nozzle, containerPFP_SUPP_NOZZLE_CONT2
Sectional valve, OS&YPFP_VALVE_OSY1
Hydrant, pillarPFP_HYDRANT_PILLAR1
Fire alarm control panelPFP_FACP1
Remote annunciatorPFP_ANNUNCIATOR1
Emergency power offPFP_EPO1
Remote shutdownPFP_REMOTE_SHUTDOWN1
Off-gas detectorPFP_OFFGAS_DETECTOR1
Electrolyte vapour detectorPFP_VAPOUR_DETECTOR1
Deflagration ventPFP_DEFLAG_VENT1
Exhaust fan, explosion-proofPFP_EXHAUST_FAN_EX1
Make-up air louverPFP_MAKEUP_LOUVRE1

Ekipman listesi

Yerleştirilen her sembol için bir satır; çizimdeki blokların özniteliklerinden okunur: paftada gösterilenler ve doldurulmuş ama gösterilmeyen liste öznitelikleri.

EtiketAçıklamaPaftada gösterilenDoldurulmuş, gösterilmeyen
BC-1Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-1Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-2Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-2Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-3Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-3Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-4Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-4Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-5Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-5Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-6Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-6Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
SD-1Separation distance, 3 mPFP_SEP_3MZONE = BESS yardAREA_M2 = -RATING_H = -HAZARD = Battery container firePROTECTION = 3 m clear distanceLOCATION = BESS yard
SD-2Separation distance, 3 mPFP_SEP_3MZONE = BESS yardAREA_M2 = -RATING_H = -HAZARD = Battery container firePROTECTION = 3 m clear distanceLOCATION = BESS yard
V-1Sectional valve, OS&YPFP_VALVE_OSYSIZE_DN = 200PRESSURE_RATING = PN16ACTUATION = HandwheelSERVICE = Fire waterMATERIAL = Ductile ironSUPERVISED = YesZONE = Transformer area
HY-1Hydrant, pillarPFP_HYDRANT_PILLARSIZE_DN = 100OUTLETS = 2FLOW_LPS = 15PRESSURE_BAR = 4ZONE = Transformer areaLOCATION = Transformer area
FACP-1Fire alarm control panelPFP_FACPZONES = 8LOOPS = 2SUPPLY_V = 230 V AC, 24 V DCBATTERY_AH = 24COMMUNICATION = Serial link to gatewayLOCATION = Fire control roomADDRESS_RANGE = 1-250
ANN-1Remote annunciatorPFP_ANNUNCIATORZONES = 8SUPPLY_V = 24 V DCCOMMUNICATION = RS-485 from FACP-1LOCATION = Fire control room
EPO-1Emergency power offPFP_EPOTYPE = Mushroom, latchingZONE = Transformer areaLOOP = 1ADDRESS = 160ENCLOSURE = IP66MOUNTING_HEIGHT_M = 1.4FUNCTION = Trips the storage system
RS-1Remote shutdownPFP_REMOTE_SHUTDOWNTYPE = Remote trip inputZONE = Transformer areaLOOP = 1ADDRESS = 161ENCLOSURE = IP54MOUNTING_HEIGHT_M = -FUNCTION = Trip from the control centre
BMS-1BMS interfacePFP_BMS_INTERFACEZONES = 1LOOPS = -SUPPLY_V = 24 V DCBATTERY_AH = -COMMUNICATION = Modbus TCPLOCATION = Transformer area
R-1Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
R-2Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
R-3Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
R-4Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
TR-1Thermal runaway detectorPFP_TR_DETECTORGAS = Thermal runaway gasesRANGE = 0-100 % LELALARM_1 = 10 % LELALARM_2 = 25 % LELZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
OG-1Off-gas detectorPFP_OFFGAS_DETECTORGAS = Battery off-gasRANGE = 0-100 % LELALARM_1 = 10 % LELALARM_2 = 25 % LELZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
TR-2Thermal runaway detectorPFP_TR_DETECTORGAS = Thermal runaway gasesRANGE = 0-100 % LELALARM_1 = 10 % LELALARM_2 = 25 % LELZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
VD-1Electrolyte vapour detectorPFP_VAPOUR_DETECTORGAS = Electrolyte vapourRANGE = 0-100 ppmALARM_1 = 10 ppmALARM_2 = 25 ppmZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
BMS-2BMS interfacePFP_BMS_INTERFACEZONES = 1LOOPS = -SUPPLY_V = 24 V DCBATTERY_AH = -COMMUNICATION = Modbus TCPLOCATION = Transformer area
DV-1Deflagration ventPFP_DEFLAG_VENTRATING_H = -SIZE_MM = 800 x 800ACTUATION = PressureRELEASE_TEMP_C = -ZONE = Transformer areaLOCATION = Transformer area
EF-1Exhaust fan, explosion-proofPFP_EXHAUST_FAN_EXRATING_H = -SIZE_MM = DN500ACTUATION = On gas alarmRELEASE_TEMP_C = -ZONE = Transformer areaLOCATION = Transformer area
ML-1Make-up air louverPFP_MAKEUP_LOUVRERATING_H = -SIZE_MM = 600 x 400ACTUATION = MotorisedRELEASE_TEMP_C = -ZONE = Transformer areaLOCATION = Transformer area
WC-nWater supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
SN-1Suppression nozzle, containerPFP_SUPP_NOZZLE_CONTAGENT = Water mistFLOW_KGS = -ORIFICE_MM = 1.5COVERAGE_M2 = 10MOUNTING = CeilingZONE = Transformer area
SN-2Suppression nozzle, containerPFP_SUPP_NOZZLE_CONTAGENT = Water mistFLOW_KGS = -ORIFICE_MM = 1.5COVERAGE_M2 = 10MOUNTING = CeilingZONE = Transformer area

Üretici, model ve açıklamalar her blokta boş bırakılmıştır, verileriniz için hazırdır. Değerler örnektir.

Nasıl kullanılır

  1. Layer'ların, yazıların ve anteti nasıl kullanıldığını görmek için örnek çizimi açın; ya da önce tarayıcıda açın, hiçbir şey kurmanız gerekmez.
  2. Kendi çiziminize şablondan başlayın (NEW, sonra DWT dosyasını seçin). Siyah-beyaz baskı istiyorsanız CTB dosyasını plot stilleri klasörünüze kopyalayın.
  3. Sembol kütüphanesinden bloklarınızı çiziminize ekleyin. Örnekteki bloklar kopyadır; kütüphane değiştiğinde değişmezler.

Sık sorulan sorular

Çizimi gerçek bir projede kullanabilir miyim?
Yerleşim ve layer düzeni için bir başlangıç noktası olarak evet. Anma değerleri, ayarlar ve kablo kesitleri uydurmadır; bu yüzden şema, tasarım ya da inşaat için kullanılmadan önce projenize göre kontrol edilip değiştirilmelidir.
Layer'lar neden renkli?
Renkler ve çizgi kalınlıkları layer'ları izler: güç devreleri kırmızı ve kalın, kumanda camgöbeği, sinyal yeşildir. ZIP'teki plot stili tablosu her şeyi siyah basar ve çizgi kalınlıklarını korur; yani siyah-beyaz da basabilirsiniz.
Hangi CAD programları açar?
Çizim ve şablon, AutoCAD 2018 ve sonrasının açtığı AutoCAD 2018 biçimindedir; bu biçimi okuyan diğer CAD programları da açar. Tarayıcı görüntüleyici hiçbir kurulum gerektirmez.