Transformer online monitoring system: sample DWG of a system diagram

The online monitoring of one power transformer, drawn as a system diagram. At field level fourteen sensors sit on the transformer: dissolved gas, moisture, partial discharge by UHF and acoustic methods, bushings, winding and top oil temperature, tap changer, cooling, oil level, gas relay, pressure relief, vibration and core earth current. Four collectors bring their signals to the monitoring IED. At station level the IED reaches a switch, a GPS time source, an edge gateway to SCADA, a server and a workstation, lights an alarm beacon, and sends a hard-wired alarm contact to the fire alarm panel. A legend, the three alarm level marks, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Kendi projelerinizde, ticari olanlar dahil, ücretsiz kullanabilir ve değiştirebilirsiniz. ZIP içinde örnek çizim, bir şablon, bir plot stili tablosu ve bir README bulunur; eklenti gerekmez. Çizimdeki veriler uydurmadır, bu yüzden tasarım ya da inşaat için kullanılamaz. Olduğu gibi sunulur, garanti verilmez. Kütüphane koşulları (CXL-1.0)

Bu örnek şu kaynakları kullanıyor

Semboller, öznitelikleri doldurulmuş olarak kendi kütüphanelerimizden gelen bloklardır. Pafta ve anteti, ISO A3 antet şablonumuzdan gelir. Kendi şemalarınızı çizmek için bunları indirin.

ZIP'in içinde ne var

  • Transformer-Online-Monitoring-System-Sample.dwg
    Örnek çizim (DWG, AutoCAD 2018 biçimi)
  • Process-Template-ISO-A3.dwt
    Çizimin üzerinde hazırlandığı şablon (DWT)
  • CADXChange-Monochrome.ctb
    Tüm renkleri siyah basan plot stili tablosu (CTB)
  • README.txt
    Layer listesi ve dosyaların kullanımını anlatan README

Şablon

Proses şablonunda renkleri, çizgi kalınlıkları ve çizgi tipleriyle 14 layer vardır (ana, ikincil ve yardımcı hatlar, elektrik ve pnömatik sinyaller, ekipman, sınırlar, akış okları, etiketler, hat numaraları, yazı ve daha fazlası); ayrıca ISO-2.5'ten ISO-5'e yazı stilleri, ISO-25 ölçü stili ve antet ile revizyon tablosu olan bir ISO A3 layout'u bulunur. Layer adları yaygın bir düzendir, bir standart değildir; şirketinizin kurallarına uysun diye yeniden adlandırın.

Tanımlı layer'lar

Şablondaki her layer; rengi, çizgi kalınlığı ve çizgi tipiyle, ve bu örneğin kaç nesnesinin üzerinde olduğuyla. Örneğin kullanmadığı layer'lar da tanımlı kalır, kendi çiziminiz için hazırdır.

LayerRenkÇizgi kalınlığıÇizgi tipiKullanımBuradaki nesneler
Proses layer'ları
PROC-PIPE-MAIN50.50 mmContinuousAna proses hatları9
PROC-PIPE-SEC40.35 mmContinuousİkincil ve branşman proses hatlarıburada kullanılmıyor
PROC-PIPE-UTIL300.35 mmContinuousYardımcı hatlar (buhar, kondensat, soğutma suyu, hava)burada kullanılmıyor
PROC-SIGNAL30.18 mmDASHEDElektrik sinyal hatları30
PROC-PNEU60.18 mmDASHDOTPnömatik ve kapiler sinyal hatlarıburada kullanılmıyor
SYMBOL70.25 mmContinuousSemboller (sembol kütüphanelerinin kullandığı layer)26
PROC-EQUIP70.35 mmContinuousSembol kütüphaneleri dışında çizilen ekipman konturlarıburada kullanılmıyor
PROC-BOUNDARY10.18 mmDASHDOTPaket, skid ve sınır limitleri2
PROC-FLOW70.18 mmContinuousAkış okları ve akış yönü işaretleri1
PROC-TAG70.18 mmContinuousEkipman ve enstrüman etiketleriburada kullanılmıyor
PROC-LINE-NO70.18 mmContinuousHat numaraları ve hat spesifikasyonlarıburada kullanılmıyor
PROC-TEXT70.18 mmContinuousGenel yazı33
PROC-NOTES70.18 mmContinuousNotlar ve lejantlar13
PROC-DIM30.18 mmContinuousÖlçülendirmeburada kullanılmıyor
Pafta ve sembol layer'ları
07varsayılanContinuousVarsayılan layer, boş bırakınburada kullanılmıyor
FRAME7varsayılanContinuousPafta kenarı5
TITLEBLOCK7varsayılanContinuousAntet ve revizyon tablosu1
VIEWPORT8varsayılanContinuousLayout viewport çerçevesi (basılmaz)2
DRAWING-AREA8varsayılanContinuousModel çizim alanı sınırı (basılmaz)2

Tanımlı stiller

Şablonun tanımladığı yazı stilleri, ölçü stili ve çizgi tipleri; böylece her yeni çizimde kurmanız gerekmez.

TürAdAyarlar
Yazı stiliISOisocp.shx, 15°, değişken yükseklik
Yazı stiliISO-2.5isocp.shx, 15°, 2.5 mm yükseklik
Yazı stiliISO-3.5isocp.shx, 15°, 3.5 mm yükseklik
Yazı stiliISO-5isocp.shx, 15°, 5 mm yükseklik
Yazı stiliTB-enArial, antette kullanılır
Ölçü stiliISO-25Yazı 2.5 mm, oklar 2.5 mm, uzatma çizgileri ölçü çizgisinin 1.25 mm ötesine uzanır ve nesneden 0.625 mm uzakta durur, ölçü çizgileri arası 3.75 mm, 0 ondalık
Çizgi tipiContinuousSürekli çizgi
Çizgi tipiDASHEDKesikli
Çizgi tipiDASHDOTÇizgi-nokta
Çizgi tipiCENTEREksen çizgisi
Çizgi tipiPHANTOMHayalet çizgi
Çizgi tipiHIDDENGizli çizgi

Pafta ve çizim ayarı

Paftanın nasıl ayarlandığı; böylece kendi çizimleriniz de aynı şekilde basılır.

Pafta
ISO A3 yatay, 420 × 297 mm.
Layout
ISO-A3 adlı tek bir layout; kenar boşluksuz A3 ortamında 1:1 basılır, yani paftada yazıcı kenar boşluğu yoktur.
Çerçeve
Sol kenardan 20 mm (cilt tarafı) ve diğer kenarlardan 10 mm; içerideki çizim alanı 390 × 277 mm'dir.
Model uzayı
Birim milimetredir. Çizim alanı 1:1 gösterilir; yani çizimdeki 1 mm kâğıtta 1 mm'dir.
Antet
Sağ altta 160 × 79 mm; şirket, proje, başlık ve onay alanlarının üstünde dört satırlık bir revizyon tablosu bulunur.
Yazı boyutu
Etiketler ve notlar için 2,5 mm, başlıklar için 3,5 mm ve 5 mm.
Çizgi tipi ölçeği
1; yani çizgi aralıkları 1:1 basım için boyutlandırılmıştır.
Plot stili
Ayarlanmamış. Siyah-beyaz baskı için sayfa yapısında ZIP'teki CTB'yi seçin.

Antet alanları

Antetin öznitelikleri.

ÖznitelikPaftadaki alanBu örnekteki değer
COMPANYCOMPANYCADXChange
PROJECTPROJECT220 kV Substation
AREAAREATransformer area
SYSTEMSYSTEMCondition monitoring
CLIENTCLIENTSample
TITLEDRAWING TITLETransformer online monitoring system
DRAWING_NODRAWING NO.M-501
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revizyon tablosu: R1–R4, her biri REV, TARİH, AÇIKLAMA ve YAPAN alanlarıyla (16 öznitelik, bu örnekte boş).

Çizimdeki bloklar

Çizimin ekipman listesi: blok adı, sembol ve kaç kez yerleştirildiği.

SembolBlokYerleştirilen
Transformer, monitoredPMN_TR_MONITORED1
Oil gas monitor, multi-gasPMN_TR_DGA_MULTI1
Oil moisture sensorPMN_TR_MOISTURE1
Partial discharge, UHFPMN_TR_PD_UHF1
Partial discharge, acousticPMN_TR_PD_AE1
Bushing monitorPMN_TR_BUSHING1
Winding temp, fibre opticPMN_TR_WINDING_FO1
Top oil temperaturePMN_TR_TOP_OIL_TEMP1
Cooler status monitorPMN_TR_COOLING1
Tap changer monitorPMN_TR_OLTC1
Oil level monitorPMN_TR_OIL_LEVEL1
Gas relay monitorPMN_TR_BUCHHOLZ1
Pressure relief monitorPMN_TR_PRV_MON1
Vibration sensorPMN_TR_VIBRATION1
Core ground currentPMN_TR_CORE_GND1
Transformer monitoring IEDPMN_TR_IED1
Alarm beacon columnPMN_SYS_BEACON1
Network switchPMN_SYS_SWITCH1
Time synchronisationPMN_SYS_TIME_SYNC1
Edge gatewayPMN_SYS_EDGE_GW1
Monitoring workstationPMN_SYS_WORKSTATION1
ServerPMN_SYS_SERVER1
Fire alarm control panelPFP_FACP1
Level mark, warningPMN_LEVEL_WARNING1
Level mark, alarmPMN_LEVEL_ALARM1
Level mark, tripPMN_LEVEL_TRIP1

Ekipman listesi

Yerleştirilen her sembol için bir satır; çizimdeki blokların özniteliklerinden okunur: paftada gösterilenler ve doldurulmuş ama gösterilmeyen liste öznitelikleri.

EtiketAçıklamaPaftada gösterilenDoldurulmuş, gösterilmeyen
T1Transformer, monitoredPMN_TR_MONITOREDTYPE = Power transformerRATING = 180 MVA, 220/110 kVLOCATION = Transformer T1 areaADDRESS = -
DGA-1Oil gas monitor, multi-gasPMN_TR_DGA_MULTIGAS = H2, CO, CH4, C2H2, C2H4, C2H6RANGE = H2 5-2000 ppmALARM_1 = H2 100 ppmALARM_2 = C2H2 5 ppmOUTPUT = IEC 61850, 4-20 mALOCATION = Transformer T1 areaADDRESS = 1
MST-1Oil moisture sensorPMN_TR_MOISTUREMEASURAND = Moisture in oilRANGE = 0-100 % RSALARM_1 = 20 % RSALARM_2 = 30 % RSOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 2
PDU-1Partial discharge, UHFPMN_TR_PD_UHFMETHOD = UHFFREQUENCY_BAND = 300-1500 MHzSENSITIVITY_PC = 5CHANNELS = 2OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 3
PDA-1Partial discharge, acousticPMN_TR_PD_AEMETHOD = AcousticFREQUENCY_BAND = 20-300 kHzSENSITIVITY_PC = 10CHANNELS = 4OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 4
BSH-1Bushing monitorPMN_TR_BUSHINGMEASURAND = Capacitance and tan deltaRANGE = tan delta 0-2 %ALARM_1 = 0.7 %ALARM_2 = 1.0 %OUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 5
WT-1Winding temp, fibre opticPMN_TR_WINDING_FORANGE_C = 0-200ALARM_C = 110SENSOR_TYPE = Fibre opticOUTPUT = RS-485MONITORED_ITEM = HV winding hot spotLOCATION = Transformer T1 areaADDRESS = 6
OT-1Top oil temperaturePMN_TR_TOP_OIL_TEMPRANGE_C = -20-120ALARM_C = 85SENSOR_TYPE = PT100OUTPUT = 4-20 mAMONITORED_ITEM = Top oilLOCATION = Transformer T1 areaADDRESS = 7
CL-1Cooler status monitorPMN_TR_COOLINGMEASURAND = Fan and pump statusRANGE = -ALARM_1 = Fan faultALARM_2 = Pump faultOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 8
OLTC-1Tap changer monitorPMN_TR_OLTCMEASURAND = Motor current and positionRANGE = 0-5 AALARM_1 = 3.5 AALARM_2 = 4.5 AOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 9
OL-1Oil level monitorPMN_TR_OIL_LEVELMEASURAND = Conservator oil levelRANGE = 0-100 %ALARM_1 = 20 %ALARM_2 = 10 %OUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 10
BR-1Gas relay monitorPMN_TR_BUCHHOLZMEASURAND = Gas relay alarm and tripRANGE = -ALARM_1 = Gas collectedALARM_2 = Oil surgeOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 11
PR-1Pressure relief monitorPMN_TR_PRV_MONMEASURAND = Pressure relief deviceRANGE = -ALARM_1 = -ALARM_2 = OperatedOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 12
VB-1Vibration sensorPMN_TR_VIBRATIONMEASURAND = Tank vibrationRANGE = 0-50 mm/sALARM_1 = 15 mm/sALARM_2 = 25 mm/sOUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 13
CG-1Core ground currentPMN_TR_CORE_GNDRATIO = 1000:1ACCURACY = 1INNER_DIAMETER_MM = 60CIRCUIT = Core earth strapTYPE = Split coreLOCATION = Transformer T1 area
IED-1Transformer monitoring IEDPMN_TR_IEDCHANNELS = 24SUPPLY_V = 110 V DCCOMMUNICATION = IEC 61850OUTPUTS = 4MOUNTING = Marshalling kioskLOCATION = Transformer T1 areaADDRESS = 14
AB-1Alarm beacon columnPMN_SYS_BEACONFUNCTION = Local alarm beaconPORTS = 1SUPPLY_V = 24 V DCPROTOCOL = Dry contactMOUNTING = PoleLOCATION = Transformer T1 areaADDRESS = 15
SW-1Network switchPMN_SYS_SWITCHFUNCTION = Ethernet switchPORTS = 8SUPPLY_V = 24 V DCPROTOCOL = IEC 61850MOUNTING = DIN railLOCATION = Transformer T1 areaADDRESS = 16
TS-1Time synchronisationPMN_SYS_TIME_SYNCFUNCTION = GPS time sourcePORTS = 2SUPPLY_V = 24 V DCPROTOCOL = PTP, IRIG-BMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 17
EG-1Edge gatewayPMN_SYS_EDGE_GWFUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 18
WS-1Monitoring workstationPMN_SYS_WORKSTATIONFUNCTION = Operator workstationPORTS = 2SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = DeskLOCATION = Transformer T1 areaADDRESS = 19
SV-1ServerPMN_SYS_SERVERFUNCTION = Monitoring serverPORTS = 4SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 20
FACP-1Fire alarm control panelPFP_FACPZONES = 8LOOPS = 2SUPPLY_V = 230 V AC, 24 V DCBATTERY_AH = 24COMMUNICATION = Serial link to gatewayLOCATION = Fire control roomADDRESS_RANGE = 1-250
LV-1Level mark, warningPMN_LEVEL_WARNINGTYPE = WarningRATING = Level 1LOCATION = Transformer T1 areaADDRESS = 21
LV-2Level mark, alarmPMN_LEVEL_ALARMTYPE = AlarmRATING = Level 2LOCATION = Transformer T1 areaADDRESS = 22
LV-3Level mark, tripPMN_LEVEL_TRIPTYPE = TripRATING = Level 3LOCATION = Transformer T1 areaADDRESS = 23

Üretici, model ve açıklamalar her blokta boş bırakılmıştır, verileriniz için hazırdır. Değerler örnektir.

Nasıl kullanılır

  1. Layer'ların, yazıların ve anteti nasıl kullanıldığını görmek için örnek çizimi açın; ya da önce tarayıcıda açın, hiçbir şey kurmanız gerekmez.
  2. Kendi çiziminize şablondan başlayın (NEW, sonra DWT dosyasını seçin). Siyah-beyaz baskı istiyorsanız CTB dosyasını plot stilleri klasörünüze kopyalayın.
  3. Sembol kütüphanesinden bloklarınızı çiziminize ekleyin. Örnekteki bloklar kopyadır; kütüphane değiştiğinde değişmezler.

Sık sorulan sorular

Çizimi gerçek bir projede kullanabilir miyim?
Yerleşim ve layer düzeni için bir başlangıç noktası olarak evet. Anma değerleri, ayarlar ve kablo kesitleri uydurmadır; bu yüzden şema, tasarım ya da inşaat için kullanılmadan önce projenize göre kontrol edilip değiştirilmelidir.
Layer'lar neden renkli?
Renkler ve çizgi kalınlıkları layer'ları izler: güç devreleri kırmızı ve kalın, kumanda camgöbeği, sinyal yeşildir. ZIP'teki plot stili tablosu her şeyi siyah basar ve çizgi kalınlıklarını korur; yani siyah-beyaz da basabilirsiniz.
Hangi CAD programları açar?
Çizim ve şablon, AutoCAD 2018 ve sonrasının açtığı AutoCAD 2018 biçimindedir; bu biçimi okuyan diğer CAD programları da açar. Tarayıcı görüntüleyici hiçbir kurulum gerektirmez.