KaynaklarTek hat şeması sembolleri
Transformer online monitoring system: sample DWG of a system diagram
The online monitoring of one power transformer, drawn as a system diagram. At field level fourteen sensors sit on the transformer: dissolved gas, moisture, partial discharge by UHF and acoustic methods, bushings, winding and top oil temperature, tap changer, cooling, oil level, gas relay, pressure relief, vibration and core earth current. Four collectors bring their signals to the monitoring IED. At station level the IED reaches a switch, a GPS time source, an edge gateway to SCADA, a server and a workstation, lights an alarm beacon, and sends a hard-wired alarm contact to the fire alarm panel. A legend, the three alarm level marks, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.
Kendi projelerinizde, ticari olanlar dahil, ücretsiz kullanabilir ve değiştirebilirsiniz. ZIP içinde örnek çizim, bir şablon, bir plot stili tablosu ve bir README bulunur; eklenti gerekmez. Çizimdeki veriler uydurmadır, bu yüzden tasarım ya da inşaat için kullanılamaz. Olduğu gibi sunulur, garanti verilmez. Kütüphane koşulları (CXL-1.0)
Bu örnek şu kaynakları kullanıyor
Semboller, öznitelikleri doldurulmuş olarak kendi kütüphanelerimizden gelen bloklardır. Pafta ve anteti, ISO A3 antet şablonumuzdan gelir. Kendi şemalarınızı çizmek için bunları indirin.
ZIP'in içinde ne var
- Transformer-Online-Monitoring-System-Sample.dwg
Örnek çizim (DWG, AutoCAD 2018 biçimi) - Process-Template-ISO-A3.dwt
Çizimin üzerinde hazırlandığı şablon (DWT) - CADXChange-Monochrome.ctb
Tüm renkleri siyah basan plot stili tablosu (CTB) - README.txt
Layer listesi ve dosyaların kullanımını anlatan README
Şablon
Proses şablonunda renkleri, çizgi kalınlıkları ve çizgi tipleriyle 14 layer vardır (ana, ikincil ve yardımcı hatlar, elektrik ve pnömatik sinyaller, ekipman, sınırlar, akış okları, etiketler, hat numaraları, yazı ve daha fazlası); ayrıca ISO-2.5'ten ISO-5'e yazı stilleri, ISO-25 ölçü stili ve antet ile revizyon tablosu olan bir ISO A3 layout'u bulunur. Layer adları yaygın bir düzendir, bir standart değildir; şirketinizin kurallarına uysun diye yeniden adlandırın.
Tanımlı layer'lar
Şablondaki her layer; rengi, çizgi kalınlığı ve çizgi tipiyle, ve bu örneğin kaç nesnesinin üzerinde olduğuyla. Örneğin kullanmadığı layer'lar da tanımlı kalır, kendi çiziminiz için hazırdır.
| Layer | Renk | Çizgi kalınlığı | Çizgi tipi | Kullanım | Buradaki nesneler |
|---|---|---|---|---|---|
| Proses layer'ları | |||||
| PROC-PIPE-MAIN | 5 | 0.50 mm | Continuous | Ana proses hatları | 9 |
| PROC-PIPE-SEC | 4 | 0.35 mm | Continuous | İkincil ve branşman proses hatları | burada kullanılmıyor |
| PROC-PIPE-UTIL | 30 | 0.35 mm | Continuous | Yardımcı hatlar (buhar, kondensat, soğutma suyu, hava) | burada kullanılmıyor |
| PROC-SIGNAL | 3 | 0.18 mm | DASHED | Elektrik sinyal hatları | 30 |
| PROC-PNEU | 6 | 0.18 mm | DASHDOT | Pnömatik ve kapiler sinyal hatları | burada kullanılmıyor |
| SYMBOL | 7 | 0.25 mm | Continuous | Semboller (sembol kütüphanelerinin kullandığı layer) | 26 |
| PROC-EQUIP | 7 | 0.35 mm | Continuous | Sembol kütüphaneleri dışında çizilen ekipman konturları | burada kullanılmıyor |
| PROC-BOUNDARY | 1 | 0.18 mm | DASHDOT | Paket, skid ve sınır limitleri | 2 |
| PROC-FLOW | 7 | 0.18 mm | Continuous | Akış okları ve akış yönü işaretleri | 1 |
| PROC-TAG | 7 | 0.18 mm | Continuous | Ekipman ve enstrüman etiketleri | burada kullanılmıyor |
| PROC-LINE-NO | 7 | 0.18 mm | Continuous | Hat numaraları ve hat spesifikasyonları | burada kullanılmıyor |
| PROC-TEXT | 7 | 0.18 mm | Continuous | Genel yazı | 33 |
| PROC-NOTES | 7 | 0.18 mm | Continuous | Notlar ve lejantlar | 13 |
| PROC-DIM | 3 | 0.18 mm | Continuous | Ölçülendirme | burada kullanılmıyor |
| Pafta ve sembol layer'ları | |||||
| 0 | 7 | varsayılan | Continuous | Varsayılan layer, boş bırakın | burada kullanılmıyor |
| FRAME | 7 | varsayılan | Continuous | Pafta kenarı | 5 |
| TITLEBLOCK | 7 | varsayılan | Continuous | Antet ve revizyon tablosu | 1 |
| VIEWPORT | 8 | varsayılan | Continuous | Layout viewport çerçevesi (basılmaz) | 2 |
| DRAWING-AREA | 8 | varsayılan | Continuous | Model çizim alanı sınırı (basılmaz) | 2 |
Tanımlı stiller
Şablonun tanımladığı yazı stilleri, ölçü stili ve çizgi tipleri; böylece her yeni çizimde kurmanız gerekmez.
| Tür | Ad | Ayarlar |
|---|---|---|
| Yazı stili | ISO | isocp.shx, 15°, değişken yükseklik |
| Yazı stili | ISO-2.5 | isocp.shx, 15°, 2.5 mm yükseklik |
| Yazı stili | ISO-3.5 | isocp.shx, 15°, 3.5 mm yükseklik |
| Yazı stili | ISO-5 | isocp.shx, 15°, 5 mm yükseklik |
| Yazı stili | TB-en | Arial, antette kullanılır |
| Ölçü stili | ISO-25 | Yazı 2.5 mm, oklar 2.5 mm, uzatma çizgileri ölçü çizgisinin 1.25 mm ötesine uzanır ve nesneden 0.625 mm uzakta durur, ölçü çizgileri arası 3.75 mm, 0 ondalık |
| Çizgi tipi | Continuous | Sürekli çizgi |
| Çizgi tipi | DASHED | Kesikli |
| Çizgi tipi | DASHDOT | Çizgi-nokta |
| Çizgi tipi | CENTER | Eksen çizgisi |
| Çizgi tipi | PHANTOM | Hayalet çizgi |
| Çizgi tipi | HIDDEN | Gizli çizgi |
Pafta ve çizim ayarı
Paftanın nasıl ayarlandığı; böylece kendi çizimleriniz de aynı şekilde basılır.
- Pafta
- ISO A3 yatay, 420 × 297 mm.
- Layout
- ISO-A3 adlı tek bir layout; kenar boşluksuz A3 ortamında 1:1 basılır, yani paftada yazıcı kenar boşluğu yoktur.
- Çerçeve
- Sol kenardan 20 mm (cilt tarafı) ve diğer kenarlardan 10 mm; içerideki çizim alanı 390 × 277 mm'dir.
- Model uzayı
- Birim milimetredir. Çizim alanı 1:1 gösterilir; yani çizimdeki 1 mm kâğıtta 1 mm'dir.
- Antet
- Sağ altta 160 × 79 mm; şirket, proje, başlık ve onay alanlarının üstünde dört satırlık bir revizyon tablosu bulunur.
- Yazı boyutu
- Etiketler ve notlar için 2,5 mm, başlıklar için 3,5 mm ve 5 mm.
- Çizgi tipi ölçeği
- 1; yani çizgi aralıkları 1:1 basım için boyutlandırılmıştır.
- Plot stili
- Ayarlanmamış. Siyah-beyaz baskı için sayfa yapısında ZIP'teki CTB'yi seçin.
Antet alanları
Antetin öznitelikleri.
| Öznitelik | Paftadaki alan | Bu örnekteki değer |
|---|---|---|
| COMPANY | COMPANY | CADXChange |
| PROJECT | PROJECT | 220 kV Substation |
| AREA | AREA | Transformer area |
| SYSTEM | SYSTEM | Condition monitoring |
| CLIENT | CLIENT | Sample |
| TITLE | DRAWING TITLE | Transformer online monitoring system |
| DRAWING_NO | DRAWING NO. | M-501 |
| CONTRACT_NO | CONTRACT NO. | — |
| REV | REV | A |
| DRAWN | DRAWN | — |
| CHECKED | CHECKED | — |
| APPROVED | APPROVED | — |
| DATE | DATE | 2026-11-25 |
| SCALE | SCALE | NTS |
| SHEET | SHEET | 1 |
| SHEET_OF | OF | 1 |
Revizyon tablosu: R1–R4, her biri REV, TARİH, AÇIKLAMA ve YAPAN alanlarıyla (16 öznitelik, bu örnekte boş).
Çizimdeki bloklar
Çizimin ekipman listesi: blok adı, sembol ve kaç kez yerleştirildiği.
| Sembol | Blok | Yerleştirilen |
|---|---|---|
| PMN_TR_MONITORED | 1 | |
| PMN_TR_DGA_MULTI | 1 | |
| PMN_TR_MOISTURE | 1 | |
| PMN_TR_PD_UHF | 1 | |
| PMN_TR_PD_AE | 1 | |
| PMN_TR_BUSHING | 1 | |
| PMN_TR_WINDING_FO | 1 | |
| PMN_TR_TOP_OIL_TEMP | 1 | |
| PMN_TR_COOLING | 1 | |
| PMN_TR_OLTC | 1 | |
| PMN_TR_OIL_LEVEL | 1 | |
| PMN_TR_BUCHHOLZ | 1 | |
| PMN_TR_PRV_MON | 1 | |
| PMN_TR_VIBRATION | 1 | |
| PMN_TR_CORE_GND | 1 | |
| PMN_TR_IED | 1 | |
| PMN_SYS_BEACON | 1 | |
| PMN_SYS_SWITCH | 1 | |
| PMN_SYS_TIME_SYNC | 1 | |
| PMN_SYS_EDGE_GW | 1 | |
| PMN_SYS_WORKSTATION | 1 | |
| PMN_SYS_SERVER | 1 | |
| PFP_FACP | 1 | |
| PMN_LEVEL_WARNING | 1 | |
| PMN_LEVEL_ALARM | 1 | |
| PMN_LEVEL_TRIP | 1 |
Ekipman listesi
Yerleştirilen her sembol için bir satır; çizimdeki blokların özniteliklerinden okunur: paftada gösterilenler ve doldurulmuş ama gösterilmeyen liste öznitelikleri.
| Etiket | Açıklama | Paftada gösterilen | Doldurulmuş, gösterilmeyen |
|---|---|---|---|
| T1 | Transformer, monitoredPMN_TR_MONITORED | TYPE = Power transformerRATING = 180 MVA, 220/110 kVLOCATION = Transformer T1 areaADDRESS = - | |
| DGA-1 | Oil gas monitor, multi-gasPMN_TR_DGA_MULTI | GAS = H2, CO, CH4, C2H2, C2H4, C2H6RANGE = H2 5-2000 ppmALARM_1 = H2 100 ppmALARM_2 = C2H2 5 ppmOUTPUT = IEC 61850, 4-20 mALOCATION = Transformer T1 areaADDRESS = 1 | |
| MST-1 | Oil moisture sensorPMN_TR_MOISTURE | MEASURAND = Moisture in oilRANGE = 0-100 % RSALARM_1 = 20 % RSALARM_2 = 30 % RSOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 2 | |
| PDU-1 | Partial discharge, UHFPMN_TR_PD_UHF | METHOD = UHFFREQUENCY_BAND = 300-1500 MHzSENSITIVITY_PC = 5CHANNELS = 2OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 3 | |
| PDA-1 | Partial discharge, acousticPMN_TR_PD_AE | METHOD = AcousticFREQUENCY_BAND = 20-300 kHzSENSITIVITY_PC = 10CHANNELS = 4OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 4 | |
| BSH-1 | Bushing monitorPMN_TR_BUSHING | MEASURAND = Capacitance and tan deltaRANGE = tan delta 0-2 %ALARM_1 = 0.7 %ALARM_2 = 1.0 %OUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 5 | |
| WT-1 | Winding temp, fibre opticPMN_TR_WINDING_FO | RANGE_C = 0-200ALARM_C = 110SENSOR_TYPE = Fibre opticOUTPUT = RS-485MONITORED_ITEM = HV winding hot spotLOCATION = Transformer T1 areaADDRESS = 6 | |
| OT-1 | Top oil temperaturePMN_TR_TOP_OIL_TEMP | RANGE_C = -20-120ALARM_C = 85SENSOR_TYPE = PT100OUTPUT = 4-20 mAMONITORED_ITEM = Top oilLOCATION = Transformer T1 areaADDRESS = 7 | |
| CL-1 | Cooler status monitorPMN_TR_COOLING | MEASURAND = Fan and pump statusRANGE = -ALARM_1 = Fan faultALARM_2 = Pump faultOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 8 | |
| OLTC-1 | Tap changer monitorPMN_TR_OLTC | MEASURAND = Motor current and positionRANGE = 0-5 AALARM_1 = 3.5 AALARM_2 = 4.5 AOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 9 | |
| OL-1 | Oil level monitorPMN_TR_OIL_LEVEL | MEASURAND = Conservator oil levelRANGE = 0-100 %ALARM_1 = 20 %ALARM_2 = 10 %OUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 10 | |
| BR-1 | Gas relay monitorPMN_TR_BUCHHOLZ | MEASURAND = Gas relay alarm and tripRANGE = -ALARM_1 = Gas collectedALARM_2 = Oil surgeOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 11 | |
| PR-1 | Pressure relief monitorPMN_TR_PRV_MON | MEASURAND = Pressure relief deviceRANGE = -ALARM_1 = -ALARM_2 = OperatedOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 12 | |
| VB-1 | Vibration sensorPMN_TR_VIBRATION | MEASURAND = Tank vibrationRANGE = 0-50 mm/sALARM_1 = 15 mm/sALARM_2 = 25 mm/sOUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 13 | |
| CG-1 | Core ground currentPMN_TR_CORE_GND | RATIO = 1000:1ACCURACY = 1INNER_DIAMETER_MM = 60CIRCUIT = Core earth strapTYPE = Split coreLOCATION = Transformer T1 area | |
| IED-1 | Transformer monitoring IEDPMN_TR_IED | CHANNELS = 24SUPPLY_V = 110 V DCCOMMUNICATION = IEC 61850OUTPUTS = 4MOUNTING = Marshalling kioskLOCATION = Transformer T1 areaADDRESS = 14 | |
| AB-1 | Alarm beacon columnPMN_SYS_BEACON | FUNCTION = Local alarm beaconPORTS = 1SUPPLY_V = 24 V DCPROTOCOL = Dry contactMOUNTING = PoleLOCATION = Transformer T1 areaADDRESS = 15 | |
| SW-1 | Network switchPMN_SYS_SWITCH | FUNCTION = Ethernet switchPORTS = 8SUPPLY_V = 24 V DCPROTOCOL = IEC 61850MOUNTING = DIN railLOCATION = Transformer T1 areaADDRESS = 16 | |
| TS-1 | Time synchronisationPMN_SYS_TIME_SYNC | FUNCTION = GPS time sourcePORTS = 2SUPPLY_V = 24 V DCPROTOCOL = PTP, IRIG-BMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 17 | |
| EG-1 | Edge gatewayPMN_SYS_EDGE_GW | FUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 18 | |
| WS-1 | Monitoring workstationPMN_SYS_WORKSTATION | FUNCTION = Operator workstationPORTS = 2SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = DeskLOCATION = Transformer T1 areaADDRESS = 19 | |
| SV-1 | ServerPMN_SYS_SERVER | FUNCTION = Monitoring serverPORTS = 4SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 20 | |
| FACP-1 | Fire alarm control panelPFP_FACP | ZONES = 8LOOPS = 2SUPPLY_V = 230 V AC, 24 V DCBATTERY_AH = 24COMMUNICATION = Serial link to gatewayLOCATION = Fire control roomADDRESS_RANGE = 1-250 | |
| LV-1 | Level mark, warningPMN_LEVEL_WARNING | TYPE = WarningRATING = Level 1LOCATION = Transformer T1 areaADDRESS = 21 | |
| LV-2 | Level mark, alarmPMN_LEVEL_ALARM | TYPE = AlarmRATING = Level 2LOCATION = Transformer T1 areaADDRESS = 22 | |
| LV-3 | Level mark, tripPMN_LEVEL_TRIP | TYPE = TripRATING = Level 3LOCATION = Transformer T1 areaADDRESS = 23 |
Üretici, model ve açıklamalar her blokta boş bırakılmıştır, verileriniz için hazırdır. Değerler örnektir.
Nasıl kullanılır
- Layer'ların, yazıların ve anteti nasıl kullanıldığını görmek için örnek çizimi açın; ya da önce tarayıcıda açın, hiçbir şey kurmanız gerekmez.
- Kendi çiziminize şablondan başlayın (NEW, sonra DWT dosyasını seçin). Siyah-beyaz baskı istiyorsanız CTB dosyasını plot stilleri klasörünüze kopyalayın.
- Sembol kütüphanesinden bloklarınızı çiziminize ekleyin. Örnekteki bloklar kopyadır; kütüphane değiştiğinde değişmezler.
Sık sorulan sorular
- Çizimi gerçek bir projede kullanabilir miyim?
- Yerleşim ve layer düzeni için bir başlangıç noktası olarak evet. Anma değerleri, ayarlar ve kablo kesitleri uydurmadır; bu yüzden şema, tasarım ya da inşaat için kullanılmadan önce projenize göre kontrol edilip değiştirilmelidir.
- Layer'lar neden renkli?
- Renkler ve çizgi kalınlıkları layer'ları izler: güç devreleri kırmızı ve kalın, kumanda camgöbeği, sinyal yeşildir. ZIP'teki plot stili tablosu her şeyi siyah basar ve çizgi kalınlıklarını korur; yani siyah-beyaz da basabilirsiniz.
- Hangi CAD programları açar?
- Çizim ve şablon, AutoCAD 2018 ve sonrasının açtığı AutoCAD 2018 biçimindedir; bu biçimi okuyan diğer CAD programları da açar. Tarayıcı görüntüleyici hiçbir kurulum gerektirmez.