A data centre with two independent power systems, in one drawing

Two utility feeds, two transformers, four generators, four UPS units, protection relays and the power monitoring system: every symbol from the Pro palette, placed and tagged on one sheet, with A and B sharing no equipment.

Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)

Version 1.0 · updated November 14, 2026

Free with a CADXChange account: sign in and the download starts. Up to 3 drawings a day.

This sample uses these resources

The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.

What is in the ZIP

  • Data-Centre-2N-Power-Single-Line-Sample.dwg
    Sample drawing (DWG, AutoCAD 2018 format)
  • Electrical-Template-ISO-A3.dwt
    Template (DWT) that the drawing was made on
  • CADXChange-Monochrome.ctb
    Plot style table (CTB) that prints every colour black
  • README.txt
    README with the layer list and how to use the files

The template

The electrical template has 16 layers with colours, line weights and linetypes (power circuits, busbars, control, signal, protective earth, enclosure boundaries, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.

Layers defined

Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.

LayerColourLine weightLinetypeUsed forObjects here
Electrical layers
ELEC-POWER10.50 mmContinuousMain power circuits50
ELEC-BUS10.70 mmContinuousBusbars and heavy lines4
ELEC-CONTROL40.25 mmContinuousControl circuitsnot used here
ELEC-SIGNAL30.18 mmContinuousSignal, instrumentation and communication circuits2
ELEC-PE20.35 mmContinuousProtective earth and bondingnot used here
ELEC-CABLE300.25 mmDASHEDCable, conduit and tray routesnot used here
SYMBOL70.25 mmContinuousSymbols (the layer the symbol libraries use)54
ELEC-TERMINAL70.25 mmContinuousTerminals and connection pointsnot used here
ELEC-BOUNDARY50.18 mmDASHDOTEnclosure, panel and device boundariesnot used here
ELEC-MECH-LINK80.18 mmDASHEDMechanical links, interlocks and measuring links6
ELEC-REF70.18 mmContinuousReference designations (-QF1, -K2)not used here
ELEC-WIRE-NO70.18 mmContinuousWire numbers and cable labelsnot used here
ELEC-XREF90.13 mmContinuousContact and cross reference textsnot used here
ELEC-TEXT70.18 mmContinuousGeneral text78
ELEC-NOTES70.18 mmContinuousNotes and legends5
ELEC-DIM30.18 mmContinuousDimensionsnot used here
Sheet and symbol layers
07defaultContinuousDefault layer, keep it emptynot used here
FRAME7defaultContinuousSheet border5
TITLEBLOCK7defaultContinuousTitle block and revision table1
VIEWPORT8defaultContinuousLayout viewport frame (does not plot)2
DRAWING-AREA8defaultContinuousBoundary of the model drawing area (does not plot)2

Styles defined

The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.

KindNameSettings
Text styleISOisocp.shx, 15°, variable height
Text styleISO-2.5isocp.shx, 15°, 2.5 mm high
Text styleISO-3.5isocp.shx, 15°, 3.5 mm high
Text styleISO-5isocp.shx, 15°, 5 mm high
Text styleTB-enArial, used by the title block
Dimension styleISO-25Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals
LinetypeContinuousSolid line
LinetypeDASHEDDashed
LinetypeDASHDOTDash-dot
LinetypeCENTERCentre line
LinetypePHANTOMPhantom line
LinetypeHIDDENHidden line

Sheet and drawing setup

How the sheet is set up, so your own drawings print the same way.

Sheet
ISO A3 landscape, 420 × 297 mm.
Layout
One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
Border
20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
Model space
Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
Title block
160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
Text size
2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
Linetype scale
1, so dashes are sized for plotting at 1:1.
Plot style
None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.

Title block fields

The attributes of the title block.

AttributeField on the sheetValue in this sample
COMPANYCOMPANYCADXChange
PROJECTPROJECTData centre, 2N power
AREAAREAUtility to IT racks
SYSTEMSYSTEM11 kV / 415 V
CLIENTCLIENTSample
TITLEDRAWING TITLEMain single line diagram
DRAWING_NODRAWING NO.E-881
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-15
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).

Blocks in the drawing

The equipment list of the drawing: block name, symbol and how many times it is placed.

SymbolBlockPlaced
Moulded case circuit breakerPWR_LV_MCCB8
Diesel generator setPWR_GEN_DIESEL4
Generator circuit breakerPWR_CB_GEN4
UPSPWR_UPS4
Data centre loadPWR_LOAD_DATA4
Grid infeed (utility source)PWR_GRID2
Disconnector, closedPWR_DISCONNECTOR_CLOSED2
Circuit breaker, vacuumPWR_CB_VCB2
Current transformerPWR_CT2
Transformer, delta-star, neutral earthedPWR_TX_DYN2
Air circuit breakerPWR_CB_ACB2
Relay, overcurrent (50/51)PWR_R_50512
Relay, transformer differential (87T)PWR_R_87T2
Relay, undervoltage (27)PWR_R_272
Variable frequency drivePWR_VFD2
Motor, inductionPWR_MOTOR_IM2
Distribution boardPWR_LV_DB2
Surge protective devicePWR_LV_SPD2
Protective earthPWR_EARTH_PE2
SCADA / HMIPWR_C_SCADA1
Protocol gatewayPWR_C_GATEWAY1

Equipment schedule

One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.

TagDescriptionShown on the sheetFilled in, not shown
G1Grid infeed (utility source)PWR_GRIDRATING = 250 MVAVOLTAGE_KV = 10
QS1Disconnector, closedPWR_DISCONNECTOR_CLOSEDRATED_KV = 12 kV
QF1Circuit breaker, vacuumPWR_CB_VCBRATED_KV = 12 kVRATED_CURRENT_A = 630BREAKING_KA = 25INTERRUPTER = VacuumMECHANISM = SpringCONTROL_VOLTAGE = 110 V DC
TA1Current transformerPWR_CTRATIO = 200/1 ACLASS = 5P20BURDEN_VA = 15CORES = 2RATED_KV = 12
T1Transformer, delta-star, neutral earthedPWR_TX_DYNRATING_MVA = 2.5 MVAVOLTAGE_RATIO = 10/0.4 kVVECTOR_GROUP = Dyn11IMPEDANCE_PCT = 6TAP_RANGE = +/-2x2.5%COOLING = ONANNEUTRAL_EARTHING = Solid
QF2Air circuit breakerPWR_CB_ACBRATED_KV = 0.415 kVRATED_CURRENT_A = 2500BREAKING_KA = 50INTERRUPTER = AirMECHANISM = Motor-charged springCONTROL_VOLTAGE = 110 V DC
F1Relay, overcurrent (50/51)PWR_R_5051
F2Relay, transformer differential (87T)PWR_R_87T
F3Relay, undervoltage (27)PWR_R_27
GS1Diesel generator setPWR_GEN_DIESELRATING_MVA = 2.0 MVAVOLTAGE_KV = 0.4POWER_FACTOR = 0.8SPEED_RPM = 1500EXCITATION = BrushlessCOOLING = Radiator
QF3Generator circuit breakerPWR_CB_GENRATED_KV = 0.415 kV
GS2Diesel generator setPWR_GEN_DIESELRATING_MVA = 2.0 MVAVOLTAGE_KV = 0.4POWER_FACTOR = 0.8SPEED_RPM = 1500EXCITATION = BrushlessCOOLING = Radiator
QF4Generator circuit breakerPWR_CB_GENRATED_KV = 0.415 kV
QF6Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 1600 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
UPS1UPSPWR_UPSRATING = 1000 kVAVOLTAGE_KV = 0.4UNITS = 1
QF7Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 1600 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
UPS2UPSPWR_UPSRATING = 1000 kVAVOLTAGE_KV = 0.4UNITS = 1
RKA1Data centre loadPWR_LOAD_DATAPOWER_KW = 800 kW
RKA2Data centre loadPWR_LOAD_DATAPOWER_KW = 800 kW
QF8Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 800 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
VF1Variable frequency drivePWR_VFDPOWER_KW = 450 kWVOLTAGE = 400 VPOWER_FACTOR = 0.95STARTING = Inverter
CH1Motor, inductionPWR_MOTOR_IMPOWER_KW = 450 kWVOLTAGE = 400 VPOWER_FACTOR = 0.85STARTING = Star-delta
QF9Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 400 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
DBADistribution boardPWR_LV_DBRATED_CURRENT_A = 400 AVOLTAGE = 400 VBREAKING_KA = 10TRIP_UNIT = Main switchPOLES = 4
SPASurge protective devicePWR_LV_SPDRATED_CURRENT_A = Type 1VOLTAGE = 400 VBREAKING_KA = 25TRIP_UNIT = Type 1+2POLES = 3+N
PEAProtective earthPWR_EARTH_PERESISTANCE_OHM = 10
G2Grid infeed (utility source)PWR_GRIDRATING = 250 MVAVOLTAGE_KV = 10
QS11Disconnector, closedPWR_DISCONNECTOR_CLOSEDRATED_KV = 12 kV
QF11Circuit breaker, vacuumPWR_CB_VCBRATED_KV = 12 kVRATED_CURRENT_A = 630BREAKING_KA = 25INTERRUPTER = VacuumMECHANISM = SpringCONTROL_VOLTAGE = 110 V DC
TA11Current transformerPWR_CTRATIO = 200/1 ACLASS = 5P20BURDEN_VA = 15CORES = 2RATED_KV = 12
T11Transformer, delta-star, neutral earthedPWR_TX_DYNRATING_MVA = 2.5 MVAVOLTAGE_RATIO = 10/0.4 kVVECTOR_GROUP = Dyn11IMPEDANCE_PCT = 6TAP_RANGE = +/-2x2.5%COOLING = ONANNEUTRAL_EARTHING = Solid
QF12Air circuit breakerPWR_CB_ACBRATED_KV = 0.415 kVRATED_CURRENT_A = 2500BREAKING_KA = 50INTERRUPTER = AirMECHANISM = Motor-charged springCONTROL_VOLTAGE = 110 V DC
F4Relay, overcurrent (50/51)PWR_R_5051
F5Relay, transformer differential (87T)PWR_R_87T
F6Relay, undervoltage (27)PWR_R_27
GS3Diesel generator setPWR_GEN_DIESELRATING_MVA = 2.0 MVAVOLTAGE_KV = 0.4POWER_FACTOR = 0.8SPEED_RPM = 1500EXCITATION = BrushlessCOOLING = Radiator
QF13Generator circuit breakerPWR_CB_GENRATED_KV = 0.415 kV
GS4Diesel generator setPWR_GEN_DIESELRATING_MVA = 2.0 MVAVOLTAGE_KV = 0.4POWER_FACTOR = 0.8SPEED_RPM = 1500EXCITATION = BrushlessCOOLING = Radiator
QF14Generator circuit breakerPWR_CB_GENRATED_KV = 0.415 kV
QF16Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 1600 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
UPS3UPSPWR_UPSRATING = 1000 kVAVOLTAGE_KV = 0.4UNITS = 1
QF17Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 1600 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
UPS4UPSPWR_UPSRATING = 1000 kVAVOLTAGE_KV = 0.4UNITS = 1
RKB1Data centre loadPWR_LOAD_DATAPOWER_KW = 800 kW
RKB2Data centre loadPWR_LOAD_DATAPOWER_KW = 800 kW
QF18Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 800 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
VF2Variable frequency drivePWR_VFDPOWER_KW = 450 kWVOLTAGE = 400 VPOWER_FACTOR = 0.95STARTING = Inverter
CH2Motor, inductionPWR_MOTOR_IMPOWER_KW = 450 kWVOLTAGE = 400 VPOWER_FACTOR = 0.85STARTING = Star-delta
QF19Moulded case circuit breakerPWR_LV_MCCBRATED_CURRENT_A = 400 AVOLTAGE = 400 VBREAKING_KA = 36TRIP_UNIT = Thermal-magneticPOLES = 3
DBBDistribution boardPWR_LV_DBRATED_CURRENT_A = 400 AVOLTAGE = 400 VBREAKING_KA = 10TRIP_UNIT = Main switchPOLES = 4
SPBSurge protective devicePWR_LV_SPDRATED_CURRENT_A = Type 1VOLTAGE = 400 VBREAKING_KA = 25TRIP_UNIT = Type 1+2POLES = 3+N
PEBProtective earthPWR_EARTH_PERESISTANCE_OHM = 10
EPMS1SCADA / HMIPWR_C_SCADA

Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.

How to use it

  1. Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
  2. Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
  3. Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.

Frequently asked questions

Can I use the drawing for a real project?
As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
Why are the layers coloured?
Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
Which CAD programs open it?
The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.