Industrial substation single-line diagram: sample DWG with ANSI device numbers

A finished single-line diagram of the main substation of a process plant, drawn in the American style. Two 13.8 kV utility feeders come in through current transformers, overcurrent relays, ammeters, watthour meters and breakers onto two buses joined by a tie breaker with a synchronism check. Two 5 MVA transformers with resistance grounded neutrals feed a second main-tie-main level at 4.16 kV, with a capacitor bank, a 3000 hp compressor motor, three more motors, a 2.5 MVA generator and two transformers to the motor control centres. Every feeder carries its protective device numbers, and the sheet has a device function legend, a breaker schedule, notes and a filled-in title block.

Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)

This sample uses these resources

The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.

What is in the ZIP

  • Industrial-Substation-ANSI-Sample.dwg
    Sample drawing (DWG, AutoCAD 2018 format)
  • Electrical-Template-ISO-A3.dwt
    Template (DWT) that the drawing was made on
  • CADXChange-Monochrome.ctb
    Plot style table (CTB) that prints every colour black
  • README.txt
    README with the layer list and how to use the files

The template

The electrical template has 16 layers with colours, line weights and linetypes (power circuits, busbars, control, signal, protective earth, enclosure boundaries, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.

Layers defined

Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.

LayerColourLine weightLinetypeUsed forObjects here
Electrical layers
ELEC-POWER10.50 mmContinuousMain power circuits30
ELEC-BUS10.70 mmContinuousBusbars and heavy lines4
ELEC-CONTROL40.25 mmContinuousControl circuitsnot used here
ELEC-SIGNAL30.18 mmContinuousSignal, instrumentation and communication circuitsnot used here
ELEC-PE20.35 mmContinuousProtective earth and bondingnot used here
ELEC-CABLE300.25 mmDASHEDCable, conduit and tray routesnot used here
SYMBOL70.25 mmContinuousSymbols (the layer the symbol libraries use)77
ELEC-TERMINAL70.25 mmContinuousTerminals and connection pointsnot used here
ELEC-BOUNDARY50.18 mmDASHDOTEnclosure, panel and device boundariesnot used here
ELEC-MECH-LINK80.18 mmDASHEDMechanical links, interlocks and measuring links28
ELEC-REF70.18 mmContinuousReference designations (-QF1, -K2)not used here
ELEC-WIRE-NO70.18 mmContinuousWire numbers and cable labels20
ELEC-XREF90.13 mmContinuousContact and cross reference textsnot used here
ELEC-TEXT70.18 mmContinuousGeneral text118
ELEC-NOTES70.18 mmContinuousNotes and legends10
ELEC-DIM30.18 mmContinuousDimensionsnot used here
Sheet and symbol layers
07defaultContinuousDefault layer, keep it emptynot used here
FRAME7defaultContinuousSheet border5
TITLEBLOCK7defaultContinuousTitle block and revision table1
VIEWPORT8defaultContinuousLayout viewport frame (does not plot)2
DRAWING-AREA8defaultContinuousBoundary of the model drawing area (does not plot)2

Styles defined

The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.

KindNameSettings
Text styleISOisocp.shx, 15°, variable height
Text styleISO-2.5isocp.shx, 15°, 2.5 mm high
Text styleISO-3.5isocp.shx, 15°, 3.5 mm high
Text styleISO-5isocp.shx, 15°, 5 mm high
Text styleTB-enArial, used by the title block
Dimension styleISO-25Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals
LinetypeContinuousSolid line
LinetypeDASHEDDashed
LinetypeDASHDOTDash-dot
LinetypeCENTERCentre line
LinetypePHANTOMPhantom line
LinetypeHIDDENHidden line

Sheet and drawing setup

How the sheet is set up, so your own drawings print the same way.

Sheet
ISO A3 landscape, 420 × 297 mm.
Layout
One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
Border
20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
Model space
Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
Title block
160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
Text size
2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
Linetype scale
1, so dashes are sized for plotting at 1:1.
Plot style
None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.

Title block fields

The attributes of the title block.

AttributeField on the sheetValue in this sample
COMPANYCOMPANYCADXChange
PROJECTPROJECTEastfield Process Plant
AREAAREAMain substation
SYSTEMSYSTEM13.8 kV / 4.16 kV / 60 Hz
CLIENTCLIENTSample
TITLEDRAWING TITLEMain substation single-line diagram, 13.8 kV and 4.16 kV
DRAWING_NODRAWING NO.E-861
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-23
SCALESCALENTS
SHEETSHEET1
OFOF1

Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).

Blocks in the drawing

The equipment list of the drawing: block name, symbol and how many times it is placed.

SymbolBlockPlaced
Protective device number, circleIEEE_DEVICE_NUMBER20
Circuit breaker, single pole (one-line)IEEE_BREAKER_1P16
Current transformer (one-line)IEEE_CT9
Ground (earth), generalIEEE_GROUND_EARTH7
Potential (voltage) transformer (one-line)IEEE_PT4
Protective device numbers, circle with two functionsIEEE_DEVICE_NUMBER_DUAL4
Transformer, two windings (circle form)IEEE_TRANSFORMER_CIRCLES4
Motor, generalIEEE_MOTOR4
AmmeterIEEE_METER_A2
Watthour meterIEEE_METER_WH2
Resistor, zigzagIEEE_RESISTOR_ZIGZAG2
Inductor, reactorIEEE_INDUCTOR1
Capacitor, two parallel linesIEEE_CAPACITOR_11
Generator, synchronousIEEE_GENERATOR_SYNC1

Equipment schedule

One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.

TagDescriptionShown on the sheetFilled in, not shown
52-TIE1Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 1200 AVOLTAGE = 13.8 kVBREAKING_KA = 25SERIES = Vacuum, drawout
25Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Synchronism check relaySETTING = dV 5 %, 10 deg, 0.1 Hz
52-TIE2Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 1200 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
25Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Synchronism check relaySETTING = dV 5 %, 10 deg, 0.1 Hz
TA-1Current transformer (one-line)IEEE_CTRATIO = 1200/5 A
52-1Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 1200 AVOLTAGE = 13.8 kVBREAKING_KA = 25SERIES = Vacuum, drawout
50/51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Instantaneous and time overcurrent relaySETTING = 1200/5 A, 1.0 pu
AAmmeterIEEE_METER_ARANGE = 1200 A
WHWatthour meterIEEE_METER_WHRANGE = kWh
TV-1Potential (voltage) transformer (one-line)IEEE_PTRATIO = 13800/120 V
27/59Protective device numbers, circle with two functionsIEEE_DEVICE_NUMBER_DUALDESCRIPTION = Under and overvoltage relaySETTING = 0.85 / 1.10 pu
TA-2Current transformer (one-line)IEEE_CTRATIO = 1200/5 A
52-2Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 1200 AVOLTAGE = 13.8 kVBREAKING_KA = 25SERIES = Vacuum, drawout
50/51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Instantaneous and time overcurrent relaySETTING = 1200/5 A, 1.0 pu
AAmmeterIEEE_METER_ARANGE = 1200 A
WHWatthour meterIEEE_METER_WHRANGE = kWh
TV-2Potential (voltage) transformer (one-line)IEEE_PTRATIO = 13800/120 V
27/59Protective device numbers, circle with two functionsIEEE_DEVICE_NUMBER_DUALDESCRIPTION = Under and overvoltage relaySETTING = 0.85 / 1.10 pu
52-F1Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 630 AVOLTAGE = 13.8 kVBREAKING_KA = 25SERIES = Vacuum, drawout
T1Transformer, two windings (circle form)IEEE_TRANSFORMER_CIRCLESRATING = 5 MVAVOLTAGE_PRIMARY = 13.8 kVVOLTAGE_SECONDARY = 4.16 kVIMPEDANCE = 6.5 %
TA-T1Current transformer (one-line)IEEE_CTRATIO = 1200/5 A
52-S1Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 1200 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
63Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Sudden pressure relaySETTING = Alarm and trip
51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Time overcurrent relaySETTING = 1200/5 A, 0.8 pu
86Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Lockout relaySETTING = Trips both breakers
52-F3Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 630 AVOLTAGE = 13.8 kVBREAKING_KA = 25SERIES = Vacuum, drawout
T2Transformer, two windings (circle form)IEEE_TRANSFORMER_CIRCLESRATING = 5 MVAVOLTAGE_PRIMARY = 13.8 kVVOLTAGE_SECONDARY = 4.16 kVIMPEDANCE = 6.5 %
TA-T2Current transformer (one-line)IEEE_CTRATIO = 1200/5 A
52-S2Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 1200 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
63Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Sudden pressure relaySETTING = Alarm and trip
51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Time overcurrent relaySETTING = 1200/5 A, 0.8 pu
86Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Lockout relaySETTING = Trips both breakers
52-F2Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 200 AVOLTAGE = 13.8 kVBREAKING_KA = 25SERIES = Vacuum, drawout
52-F4Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 200 AVOLTAGE = 13.8 kVBREAKING_KA = 25SERIES = Vacuum, drawout
TA-M4Current transformer (one-line)IEEE_CTRATIO = 200/5 A
M4Motor, generalIEEE_MOTORRATING = 3000 hpVOLTAGE = 13.8 kVPHASES = 3SPEED_RPM = 1800
49Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Thermal overload relaySETTING = Class 30
50/51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Overcurrent relaySETTING = 200/5 A, 1.0 pu
TV-3Potential (voltage) transformer (one-line)IEEE_PTRATIO = 4160/120 V
27/59Protective device numbers, circle with two functionsIEEE_DEVICE_NUMBER_DUALDESCRIPTION = Under and overvoltage relaySETTING = 0.80 / 1.10 pu
TV-4Potential (voltage) transformer (one-line)IEEE_PTRATIO = 4160/120 V
27/59Protective device numbers, circle with two functionsIEEE_DEVICE_NUMBER_DUALDESCRIPTION = Under and overvoltage relaySETTING = 0.80 / 1.10 pu
52-M1Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 630 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
TA-M1Current transformer (one-line)IEEE_CTRATIO = 300/5 A
M1Motor, generalIEEE_MOTORRATING = 1500 hpVOLTAGE = 4.16 kVPHASES = 3SPEED_RPM = 1800
49Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Thermal overload relaySETTING = Class 20
50/51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Overcurrent relaySETTING = 300/5 A, 1.0 pu
52-M2Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 630 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
TA-M2Current transformer (one-line)IEEE_CTRATIO = 300/5 A
M2Motor, generalIEEE_MOTORRATING = 1000 hpVOLTAGE = 4.16 kVPHASES = 3SPEED_RPM = 1800
49Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Thermal overload relaySETTING = Class 20
50/51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Overcurrent relaySETTING = 300/5 A, 1.0 pu
52-M3Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 630 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
TA-M3Current transformer (one-line)IEEE_CTRATIO = 300/5 A
M3Motor, generalIEEE_MOTORRATING = 800 hpVOLTAGE = 4.16 kVPHASES = 3SPEED_RPM = 1800
49Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Thermal overload relaySETTING = Class 20
50/51Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Overcurrent relaySETTING = 300/5 A, 1.0 pu
52-G1Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 630 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
TA-G1Current transformer (one-line)IEEE_CTRATIO = 300/5 A
G1Generator, synchronousIEEE_GENERATOR_SYNCRATING = 2.5 MVAVOLTAGE = 4.16 kVPHASES = 3SPEED_RPM = 1800
32Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Reverse power relaySETTING = -5 %
40Protective device number, circleIEEE_DEVICE_NUMBERDESCRIPTION = Loss of field relaySETTING = Mho circle
52-L1Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 400 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
T3Transformer, two windings (circle form)IEEE_TRANSFORMER_CIRCLESRATING = 1500 kVAVOLTAGE_PRIMARY = 4.16 kVVOLTAGE_SECONDARY = 0.48 kVIMPEDANCE = 6.5 %
52-L2Circuit breaker, single pole (one-line)IEEE_BREAKER_1PRATING = 400 AVOLTAGE = 4.16 kVBREAKING_KA = 40SERIES = Vacuum, drawout
T4Transformer, two windings (circle form)IEEE_TRANSFORMER_CIRCLESRATING = 1500 kVAVOLTAGE_PRIMARY = 4.16 kVVOLTAGE_SECONDARY = 0.48 kVIMPEDANCE = 6.5 %

Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.

How to use it

  1. Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
  2. Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
  3. Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.

Frequently asked questions

Can I use the drawing for a real project?
As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
Why are the layers coloured?
Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
Which CAD programs open it?
The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.