Battery storage fire protection layout: sample DWG of a container yard

The fire protection of a battery energy storage site, drawn as a layout. Six battery containers stand in two rows, each with its own water connection on a fire water ring main, and a 3 m separation mark shows the clear distance between neighbours. A signal trunk runs under the yard to the fire alarm panel, the annunciator, the emergency power off, the remote shutdown and the battery management interface. On the right a typical container is opened up: four battery racks, thermal runaway, off-gas and electrolyte vapour detectors under the roof, a deflagration vent, an explosion-proof exhaust fan with a make-up air louver, and water mist nozzles fed from the container's water connection. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)

This sample uses these resources

The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.

What is in the ZIP

  • Battery-Storage-Fire-Protection-Layout-Sample.dwg
    Sample drawing (DWG, AutoCAD 2018 format)
  • Process-Template-ISO-A3.dwt
    Template (DWT) that the drawing was made on
  • CADXChange-Monochrome.ctb
    Plot style table (CTB) that prints every colour black
  • README.txt
    README with the layer list and how to use the files

The template

The process template has 14 layers with colours, line weights and linetypes (main, secondary and utility lines, electrical and pneumatic signals, equipment, boundaries, flow arrows, tags, line numbers, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.

Layers defined

Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.

LayerColourLine weightLinetypeUsed forObjects here
Process layers
PROC-PIPE-MAIN50.50 mmContinuousMain process lines23
PROC-PIPE-SEC40.35 mmContinuousSecondary and branch process linesnot used here
PROC-PIPE-UTIL300.35 mmContinuousUtility lines (steam, condensate, cooling water, air)not used here
PROC-SIGNAL30.18 mmDASHEDElectrical signal lines33
PROC-PNEU60.18 mmDASHDOTPneumatic and capillary signal linesnot used here
SYMBOL70.25 mmContinuousSymbols (the layer the symbol libraries use)36
PROC-EQUIP70.35 mmContinuousEquipment outlines drawn outside the symbol libraries4
PROC-BOUNDARY10.18 mmDASHDOTPackage, skid and battery limitsnot used here
PROC-FLOW70.18 mmContinuousFlow arrows and flow direction marks1
PROC-TAG70.18 mmContinuousEquipment and instrument tagsnot used here
PROC-LINE-NO70.18 mmContinuousLine numbers and line specificationsnot used here
PROC-TEXT70.18 mmContinuousGeneral text30
PROC-NOTES70.18 mmContinuousNotes and legends14
PROC-DIM30.18 mmContinuousDimensionsnot used here
Sheet and symbol layers
07defaultContinuousDefault layer, keep it emptynot used here
FRAME7defaultContinuousSheet border5
TITLEBLOCK7defaultContinuousTitle block and revision table1
VIEWPORT8defaultContinuousLayout viewport frame (does not plot)2
DRAWING-AREA8defaultContinuousBoundary of the model drawing area (does not plot)2

Styles defined

The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.

KindNameSettings
Text styleISOisocp.shx, 15°, variable height
Text styleISO-2.5isocp.shx, 15°, 2.5 mm high
Text styleISO-3.5isocp.shx, 15°, 3.5 mm high
Text styleISO-5isocp.shx, 15°, 5 mm high
Text styleTB-enArial, used by the title block
Dimension styleISO-25Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals
LinetypeContinuousSolid line
LinetypeDASHEDDashed
LinetypeDASHDOTDash-dot
LinetypeCENTERCentre line
LinetypePHANTOMPhantom line
LinetypeHIDDENHidden line

Sheet and drawing setup

How the sheet is set up, so your own drawings print the same way.

Sheet
ISO A3 landscape, 420 × 297 mm.
Layout
One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
Border
20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
Model space
Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
Title block
160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
Text size
2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
Linetype scale
1, so dashes are sized for plotting at 1:1.
Plot style
None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.

Title block fields

The attributes of the title block.

AttributeField on the sheetValue in this sample
COMPANYCOMPANYCADXChange
PROJECTPROJECTBattery Storage Station
AREAAREABattery yard
SYSTEMSYSTEMFire protection
CLIENTCLIENTSample
TITLEDRAWING TITLEBattery storage fire protection layout
DRAWING_NODRAWING NO.F-502
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).

Blocks in the drawing

The equipment list of the drawing: block name, symbol and how many times it is placed.

SymbolBlockPlaced
Water supply connectionPFP_WATER_CONN7
Battery containerPFP_BATT_CONTAINER6
Battery rackPFP_BATT_RACK4
Separation distance, 3 mPFP_SEP_3M2
BMS interfacePFP_BMS_INTERFACE2
Thermal runaway detectorPFP_TR_DETECTOR2
Suppression nozzle, containerPFP_SUPP_NOZZLE_CONT2
Sectional valve, OS&YPFP_VALVE_OSY1
Hydrant, pillarPFP_HYDRANT_PILLAR1
Fire alarm control panelPFP_FACP1
Remote annunciatorPFP_ANNUNCIATOR1
Emergency power offPFP_EPO1
Remote shutdownPFP_REMOTE_SHUTDOWN1
Off-gas detectorPFP_OFFGAS_DETECTOR1
Electrolyte vapour detectorPFP_VAPOUR_DETECTOR1
Deflagration ventPFP_DEFLAG_VENT1
Exhaust fan, explosion-proofPFP_EXHAUST_FAN_EX1
Make-up air louverPFP_MAKEUP_LOUVRE1

Equipment schedule

One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.

TagDescriptionShown on the sheetFilled in, not shown
BC-1Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-1Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-2Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-2Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-3Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-3Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-4Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-4Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-5Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-5Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
BC-6Battery containerPFP_BATT_CONTAINERCAPACITY_KWH = 3000CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Gas detection, venting, fire water connectionZONE = BESS yardLOCATION = BESS yard
WC-6Water supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
SD-1Separation distance, 3 mPFP_SEP_3MZONE = BESS yardAREA_M2 = -RATING_H = -HAZARD = Battery container firePROTECTION = 3 m clear distanceLOCATION = BESS yard
SD-2Separation distance, 3 mPFP_SEP_3MZONE = BESS yardAREA_M2 = -RATING_H = -HAZARD = Battery container firePROTECTION = 3 m clear distanceLOCATION = BESS yard
V-1Sectional valve, OS&YPFP_VALVE_OSYSIZE_DN = 200PRESSURE_RATING = PN16ACTUATION = HandwheelSERVICE = Fire waterMATERIAL = Ductile ironSUPERVISED = YesZONE = Transformer area
HY-1Hydrant, pillarPFP_HYDRANT_PILLARSIZE_DN = 100OUTLETS = 2FLOW_LPS = 15PRESSURE_BAR = 4ZONE = Transformer areaLOCATION = Transformer area
FACP-1Fire alarm control panelPFP_FACPZONES = 8LOOPS = 2SUPPLY_V = 230 V AC, 24 V DCBATTERY_AH = 24COMMUNICATION = Serial link to gatewayLOCATION = Fire control roomADDRESS_RANGE = 1-250
ANN-1Remote annunciatorPFP_ANNUNCIATORZONES = 8SUPPLY_V = 24 V DCCOMMUNICATION = RS-485 from FACP-1LOCATION = Fire control room
EPO-1Emergency power offPFP_EPOTYPE = Mushroom, latchingZONE = Transformer areaLOOP = 1ADDRESS = 160ENCLOSURE = IP66MOUNTING_HEIGHT_M = 1.4FUNCTION = Trips the storage system
RS-1Remote shutdownPFP_REMOTE_SHUTDOWNTYPE = Remote trip inputZONE = Transformer areaLOOP = 1ADDRESS = 161ENCLOSURE = IP54MOUNTING_HEIGHT_M = -FUNCTION = Trip from the control centre
BMS-1BMS interfacePFP_BMS_INTERFACEZONES = 1LOOPS = -SUPPLY_V = 24 V DCBATTERY_AH = -COMMUNICATION = Modbus TCPLOCATION = Transformer area
R-1Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
R-2Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
R-3Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
R-4Battery rackPFP_BATT_RACKCAPACITY_KWH = 250CHEMISTRY = LFPVOLTAGE_V = 1228PROTECTION = Rack-level detectionZONE = BESS yardLOCATION = BESS yard
TR-1Thermal runaway detectorPFP_TR_DETECTORGAS = Thermal runaway gasesRANGE = 0-100 % LELALARM_1 = 10 % LELALARM_2 = 25 % LELZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
OG-1Off-gas detectorPFP_OFFGAS_DETECTORGAS = Battery off-gasRANGE = 0-100 % LELALARM_1 = 10 % LELALARM_2 = 25 % LELZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
TR-2Thermal runaway detectorPFP_TR_DETECTORGAS = Thermal runaway gasesRANGE = 0-100 % LELALARM_1 = 10 % LELALARM_2 = 25 % LELZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
VD-1Electrolyte vapour detectorPFP_VAPOUR_DETECTORGAS = Electrolyte vapourRANGE = 0-100 ppmALARM_1 = 10 ppmALARM_2 = 25 ppmZONE = BESS yardLOOP = 1ADDRESS = 1OUTPUT = Relay, 4-20 mA
BMS-2BMS interfacePFP_BMS_INTERFACEZONES = 1LOOPS = -SUPPLY_V = 24 V DCBATTERY_AH = -COMMUNICATION = Modbus TCPLOCATION = Transformer area
DV-1Deflagration ventPFP_DEFLAG_VENTRATING_H = -SIZE_MM = 800 x 800ACTUATION = PressureRELEASE_TEMP_C = -ZONE = Transformer areaLOCATION = Transformer area
EF-1Exhaust fan, explosion-proofPFP_EXHAUST_FAN_EXRATING_H = -SIZE_MM = DN500ACTUATION = On gas alarmRELEASE_TEMP_C = -ZONE = Transformer areaLOCATION = Transformer area
ML-1Make-up air louverPFP_MAKEUP_LOUVRERATING_H = -SIZE_MM = 600 x 400ACTUATION = MotorisedRELEASE_TEMP_C = -ZONE = Transformer areaLOCATION = Transformer area
WC-nWater supply connectionPFP_WATER_CONNSIZE_DN = 100OUTLETS = 1FLOW_LPS = 20PRESSURE_BAR = 6ZONE = BESS yardLOCATION = BESS yard
SN-1Suppression nozzle, containerPFP_SUPP_NOZZLE_CONTAGENT = Water mistFLOW_KGS = -ORIFICE_MM = 1.5COVERAGE_M2 = 10MOUNTING = CeilingZONE = Transformer area
SN-2Suppression nozzle, containerPFP_SUPP_NOZZLE_CONTAGENT = Water mistFLOW_KGS = -ORIFICE_MM = 1.5COVERAGE_M2 = 10MOUNTING = CeilingZONE = Transformer area

Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.

How to use it

  1. Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
  2. Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
  3. Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.

Frequently asked questions

Can I use the drawing for a real project?
As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
Why are the layers coloured?
Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
Which CAD programs open it?
The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.