Cable spreading room fire protection: sample DWG of a clean agent system

The fire protection of a cable spreading room, drawn as one sheet. On the left the agent store holds a bank of cylinders with a release solenoid and a check valve; the discharge pipe passes through a sealed penetration in the fire-rated wall and feeds three nozzles in the room. Two cable trays enter through penetration seals. The room is watched three ways: an aspirating unit with four sampling points on the ceiling, two multi-criteria smoke detectors and linear heat cable along the trays, all wired to a releasing panel outside. The panel drives a delay timer, a pre-discharge alarm, a door hold-open, a fire damper, an agent released lamp, a manual release and an abort switch, and a pressure relief vent protects the walls. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)

This sample uses these resources

The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.

What is in the ZIP

  • Cable-Spreading-Room-Fire-Protection-Sample.dwg
    Sample drawing (DWG, AutoCAD 2018 format)
  • Process-Template-ISO-A3.dwt
    Template (DWT) that the drawing was made on
  • CADXChange-Monochrome.ctb
    Plot style table (CTB) that prints every colour black
  • README.txt
    README with the layer list and how to use the files

The template

The process template has 14 layers with colours, line weights and linetypes (main, secondary and utility lines, electrical and pneumatic signals, equipment, boundaries, flow arrows, tags, line numbers, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.

Layers defined

Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.

LayerColourLine weightLinetypeUsed forObjects here
Process layers
PROC-PIPE-MAIN50.50 mmContinuousMain process lines11
PROC-PIPE-SEC40.35 mmContinuousSecondary and branch process lines5
PROC-PIPE-UTIL300.35 mmContinuousUtility lines (steam, condensate, cooling water, air)not used here
PROC-SIGNAL30.18 mmDASHEDElectrical signal lines31
PROC-PNEU60.18 mmDASHDOTPneumatic and capillary signal linesnot used here
SYMBOL70.25 mmContinuousSymbols (the layer the symbol libraries use)31
PROC-EQUIP70.35 mmContinuousEquipment outlines drawn outside the symbol libraries21
PROC-BOUNDARY10.18 mmDASHDOTPackage, skid and battery limitsnot used here
PROC-FLOW70.18 mmContinuousFlow arrows and flow direction marks2
PROC-TAG70.18 mmContinuousEquipment and instrument tagsnot used here
PROC-LINE-NO70.18 mmContinuousLine numbers and line specificationsnot used here
PROC-TEXT70.18 mmContinuousGeneral text32
PROC-NOTES70.18 mmContinuousNotes and legends12
PROC-DIM30.18 mmContinuousDimensionsnot used here
Sheet and symbol layers
07defaultContinuousDefault layer, keep it emptynot used here
FRAME7defaultContinuousSheet border5
TITLEBLOCK7defaultContinuousTitle block and revision table1
VIEWPORT8defaultContinuousLayout viewport frame (does not plot)2
DRAWING-AREA8defaultContinuousBoundary of the model drawing area (does not plot)2

Styles defined

The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.

KindNameSettings
Text styleISOisocp.shx, 15°, variable height
Text styleISO-2.5isocp.shx, 15°, 2.5 mm high
Text styleISO-3.5isocp.shx, 15°, 3.5 mm high
Text styleISO-5isocp.shx, 15°, 5 mm high
Text styleTB-enArial, used by the title block
Dimension styleISO-25Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals
LinetypeContinuousSolid line
LinetypeDASHEDDashed
LinetypeDASHDOTDash-dot
LinetypeCENTERCentre line
LinetypePHANTOMPhantom line
LinetypeHIDDENHidden line

Sheet and drawing setup

How the sheet is set up, so your own drawings print the same way.

Sheet
ISO A3 landscape, 420 × 297 mm.
Layout
One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
Border
20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
Model space
Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
Title block
160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
Text size
2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
Linetype scale
1, so dashes are sized for plotting at 1:1.
Plot style
None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.

Title block fields

The attributes of the title block.

AttributeField on the sheetValue in this sample
COMPANYCOMPANYCADXChange
PROJECTPROJECTPower Plant
AREAAREACable spreading room
SYSTEMSYSTEMFire protection
CLIENTCLIENTSample
TITLEDRAWING TITLECable spreading room fire protection
DRAWING_NODRAWING NO.F-503
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).

Blocks in the drawing

The equipment list of the drawing: block name, symbol and how many times it is placed.

SymbolBlockPlaced
Sampling pointPFP_SAMPLING_POINT4
Cable penetration sealPFP_CABLE_SEAL3
Discharge nozzle, 360PFP_NOZZLE_3603
Linear heat cablePFP_LHC2
Smoke detector, multi-criteriaPFP_SMOKE_MULTI2
Cylinder bank, 8PFP_BANK_81
Release solenoidPFP_SOLENOID1
Solenoid control modulePFP_MOD_SOLENOID1
Check valve, manifoldPFP_CHECK_MANIFOLD1
Discharge pressure switchPFP_DISCH_PS1
Pipe penetration sealPFP_PIPE_SEAL1
Aspirating unitPFP_ASPIRATING1
Fire door, doublePFP_DOOR_DOUBLE1
Pressure relief ventPFP_RELIEF_VENT1
Releasing control panelPFP_RELEASE_PANEL1
Time delayPFP_TIME_DELAY1
Pre-discharge horn, strobePFP_PREDISCH_ALARM1
Door hold-openPFP_DOOR_HOLD1
Agent released lampPFP_AGENT_LAMP1
Fire damperPFP_FIRE_DAMPER1
Manual release stationPFP_MANUAL_RELEASE1
Abort switchPFP_ABORT1

Equipment schedule

One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.

TagDescriptionShown on the sheetFilled in, not shown
CS-1Cable penetration sealPFP_CABLE_SEALRATING_H = 2PENETRANT = Cable traySIZE_MM = 600 x 100SEAL_SYSTEM = Intumescent mortarZONE = Transformer areaLOCATION = Transformer area
CS-2Cable penetration sealPFP_CABLE_SEALRATING_H = 2PENETRANT = Cable traySIZE_MM = 600 x 100SEAL_SYSTEM = Intumescent mortarZONE = Transformer areaLOCATION = Transformer area
CB-1Cylinder bank, 8PFP_BANK_8AGENT = HFC-227eaFILL_KG = 8 x 90VOLUME_L = 8 x 120PRESSURE_BAR = 42DISCHARGE_S = 10ZONE = Transformer areaLOCATION = Transformer area
SOL-1Release solenoidPFP_SOLENOIDADDRESS = -LOOP = -ZONE = Transformer areaFUNCTION = Releases the pilot cylinderVOLTAGE_V = 24CIRCUIT = Release circuit 1LOCATION = Transformer area
SCM-1Solenoid control modulePFP_MOD_SOLENOIDADDRESS = 213LOOP = 1ZONE = Transformer areaFUNCTION = Drives the release solenoidVOLTAGE_V = 24CIRCUIT = Release circuit 1LOCATION = Transformer area
CM-1Check valve, manifoldPFP_CHECK_MANIFOLDSIZE_DN = 80PRESSURE_RATING = PN63ACTUATION = Spring returnSERVICE = Clean agentMATERIAL = SteelSUPERVISED = NoZONE = Transformer area
DPS-1Discharge pressure switchPFP_DISCH_PSSETTING = 5 barCONTACTS = 1 NOENCLOSURE = IP65SERVICE = Agent discharge feedbackZONE = Transformer areaLOOP = 1ADDRESS = 212
PS-1Pipe penetration sealPFP_PIPE_SEALRATING_H = 2PENETRANT = Steel pipe DN80SIZE_MM = DN80SEAL_SYSTEM = Intumescent collarZONE = Transformer areaLOCATION = Transformer area
NZ-1Discharge nozzle, 360PFP_NOZZLE_360AGENT = HFC-227eaFLOW_KGS = 5ORIFICE_MM = 8COVERAGE_M2 = 50MOUNTING = CeilingZONE = Transformer area
NZ-2Discharge nozzle, 360PFP_NOZZLE_360AGENT = HFC-227eaFLOW_KGS = 5ORIFICE_MM = 8COVERAGE_M2 = 50MOUNTING = CeilingZONE = Transformer area
NZ-3Discharge nozzle, 360PFP_NOZZLE_360AGENT = HFC-227eaFLOW_KGS = 5ORIFICE_MM = 8COVERAGE_M2 = 50MOUNTING = CeilingZONE = Transformer area
ASP-1Aspirating unitPFP_ASPIRATINGDETECTOR_TYPE = Aspirating smokeZONE = Transformer areaLOOP = 1ADDRESS = 205COVERAGE_M2 = 600MOUNTING = WallRESPONSE = Under 60 sENCLOSURE = IP54
SP-1Sampling pointPFP_SAMPLING_POINTDETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = -
SP-2Sampling pointPFP_SAMPLING_POINTDETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = -
SP-3Sampling pointPFP_SAMPLING_POINTDETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = -
SP-4Sampling pointPFP_SAMPLING_POINTDETECTOR_TYPE = Sampling pointZONE = Transformer areaLOOP = -ADDRESS = -COVERAGE_M2 = 50MOUNTING = CeilingRESPONSE = -ENCLOSURE = -
LH-1Linear heat cablePFP_LHCCABLE_TYPE = Digital linear heatLENGTH_M = 40ALARM_TEMP_C = 70ZONE = Transformer areaLOOP = 1ADDRESS = 201MOUNTING = Clipped along the tray
LH-2Linear heat cablePFP_LHCCABLE_TYPE = Digital linear heatLENGTH_M = 40ALARM_TEMP_C = 70ZONE = Transformer areaLOOP = 1ADDRESS = 201MOUNTING = Clipped along the tray
SD-1Smoke detector, multi-criteriaPFP_SMOKE_MULTIDETECTOR_TYPE = Multi-criteria smokeZONE = Transformer areaLOOP = 1ADDRESS = 202COVERAGE_M2 = 40MOUNTING = CeilingRESPONSE = Under 30 sENCLOSURE = IP40
SD-2Smoke detector, multi-criteriaPFP_SMOKE_MULTIDETECTOR_TYPE = Multi-criteria smokeZONE = Transformer areaLOOP = 1ADDRESS = 202COVERAGE_M2 = 40MOUNTING = CeilingRESPONSE = Under 30 sENCLOSURE = IP40
CS-3Cable penetration sealPFP_CABLE_SEALRATING_H = 2PENETRANT = Cable traySIZE_MM = 600 x 100SEAL_SYSTEM = Intumescent mortarZONE = Transformer areaLOCATION = Transformer area
DR-1Fire door, doublePFP_DOOR_DOUBLERATING_H = 2MATERIAL = SteelTHICKNESS_MM = 60TEST_STANDARD = Local codeLOCATION = Transformer areaZONE = Transformer area
RV-1Pressure relief ventPFP_RELIEF_VENTZONE = Transformer areaLOCATION = Transformer area
RP-1Releasing control panelPFP_RELEASE_PANELZONES = 2LOOPS = 1SUPPLY_V = 24 V DCBATTERY_AH = 12COMMUNICATION = Hardwired to FACP-1LOCATION = Fire control roomADDRESS_RANGE = -
TD-1Time delayPFP_TIME_DELAYADDRESS = -LOOP = -ZONE = Transformer areaFUNCTION = Pre-discharge delay, 30 sVOLTAGE_V = 24CIRCUIT = Release circuit 1LOCATION = Transformer area
PD-1Pre-discharge horn, strobePFP_PREDISCH_ALARMSOUND_DB = 100CANDELA = 75VOLTAGE_V = 24MOUNTING = CeilingCIRCUIT = Sounder circuit 1ZONE = Transformer areaENCLOSURE = IP54
DH-1Door hold-openPFP_DOOR_HOLDADDRESS = -LOOP = -ZONE = Transformer areaFUNCTION = Releases the door on alarmVOLTAGE_V = 24CIRCUIT = Door circuit 1LOCATION = Transformer area
AL-1Agent released lampPFP_AGENT_LAMPSOUND_DB = -CANDELA = -VOLTAGE_V = 24MOUNTING = Above the doorCIRCUIT = Lamp circuit 1ZONE = Transformer areaENCLOSURE = IP54
FD-1Fire damperPFP_FIRE_DAMPERRATING_H = 2SIZE_MM = 600 x 400ACTUATION = Motorised, closes on releaseRELEASE_TEMP_C = 72ZONE = Transformer areaLOCATION = Transformer area
MR-1Manual release stationPFP_MANUAL_RELEASETYPE = Break glass, dual actionZONE = Transformer areaLOOP = 1ADDRESS = 210ENCLOSURE = IP54MOUNTING_HEIGHT_M = 1.4FUNCTION = Starts the discharge sequence
AB-1Abort switchPFP_ABORTTYPE = Hold-to-runZONE = Transformer areaLOOP = 1ADDRESS = 211ENCLOSURE = IP54MOUNTING_HEIGHT_M = 1.4FUNCTION = Holds the time delay

Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.

How to use it

  1. Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
  2. Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
  3. Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.

Frequently asked questions

Can I use the drawing for a real project?
As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
Why are the layers coloured?
Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
Which CAD programs open it?
The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.