Cable tunnel monitoring and inspection robot layout: sample DWG

The monitoring of a 110 kV cable tunnel, drawn as a plan. The control room on the left holds the distributed temperature unit, a protocol converter, an edge gateway to SCADA, a switch, the thermal image gateway and the robot base station. A temperature sensing fibre runs along the cable tray in three zones, with temperature monitors at two joints, a sheath current monitor and a tunnel point sensor. A sensor bus carries temperature and humidity, oxygen, cameras, wireless nodes and the water level, and two water leak cables lie on the floor. A rail-hung inspection robot runs from its dock along a ceiling rail and stops at inspection points under the joints. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)

This sample uses these resources

The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.

What is in the ZIP

  • Cable-Tunnel-Monitoring-Sample.dwg
    Sample drawing (DWG, AutoCAD 2018 format)
  • Process-Template-ISO-A3.dwt
    Template (DWT) that the drawing was made on
  • CADXChange-Monochrome.ctb
    Plot style table (CTB) that prints every colour black
  • README.txt
    README with the layer list and how to use the files

The template

The process template has 14 layers with colours, line weights and linetypes (main, secondary and utility lines, electrical and pneumatic signals, equipment, boundaries, flow arrows, tags, line numbers, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.

Layers defined

Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.

LayerColourLine weightLinetypeUsed forObjects here
Process layers
PROC-PIPE-MAIN50.50 mmContinuousMain process lines15
PROC-PIPE-SEC40.35 mmContinuousSecondary and branch process lines3
PROC-PIPE-UTIL300.35 mmContinuousUtility lines (steam, condensate, cooling water, air)not used here
PROC-SIGNAL30.18 mmDASHEDElectrical signal linesnot used here
PROC-PNEU60.18 mmDASHDOTPneumatic and capillary signal lines22
SYMBOL70.25 mmContinuousSymbols (the layer the symbol libraries use)28
PROC-EQUIP70.35 mmContinuousEquipment outlines drawn outside the symbol libraries5
PROC-BOUNDARY10.18 mmDASHDOTPackage, skid and battery limits2
PROC-FLOW70.18 mmContinuousFlow arrows and flow direction marks1
PROC-TAG70.18 mmContinuousEquipment and instrument tagsnot used here
PROC-LINE-NO70.18 mmContinuousLine numbers and line specificationsnot used here
PROC-TEXT70.18 mmContinuousGeneral text30
PROC-NOTES70.18 mmContinuousNotes and legends11
PROC-DIM30.18 mmContinuousDimensionsnot used here
Sheet and symbol layers
07defaultContinuousDefault layer, keep it emptynot used here
FRAME7defaultContinuousSheet border5
TITLEBLOCK7defaultContinuousTitle block and revision table1
VIEWPORT8defaultContinuousLayout viewport frame (does not plot)2
DRAWING-AREA8defaultContinuousBoundary of the model drawing area (does not plot)2

Styles defined

The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.

KindNameSettings
Text styleISOisocp.shx, 15°, variable height
Text styleISO-2.5isocp.shx, 15°, 2.5 mm high
Text styleISO-3.5isocp.shx, 15°, 3.5 mm high
Text styleISO-5isocp.shx, 15°, 5 mm high
Text styleTB-enArial, used by the title block
Dimension styleISO-25Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals
LinetypeContinuousSolid line
LinetypeDASHEDDashed
LinetypeDASHDOTDash-dot
LinetypeCENTERCentre line
LinetypePHANTOMPhantom line
LinetypeHIDDENHidden line

Sheet and drawing setup

How the sheet is set up, so your own drawings print the same way.

Sheet
ISO A3 landscape, 420 × 297 mm.
Layout
One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
Border
20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
Model space
Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
Title block
160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
Text size
2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
Linetype scale
1, so dashes are sized for plotting at 1:1.
Plot style
None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.

Title block fields

The attributes of the title block.

AttributeField on the sheetValue in this sample
COMPANYCOMPANYCADXChange
PROJECTPROJECT110 kV Cable Tunnel
AREAAREACable tunnel
SYSTEMSYSTEMCondition monitoring
CLIENTCLIENTSample
TITLEDRAWING TITLECable tunnel monitoring and inspection robot
DRAWING_NODRAWING NO.M-503
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).

Blocks in the drawing

The equipment list of the drawing: block name, symbol and how many times it is placed.

SymbolBlockPlaced
Temperature zone markerPMN_CB_DTS_ZONE3
Cable joint temperaturePMN_CB_JOINT_TEMP2
Inspection rail segmentPMN_INS_RAIL2
Inspection point markerPMN_INS_POINT2
Water leak cablePMN_ENV_WATER_LEAK2
Distributed temp sensing unitPMN_CB_DTS_UNIT1
Protocol converterPMN_SYS_PROTOCOL_CONV1
Edge gatewayPMN_SYS_EDGE_GW1
Network switchPMN_SYS_SWITCH1
Infrared imaging gatewayPMN_INS_IR_GATEWAY1
Robot base stationPMN_INS_BASE_STATION1
Sheath current monitorPMN_CB_SHEATH_CURRENT1
Tunnel point temperaturePMN_CB_TUNNEL_TEMP1
Charging dockPMN_INS_DOCK1
Inspection robot, rail-hungPMN_INS_ROBOT_RAIL1
Temperature and humidityPMN_ENV_TEMP_HUM1
Oxygen deficiency sensorPMN_ENV_O2_DEFICIENCY1
Wireless nodePMN_SYS_WIRELESS_NODE1
Camera, pan-tilt-zoomPMN_ENV_CAM_PTZ1
Camera, thermal imagingPMN_ENV_CAM_THERMAL1
Wireless repeaterPMN_SYS_WIRELESS_REPEATER1
Water level sensorPMN_ENV_WATER_LEVEL1

Equipment schedule

One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.

TagDescriptionShown on the sheetFilled in, not shown
DTS-1Distributed temp sensing unitPMN_CB_DTS_UNITCHANNELS = 4SUPPLY_V = 230 V ACCOMMUNICATION = Modbus TCPOUTPUTS = 8MOUNTING = RackLOCATION = Cable tunnel T-01ADDRESS = 1
PC-1Protocol converterPMN_SYS_PROTOCOL_CONVFUNCTION = RS-485 to EthernetPORTS = 2SUPPLY_V = 24 V DCPROTOCOL = Modbus RTU, Modbus TCPMOUNTING = RackLOCATION = Cable tunnel T-01ADDRESS = 2
EG-1Edge gatewayPMN_SYS_EDGE_GWFUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = Cable tunnel T-01ADDRESS = 3
SW-1Network switchPMN_SYS_SWITCHFUNCTION = Ethernet switchPORTS = 8SUPPLY_V = 24 V DCPROTOCOL = IEC 61850MOUNTING = DIN railLOCATION = Cable tunnel T-01ADDRESS = 4
IRG-1Infrared imaging gatewayPMN_INS_IR_GATEWAYFUNCTION = Thermal image gatewayPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = EthernetMOUNTING = RackLOCATION = Cable tunnel T-01ADDRESS = 5
BS-1Robot base stationPMN_INS_BASE_STATIONFUNCTION = Robot base stationPORTS = 2SUPPLY_V = 230 V ACPROTOCOL = EthernetMOUNTING = FloorLOCATION = Cable tunnel T-01ADDRESS = 6
Z-1Temperature zone markerPMN_CB_DTS_ZONEZONE = Zone 1LENGTH_M = 100ALARM_C = 90CHANNEL = 1LOCATION = Cable tunnel T-01
Z-2Temperature zone markerPMN_CB_DTS_ZONEZONE = Zone 2LENGTH_M = 100ALARM_C = 90CHANNEL = 1LOCATION = Cable tunnel T-01
Z-3Temperature zone markerPMN_CB_DTS_ZONEZONE = Zone 3LENGTH_M = 100ALARM_C = 90CHANNEL = 1LOCATION = Cable tunnel T-01
JT-1Cable joint temperaturePMN_CB_JOINT_TEMPRANGE_C = 0-150ALARM_C = 90SENSOR_TYPE = Fibre opticOUTPUT = RS-485MONITORED_ITEM = Cable jointLOCATION = Cable tunnel T-01ADDRESS = 7
SC-1Sheath current monitorPMN_CB_SHEATH_CURRENTRATIO = 100:1ACCURACY = 1INNER_DIAMETER_MM = 40CIRCUIT = Cross-bonding linkTYPE = Split coreLOCATION = Cable tunnel T-01
JT-2Cable joint temperaturePMN_CB_JOINT_TEMPRANGE_C = 0-150ALARM_C = 90SENSOR_TYPE = Fibre opticOUTPUT = RS-485MONITORED_ITEM = Cable jointLOCATION = Cable tunnel T-01ADDRESS = 8
TT-1Tunnel point temperaturePMN_CB_TUNNEL_TEMPRANGE_C = -20-120ALARM_C = 60SENSOR_TYPE = PT100OUTPUT = RS-485MONITORED_ITEM = Tunnel airLOCATION = Cable tunnel T-01ADDRESS = 9
RL-1Inspection rail segmentPMN_INS_RAILMEDIUM = Aluminium rail, ceiling hungLENGTH_M = 4PROTOCOL = -FROM_TO = Tunnel inspection railLABEL = RL-01
RL-2Inspection rail segmentPMN_INS_RAILMEDIUM = Aluminium rail, ceiling hungLENGTH_M = 4PROTOCOL = -FROM_TO = Tunnel inspection railLABEL = RL-01
DK-1Charging dockPMN_INS_DOCKDRIVE = Rail-hungRUN_TIME_H = -PAYLOAD = Charging contactsPROTECTION = IP54NAVIGATION = Fixed positionLOCATION = Cable tunnel T-01ADDRESS = 10
RB-1Inspection robot, rail-hungPMN_INS_ROBOT_RAILDRIVE = Rail-hungRUN_TIME_H = 8PAYLOAD = Visible and thermal camera, gasPROTECTION = IP55NAVIGATION = Rail positionLOCATION = Cable tunnel T-01ADDRESS = 11
IP-1Inspection point markerPMN_INS_POINTTYPE = Thermal image point at joint JT-1RATING = -LOCATION = Cable tunnel T-01ADDRESS = 12
TH-1Temperature and humidityPMN_ENV_TEMP_HUMMEASURAND = Temperature and humidityRANGE = -20-80 C, 0-100 % RHALARM_1 = 45 CALARM_2 = 90 % RHOUTPUT = RS-485LOCATION = Cable tunnel T-01ADDRESS = 13
OX-1Oxygen deficiency sensorPMN_ENV_O2_DEFICIENCYGAS = OxygenRANGE = 0-25 % volALARM_1 = 19.5 %ALARM_2 = 18 %OUTPUT = RS-485LOCATION = Cable tunnel T-01ADDRESS = 14
WN-1Wireless nodePMN_SYS_WIRELESS_NODEFUNCTION = Wireless access pointPORTS = 1SUPPLY_V = PoEPROTOCOL = Wi-FiMOUNTING = WallLOCATION = Cable tunnel T-01ADDRESS = 15
IP-2Inspection point markerPMN_INS_POINTTYPE = Thermal image point at joint JT-2RATING = -LOCATION = Cable tunnel T-01ADDRESS = 16
PTZ-1Camera, pan-tilt-zoomPMN_ENV_CAM_PTZRESOLUTION = 1920 x 1080LENS = 4.7-94 mmPROTECTION = IP66STREAM = H.265POWER = PoE+LOCATION = Cable tunnel T-01ADDRESS = 17
IRC-1Camera, thermal imagingPMN_ENV_CAM_THERMALTEMP_RANGE_C = -20-150ACCURACY_C = 2RESOLUTION = 384 x 288LENS = 25 degOUTPUT = EthernetLOCATION = Cable tunnel T-01ADDRESS = 18
WR-1Wireless repeaterPMN_SYS_WIRELESS_REPEATERFUNCTION = Wireless repeaterPORTS = 1SUPPLY_V = PoEPROTOCOL = Wi-FiMOUNTING = WallLOCATION = Cable tunnel T-01ADDRESS = 19
LV-1Water level sensorPMN_ENV_WATER_LEVELMEASURAND = Sump water levelRANGE = 0-2 mALARM_1 = 0.5 mALARM_2 = 1.0 mOUTPUT = 4-20 mALOCATION = Cable tunnel T-01ADDRESS = 20
WK-1Water leak cablePMN_ENV_WATER_LEAKMEDIUM = Water leak sensing cableLENGTH_M = 100PROTOCOL = Dry contactFROM_TO = Sump to tunnel endLABEL = WLC-01
WK-2Water leak cablePMN_ENV_WATER_LEAKMEDIUM = Water leak sensing cableLENGTH_M = 100PROTOCOL = Dry contactFROM_TO = Sump to tunnel endLABEL = WLC-01

Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.

How to use it

  1. Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
  2. Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
  3. Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.

Frequently asked questions

Can I use the drawing for a real project?
As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
Why are the layers coloured?
Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
Which CAD programs open it?
The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.