ResourcesSingle-line diagram symbols
Switchboard arc flash protection and PD monitoring: sample DWG
The arc flash protection and partial discharge monitoring of an 11 kV switchboard. Four panels, an incomer, two feeders and a bus section, each have a busbar, a breaker and a cable compartment with its own zone mark and light sensor. The twelve sensor fibres are grouped into four channels on the arc flash relay. The relay trips the incomer and the bus section only when the current check from the incomer sees an overcurrent, and a mark shows the light-only mode used for tests. Below the panels one earth voltage sensor per panel feeds a partial discharge host, which reports through a gateway to SCADA. A legend, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.
Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)
This sample uses these resources
The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.
What is in the ZIP
- Switchboard-Arc-Flash-Monitoring-Sample.dwg
Sample drawing (DWG, AutoCAD 2018 format) - Process-Template-ISO-A3.dwt
Template (DWT) that the drawing was made on - CADXChange-Monochrome.ctb
Plot style table (CTB) that prints every colour black - README.txt
README with the layer list and how to use the files
The template
The process template has 14 layers with colours, line weights and linetypes (main, secondary and utility lines, electrical and pneumatic signals, equipment, boundaries, flow arrows, tags, line numbers, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.
Layers defined
Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.
| Layer | Colour | Line weight | Linetype | Used for | Objects here |
|---|---|---|---|---|---|
| Process layers | |||||
| PROC-PIPE-MAIN | 5 | 0.50 mm | Continuous | Main process lines | 3 |
| PROC-PIPE-SEC | 4 | 0.35 mm | Continuous | Secondary and branch process lines | 51 |
| PROC-PIPE-UTIL | 30 | 0.35 mm | Continuous | Utility lines (steam, condensate, cooling water, air) | not used here |
| PROC-SIGNAL | 3 | 0.18 mm | DASHED | Electrical signal lines | 14 |
| PROC-PNEU | 6 | 0.18 mm | DASHDOT | Pneumatic and capillary signal lines | not used here |
| SYMBOL | 7 | 0.25 mm | Continuous | Symbols (the layer the symbol libraries use) | 35 |
| PROC-EQUIP | 7 | 0.35 mm | Continuous | Equipment outlines drawn outside the symbol libraries | 24 |
| PROC-BOUNDARY | 1 | 0.18 mm | DASHDOT | Package, skid and battery limits | not used here |
| PROC-FLOW | 7 | 0.18 mm | Continuous | Flow arrows and flow direction marks | 1 |
| PROC-TAG | 7 | 0.18 mm | Continuous | Equipment and instrument tags | not used here |
| PROC-LINE-NO | 7 | 0.18 mm | Continuous | Line numbers and line specifications | not used here |
| PROC-TEXT | 7 | 0.18 mm | Continuous | General text | 40 |
| PROC-NOTES | 7 | 0.18 mm | Continuous | Notes and legends | 12 |
| PROC-DIM | 3 | 0.18 mm | Continuous | Dimensions | not used here |
| Sheet and symbol layers | |||||
| 0 | 7 | default | Continuous | Default layer, keep it empty | not used here |
| FRAME | 7 | default | Continuous | Sheet border | 5 |
| TITLEBLOCK | 7 | default | Continuous | Title block and revision table | 1 |
| VIEWPORT | 8 | default | Continuous | Layout viewport frame (does not plot) | 2 |
| DRAWING-AREA | 8 | default | Continuous | Boundary of the model drawing area (does not plot) | 2 |
Styles defined
The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.
| Kind | Name | Settings |
|---|---|---|
| Text style | ISO | isocp.shx, 15°, variable height |
| Text style | ISO-2.5 | isocp.shx, 15°, 2.5 mm high |
| Text style | ISO-3.5 | isocp.shx, 15°, 3.5 mm high |
| Text style | ISO-5 | isocp.shx, 15°, 5 mm high |
| Text style | TB-en | Arial, used by the title block |
| Dimension style | ISO-25 | Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals |
| Linetype | Continuous | Solid line |
| Linetype | DASHED | Dashed |
| Linetype | DASHDOT | Dash-dot |
| Linetype | CENTER | Centre line |
| Linetype | PHANTOM | Phantom line |
| Linetype | HIDDEN | Hidden line |
Sheet and drawing setup
How the sheet is set up, so your own drawings print the same way.
- Sheet
- ISO A3 landscape, 420 × 297 mm.
- Layout
- One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
- Border
- 20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
- Model space
- Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
- Title block
- 160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
- Text size
- 2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
- Linetype scale
- 1, so dashes are sized for plotting at 1:1.
- Plot style
- None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.
Title block fields
The attributes of the title block.
| Attribute | Field on the sheet | Value in this sample |
|---|---|---|
| COMPANY | COMPANY | CADXChange |
| PROJECT | PROJECT | 11 kV Switchboard S1 |
| AREA | AREA | Switch room |
| SYSTEM | SYSTEM | Condition monitoring |
| CLIENT | CLIENT | Sample |
| TITLE | DRAWING TITLE | Switchboard arc flash and PD monitoring |
| DRAWING_NO | DRAWING NO. | M-502 |
| CONTRACT_NO | CONTRACT NO. | — |
| REV | REV | A |
| DRAWN | DRAWN | — |
| CHECKED | CHECKED | — |
| APPROVED | APPROVED | — |
| DATE | DATE | 2026-11-25 |
| SCALE | SCALE | NTS |
| SHEET | SHEET | 1 |
| SHEET_OF | OF | 1 |
Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).
Blocks in the drawing
The equipment list of the drawing: block name, symbol and how many times it is placed.
| Symbol | Block | Placed |
|---|---|---|
| PMN_ARC_POINT | 12 | |
| PMN_ARC_ZONE_BUS | 4 | |
| PMN_ARC_ZONE_CB | 4 | |
| PMN_ARC_ZONE_CABLE | 4 | |
| PMN_SG_PD_TEV | 4 | |
| PMN_ARC_TRIP_OUT | 2 | |
| PMN_ARC_RELAY | 1 | |
| PMN_ARC_CT_INPUT | 1 | |
| PMN_ARC_LIGHT_ONLY | 1 | |
| PMN_SG_PD_HOST | 1 | |
| PMN_SYS_EDGE_GW | 1 |
Equipment schedule
One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.
| Tag | Description | Shown on the sheet | Filled in, not shown |
|---|---|---|---|
| BB-1 | Busbar compartment zonePMN_ARC_ZONE_BUS | ZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-1 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 1 | |
| CB-1 | Breaker compartment zonePMN_ARC_ZONE_CB | ZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-2 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 2 | |
| CC-1 | Cable compartment zonePMN_ARC_ZONE_CABLE | ZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-3 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 3 | |
| BB-2 | Busbar compartment zonePMN_ARC_ZONE_BUS | ZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-4 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 4 | |
| CB-2 | Breaker compartment zonePMN_ARC_ZONE_CB | ZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-5 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 5 | |
| CC-2 | Cable compartment zonePMN_ARC_ZONE_CABLE | ZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-6 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 6 | |
| BB-3 | Busbar compartment zonePMN_ARC_ZONE_BUS | ZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-7 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 7 | |
| CB-3 | Breaker compartment zonePMN_ARC_ZONE_CB | ZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-8 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 8 | |
| CC-3 | Cable compartment zonePMN_ARC_ZONE_CABLE | ZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-9 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 9 | |
| BB-4 | Busbar compartment zonePMN_ARC_ZONE_BUS | ZONE = Busbar compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-10 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 10 | |
| CB-4 | Breaker compartment zonePMN_ARC_ZONE_CB | ZONE = Breaker compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-11 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 11 | |
| CC-4 | Cable compartment zonePMN_ARC_ZONE_CABLE | ZONE = Cable compartmentLENGTH_M = -ALARM_C = -CHANNEL = -LOCATION = 11 kV switchboard S1 | |
| AS-12 | Arc point sensorPMN_ARC_POINT | SENSITIVITY_LUX = 8000TRIP_TIME_MS = 2COMPARTMENT = Panel compartmentOUTPUT = Fibre opticCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 12 | |
| AFR-1 | Arc flash relayPMN_ARC_RELAY | SENSITIVITY_LUX = -TRIP_TIME_MS = 7COMPARTMENT = All panelsOUTPUT = 2 trip, 1 alarmCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 13 | |
| CI-1 | Current check inputPMN_ARC_CT_INPUT | SENSITIVITY_LUX = -TRIP_TIME_MS = -COMPARTMENT = IncomerOUTPUT = Current checkCURRENT_CHECK = 2.5 x InLOCATION = 11 kV switchboard S1ADDRESS = 14 | |
| TO-1 | Trip outputPMN_ARC_TRIP_OUT | SENSITIVITY_LUX = -TRIP_TIME_MS = 3COMPARTMENT = Q1 and Q3OUTPUT = Trip coil, 110 V DCCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 15 | |
| TO-2 | Trip outputPMN_ARC_TRIP_OUT | SENSITIVITY_LUX = -TRIP_TIME_MS = 3COMPARTMENT = Q1 and Q3OUTPUT = Trip coil, 110 V DCCURRENT_CHECK = YesLOCATION = 11 kV switchboard S1ADDRESS = 16 | |
| LO-1 | Light-only mode markPMN_ARC_LIGHT_ONLY | SENSITIVITY_LUX = -TRIP_TIME_MS = -COMPARTMENT = All panelsOUTPUT = Alarm onlyCURRENT_CHECK = NoLOCATION = 11 kV switchboard S1ADDRESS = 17 | |
| PDT-1 | Partial discharge, TEVPMN_SG_PD_TEV | METHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 18 | |
| PDT-2 | Partial discharge, TEVPMN_SG_PD_TEV | METHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 19 | |
| PDT-3 | Partial discharge, TEVPMN_SG_PD_TEV | METHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 20 | |
| PDT-4 | Partial discharge, TEVPMN_SG_PD_TEV | METHOD = TEVFREQUENCY_BAND = 3-100 MHzSENSITIVITY_PC = 50CHANNELS = 1OUTPUT = CoaxialLOCATION = 11 kV switchboard S1ADDRESS = 21 | |
| PDH-1 | Partial discharge hostPMN_SG_PD_HOST | CHANNELS = 8SUPPLY_V = 24 V DCCOMMUNICATION = EthernetOUTPUTS = 2MOUNTING = WallLOCATION = 11 kV switchboard S1ADDRESS = 22 | |
| EG-1 | Edge gatewayPMN_SYS_EDGE_GW | FUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = 11 kV switchboard S1ADDRESS = 23 |
Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.
How to use it
- Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
- Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
- Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.
Frequently asked questions
- Can I use the drawing for a real project?
- As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
- Why are the layers coloured?
- Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
- Which CAD programs open it?
- The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.