ResourcesSingle-line diagram symbols
Transformer online monitoring system: sample DWG of a system diagram
The online monitoring of one power transformer, drawn as a system diagram. At field level fourteen sensors sit on the transformer: dissolved gas, moisture, partial discharge by UHF and acoustic methods, bushings, winding and top oil temperature, tap changer, cooling, oil level, gas relay, pressure relief, vibration and core earth current. Four collectors bring their signals to the monitoring IED. At station level the IED reaches a switch, a GPS time source, an edge gateway to SCADA, a server and a workstation, lights an alarm beacon, and sends a hard-wired alarm contact to the fire alarm panel. A legend, the three alarm level marks, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.
Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)
This sample uses these resources
The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.
What is in the ZIP
- Transformer-Online-Monitoring-System-Sample.dwg
Sample drawing (DWG, AutoCAD 2018 format) - Process-Template-ISO-A3.dwt
Template (DWT) that the drawing was made on - CADXChange-Monochrome.ctb
Plot style table (CTB) that prints every colour black - README.txt
README with the layer list and how to use the files
The template
The process template has 14 layers with colours, line weights and linetypes (main, secondary and utility lines, electrical and pneumatic signals, equipment, boundaries, flow arrows, tags, line numbers, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.
Layers defined
Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.
| Layer | Colour | Line weight | Linetype | Used for | Objects here |
|---|---|---|---|---|---|
| Process layers | |||||
| PROC-PIPE-MAIN | 5 | 0.50 mm | Continuous | Main process lines | 9 |
| PROC-PIPE-SEC | 4 | 0.35 mm | Continuous | Secondary and branch process lines | not used here |
| PROC-PIPE-UTIL | 30 | 0.35 mm | Continuous | Utility lines (steam, condensate, cooling water, air) | not used here |
| PROC-SIGNAL | 3 | 0.18 mm | DASHED | Electrical signal lines | 30 |
| PROC-PNEU | 6 | 0.18 mm | DASHDOT | Pneumatic and capillary signal lines | not used here |
| SYMBOL | 7 | 0.25 mm | Continuous | Symbols (the layer the symbol libraries use) | 26 |
| PROC-EQUIP | 7 | 0.35 mm | Continuous | Equipment outlines drawn outside the symbol libraries | not used here |
| PROC-BOUNDARY | 1 | 0.18 mm | DASHDOT | Package, skid and battery limits | 2 |
| PROC-FLOW | 7 | 0.18 mm | Continuous | Flow arrows and flow direction marks | 1 |
| PROC-TAG | 7 | 0.18 mm | Continuous | Equipment and instrument tags | not used here |
| PROC-LINE-NO | 7 | 0.18 mm | Continuous | Line numbers and line specifications | not used here |
| PROC-TEXT | 7 | 0.18 mm | Continuous | General text | 33 |
| PROC-NOTES | 7 | 0.18 mm | Continuous | Notes and legends | 13 |
| PROC-DIM | 3 | 0.18 mm | Continuous | Dimensions | not used here |
| Sheet and symbol layers | |||||
| 0 | 7 | default | Continuous | Default layer, keep it empty | not used here |
| FRAME | 7 | default | Continuous | Sheet border | 5 |
| TITLEBLOCK | 7 | default | Continuous | Title block and revision table | 1 |
| VIEWPORT | 8 | default | Continuous | Layout viewport frame (does not plot) | 2 |
| DRAWING-AREA | 8 | default | Continuous | Boundary of the model drawing area (does not plot) | 2 |
Styles defined
The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.
| Kind | Name | Settings |
|---|---|---|
| Text style | ISO | isocp.shx, 15°, variable height |
| Text style | ISO-2.5 | isocp.shx, 15°, 2.5 mm high |
| Text style | ISO-3.5 | isocp.shx, 15°, 3.5 mm high |
| Text style | ISO-5 | isocp.shx, 15°, 5 mm high |
| Text style | TB-en | Arial, used by the title block |
| Dimension style | ISO-25 | Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals |
| Linetype | Continuous | Solid line |
| Linetype | DASHED | Dashed |
| Linetype | DASHDOT | Dash-dot |
| Linetype | CENTER | Centre line |
| Linetype | PHANTOM | Phantom line |
| Linetype | HIDDEN | Hidden line |
Sheet and drawing setup
How the sheet is set up, so your own drawings print the same way.
- Sheet
- ISO A3 landscape, 420 × 297 mm.
- Layout
- One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
- Border
- 20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
- Model space
- Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
- Title block
- 160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
- Text size
- 2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
- Linetype scale
- 1, so dashes are sized for plotting at 1:1.
- Plot style
- None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.
Title block fields
The attributes of the title block.
| Attribute | Field on the sheet | Value in this sample |
|---|---|---|
| COMPANY | COMPANY | CADXChange |
| PROJECT | PROJECT | 220 kV Substation |
| AREA | AREA | Transformer area |
| SYSTEM | SYSTEM | Condition monitoring |
| CLIENT | CLIENT | Sample |
| TITLE | DRAWING TITLE | Transformer online monitoring system |
| DRAWING_NO | DRAWING NO. | M-501 |
| CONTRACT_NO | CONTRACT NO. | — |
| REV | REV | A |
| DRAWN | DRAWN | — |
| CHECKED | CHECKED | — |
| APPROVED | APPROVED | — |
| DATE | DATE | 2026-11-25 |
| SCALE | SCALE | NTS |
| SHEET | SHEET | 1 |
| SHEET_OF | OF | 1 |
Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).
Blocks in the drawing
The equipment list of the drawing: block name, symbol and how many times it is placed.
| Symbol | Block | Placed |
|---|---|---|
| PMN_TR_MONITORED | 1 | |
| PMN_TR_DGA_MULTI | 1 | |
| PMN_TR_MOISTURE | 1 | |
| PMN_TR_PD_UHF | 1 | |
| PMN_TR_PD_AE | 1 | |
| PMN_TR_BUSHING | 1 | |
| PMN_TR_WINDING_FO | 1 | |
| PMN_TR_TOP_OIL_TEMP | 1 | |
| PMN_TR_COOLING | 1 | |
| PMN_TR_OLTC | 1 | |
| PMN_TR_OIL_LEVEL | 1 | |
| PMN_TR_BUCHHOLZ | 1 | |
| PMN_TR_PRV_MON | 1 | |
| PMN_TR_VIBRATION | 1 | |
| PMN_TR_CORE_GND | 1 | |
| PMN_TR_IED | 1 | |
| PMN_SYS_BEACON | 1 | |
| PMN_SYS_SWITCH | 1 | |
| PMN_SYS_TIME_SYNC | 1 | |
| PMN_SYS_EDGE_GW | 1 | |
| PMN_SYS_WORKSTATION | 1 | |
| PMN_SYS_SERVER | 1 | |
| PFP_FACP | 1 | |
| PMN_LEVEL_WARNING | 1 | |
| PMN_LEVEL_ALARM | 1 | |
| PMN_LEVEL_TRIP | 1 |
Equipment schedule
One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.
| Tag | Description | Shown on the sheet | Filled in, not shown |
|---|---|---|---|
| T1 | Transformer, monitoredPMN_TR_MONITORED | TYPE = Power transformerRATING = 180 MVA, 220/110 kVLOCATION = Transformer T1 areaADDRESS = - | |
| DGA-1 | Oil gas monitor, multi-gasPMN_TR_DGA_MULTI | GAS = H2, CO, CH4, C2H2, C2H4, C2H6RANGE = H2 5-2000 ppmALARM_1 = H2 100 ppmALARM_2 = C2H2 5 ppmOUTPUT = IEC 61850, 4-20 mALOCATION = Transformer T1 areaADDRESS = 1 | |
| MST-1 | Oil moisture sensorPMN_TR_MOISTURE | MEASURAND = Moisture in oilRANGE = 0-100 % RSALARM_1 = 20 % RSALARM_2 = 30 % RSOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 2 | |
| PDU-1 | Partial discharge, UHFPMN_TR_PD_UHF | METHOD = UHFFREQUENCY_BAND = 300-1500 MHzSENSITIVITY_PC = 5CHANNELS = 2OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 3 | |
| PDA-1 | Partial discharge, acousticPMN_TR_PD_AE | METHOD = AcousticFREQUENCY_BAND = 20-300 kHzSENSITIVITY_PC = 10CHANNELS = 4OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 4 | |
| BSH-1 | Bushing monitorPMN_TR_BUSHING | MEASURAND = Capacitance and tan deltaRANGE = tan delta 0-2 %ALARM_1 = 0.7 %ALARM_2 = 1.0 %OUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 5 | |
| WT-1 | Winding temp, fibre opticPMN_TR_WINDING_FO | RANGE_C = 0-200ALARM_C = 110SENSOR_TYPE = Fibre opticOUTPUT = RS-485MONITORED_ITEM = HV winding hot spotLOCATION = Transformer T1 areaADDRESS = 6 | |
| OT-1 | Top oil temperaturePMN_TR_TOP_OIL_TEMP | RANGE_C = -20-120ALARM_C = 85SENSOR_TYPE = PT100OUTPUT = 4-20 mAMONITORED_ITEM = Top oilLOCATION = Transformer T1 areaADDRESS = 7 | |
| CL-1 | Cooler status monitorPMN_TR_COOLING | MEASURAND = Fan and pump statusRANGE = -ALARM_1 = Fan faultALARM_2 = Pump faultOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 8 | |
| OLTC-1 | Tap changer monitorPMN_TR_OLTC | MEASURAND = Motor current and positionRANGE = 0-5 AALARM_1 = 3.5 AALARM_2 = 4.5 AOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 9 | |
| OL-1 | Oil level monitorPMN_TR_OIL_LEVEL | MEASURAND = Conservator oil levelRANGE = 0-100 %ALARM_1 = 20 %ALARM_2 = 10 %OUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 10 | |
| BR-1 | Gas relay monitorPMN_TR_BUCHHOLZ | MEASURAND = Gas relay alarm and tripRANGE = -ALARM_1 = Gas collectedALARM_2 = Oil surgeOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 11 | |
| PR-1 | Pressure relief monitorPMN_TR_PRV_MON | MEASURAND = Pressure relief deviceRANGE = -ALARM_1 = -ALARM_2 = OperatedOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 12 | |
| VB-1 | Vibration sensorPMN_TR_VIBRATION | MEASURAND = Tank vibrationRANGE = 0-50 mm/sALARM_1 = 15 mm/sALARM_2 = 25 mm/sOUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 13 | |
| CG-1 | Core ground currentPMN_TR_CORE_GND | RATIO = 1000:1ACCURACY = 1INNER_DIAMETER_MM = 60CIRCUIT = Core earth strapTYPE = Split coreLOCATION = Transformer T1 area | |
| IED-1 | Transformer monitoring IEDPMN_TR_IED | CHANNELS = 24SUPPLY_V = 110 V DCCOMMUNICATION = IEC 61850OUTPUTS = 4MOUNTING = Marshalling kioskLOCATION = Transformer T1 areaADDRESS = 14 | |
| AB-1 | Alarm beacon columnPMN_SYS_BEACON | FUNCTION = Local alarm beaconPORTS = 1SUPPLY_V = 24 V DCPROTOCOL = Dry contactMOUNTING = PoleLOCATION = Transformer T1 areaADDRESS = 15 | |
| SW-1 | Network switchPMN_SYS_SWITCH | FUNCTION = Ethernet switchPORTS = 8SUPPLY_V = 24 V DCPROTOCOL = IEC 61850MOUNTING = DIN railLOCATION = Transformer T1 areaADDRESS = 16 | |
| TS-1 | Time synchronisationPMN_SYS_TIME_SYNC | FUNCTION = GPS time sourcePORTS = 2SUPPLY_V = 24 V DCPROTOCOL = PTP, IRIG-BMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 17 | |
| EG-1 | Edge gatewayPMN_SYS_EDGE_GW | FUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 18 | |
| WS-1 | Monitoring workstationPMN_SYS_WORKSTATION | FUNCTION = Operator workstationPORTS = 2SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = DeskLOCATION = Transformer T1 areaADDRESS = 19 | |
| SV-1 | ServerPMN_SYS_SERVER | FUNCTION = Monitoring serverPORTS = 4SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 20 | |
| FACP-1 | Fire alarm control panelPFP_FACP | ZONES = 8LOOPS = 2SUPPLY_V = 230 V AC, 24 V DCBATTERY_AH = 24COMMUNICATION = Serial link to gatewayLOCATION = Fire control roomADDRESS_RANGE = 1-250 | |
| LV-1 | Level mark, warningPMN_LEVEL_WARNING | TYPE = WarningRATING = Level 1LOCATION = Transformer T1 areaADDRESS = 21 | |
| LV-2 | Level mark, alarmPMN_LEVEL_ALARM | TYPE = AlarmRATING = Level 2LOCATION = Transformer T1 areaADDRESS = 22 | |
| LV-3 | Level mark, tripPMN_LEVEL_TRIP | TYPE = TripRATING = Level 3LOCATION = Transformer T1 areaADDRESS = 23 |
Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.
How to use it
- Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
- Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
- Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.
Frequently asked questions
- Can I use the drawing for a real project?
- As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
- Why are the layers coloured?
- Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
- Which CAD programs open it?
- The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.