CADXChange

ResourcesSingle-line diagram symbols

Transformer online monitoring system: sample DWG of a system diagram

The online monitoring of one power transformer, drawn as a system diagram. At field level fourteen sensors sit on the transformer: dissolved gas, moisture, partial discharge by UHF and acoustic methods, bushings, winding and top oil temperature, tap changer, cooling, oil level, gas relay, pressure relief, vibration and core earth current. Four collectors bring their signals to the monitoring IED. At station level the IED reaches a switch, a GPS time source, an edge gateway to SCADA, a server and a workstation, lights an alarm beacon, and sends a hard-wired alarm contact to the fire alarm panel. A legend, the three alarm level marks, system data and notes complete the sheet with a filled-in title block, on the same template as our process drawings.

Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)

This sample uses these resources

The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.

What is in the ZIP

  • Transformer-Online-Monitoring-System-Sample.dwg
    Sample drawing (DWG, AutoCAD 2018 format)
  • Process-Template-ISO-A3.dwt
    Template (DWT) that the drawing was made on
  • CADXChange-Monochrome.ctb
    Plot style table (CTB) that prints every colour black
  • README.txt
    README with the layer list and how to use the files

The template

The process template has 14 layers with colours, line weights and linetypes (main, secondary and utility lines, electrical and pneumatic signals, equipment, boundaries, flow arrows, tags, line numbers, text and more), the text styles ISO-2.5 to ISO-5, the dimension style ISO-25 and an ISO A3 layout with a title block and revision table. The layer names are a common convention, not a standard; rename them to match your company's rules.

Layers defined

Every layer in the template with its colour, line weight and linetype, and how many objects of this sample are on it. Layers the sample does not use are still defined, ready for your own drawing.

LayerColourLine weightLinetypeUsed forObjects here
Process layers
PROC-PIPE-MAIN50.50 mmContinuousMain process lines9
PROC-PIPE-SEC40.35 mmContinuousSecondary and branch process linesnot used here
PROC-PIPE-UTIL300.35 mmContinuousUtility lines (steam, condensate, cooling water, air)not used here
PROC-SIGNAL30.18 mmDASHEDElectrical signal lines30
PROC-PNEU60.18 mmDASHDOTPneumatic and capillary signal linesnot used here
SYMBOL70.25 mmContinuousSymbols (the layer the symbol libraries use)26
PROC-EQUIP70.35 mmContinuousEquipment outlines drawn outside the symbol librariesnot used here
PROC-BOUNDARY10.18 mmDASHDOTPackage, skid and battery limits2
PROC-FLOW70.18 mmContinuousFlow arrows and flow direction marks1
PROC-TAG70.18 mmContinuousEquipment and instrument tagsnot used here
PROC-LINE-NO70.18 mmContinuousLine numbers and line specificationsnot used here
PROC-TEXT70.18 mmContinuousGeneral text33
PROC-NOTES70.18 mmContinuousNotes and legends13
PROC-DIM30.18 mmContinuousDimensionsnot used here
Sheet and symbol layers
07defaultContinuousDefault layer, keep it emptynot used here
FRAME7defaultContinuousSheet border5
TITLEBLOCK7defaultContinuousTitle block and revision table1
VIEWPORT8defaultContinuousLayout viewport frame (does not plot)2
DRAWING-AREA8defaultContinuousBoundary of the model drawing area (does not plot)2

Styles defined

The text styles, the dimension style and the linetypes that the template defines, so you do not have to set them up in each new drawing.

KindNameSettings
Text styleISOisocp.shx, 15°, variable height
Text styleISO-2.5isocp.shx, 15°, 2.5 mm high
Text styleISO-3.5isocp.shx, 15°, 3.5 mm high
Text styleISO-5isocp.shx, 15°, 5 mm high
Text styleTB-enArial, used by the title block
Dimension styleISO-25Text 2.5 mm, arrows 2.5 mm, extension lines 1.25 mm beyond the dimension line and 0.625 mm from the object, dimension lines 3.75 mm apart, 0 decimals
LinetypeContinuousSolid line
LinetypeDASHEDDashed
LinetypeDASHDOTDash-dot
LinetypeCENTERCentre line
LinetypePHANTOMPhantom line
LinetypeHIDDENHidden line

Sheet and drawing setup

How the sheet is set up, so your own drawings print the same way.

Sheet
ISO A3 landscape, 420 × 297 mm.
Layout
One layout named ISO-A3, plotted at 1:1 on full-bleed A3 media, so the sheet has no printer margin.
Border
20 mm from the left edge (binding side) and 10 mm from the other edges; the drawing area inside is 390 × 277 mm.
Model space
Units are millimetres. The drawing area is shown at 1:1, so 1 mm in the drawing is 1 mm on paper.
Title block
160 × 79 mm at the lower right, with a four-line revision table above the company, project, title and approval fields.
Text size
2.5 mm for labels and notes, 3.5 mm and 5 mm for headings.
Linetype scale
1, so dashes are sized for plotting at 1:1.
Plot style
None set. Pick the CTB from the ZIP in the page setup for black-and-white plots.

Title block fields

The attributes of the title block.

AttributeField on the sheetValue in this sample
COMPANYCOMPANYCADXChange
PROJECTPROJECT220 kV Substation
AREAAREATransformer area
SYSTEMSYSTEMCondition monitoring
CLIENTCLIENTSample
TITLEDRAWING TITLETransformer online monitoring system
DRAWING_NODRAWING NO.M-501
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).

Blocks in the drawing

The equipment list of the drawing: block name, symbol and how many times it is placed.

SymbolBlockPlaced
Transformer, monitoredPMN_TR_MONITORED1
Oil gas monitor, multi-gasPMN_TR_DGA_MULTI1
Oil moisture sensorPMN_TR_MOISTURE1
Partial discharge, UHFPMN_TR_PD_UHF1
Partial discharge, acousticPMN_TR_PD_AE1
Bushing monitorPMN_TR_BUSHING1
Winding temp, fibre opticPMN_TR_WINDING_FO1
Top oil temperaturePMN_TR_TOP_OIL_TEMP1
Cooler status monitorPMN_TR_COOLING1
Tap changer monitorPMN_TR_OLTC1
Oil level monitorPMN_TR_OIL_LEVEL1
Gas relay monitorPMN_TR_BUCHHOLZ1
Pressure relief monitorPMN_TR_PRV_MON1
Vibration sensorPMN_TR_VIBRATION1
Core ground currentPMN_TR_CORE_GND1
Transformer monitoring IEDPMN_TR_IED1
Alarm beacon columnPMN_SYS_BEACON1
Network switchPMN_SYS_SWITCH1
Time synchronisationPMN_SYS_TIME_SYNC1
Edge gatewayPMN_SYS_EDGE_GW1
Monitoring workstationPMN_SYS_WORKSTATION1
ServerPMN_SYS_SERVER1
Fire alarm control panelPFP_FACP1
Level mark, warningPMN_LEVEL_WARNING1
Level mark, alarmPMN_LEVEL_ALARM1
Level mark, tripPMN_LEVEL_TRIP1

Equipment schedule

One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.

TagDescriptionShown on the sheetFilled in, not shown
T1Transformer, monitoredPMN_TR_MONITOREDTYPE = Power transformerRATING = 180 MVA, 220/110 kVLOCATION = Transformer T1 areaADDRESS = -
DGA-1Oil gas monitor, multi-gasPMN_TR_DGA_MULTIGAS = H2, CO, CH4, C2H2, C2H4, C2H6RANGE = H2 5-2000 ppmALARM_1 = H2 100 ppmALARM_2 = C2H2 5 ppmOUTPUT = IEC 61850, 4-20 mALOCATION = Transformer T1 areaADDRESS = 1
MST-1Oil moisture sensorPMN_TR_MOISTUREMEASURAND = Moisture in oilRANGE = 0-100 % RSALARM_1 = 20 % RSALARM_2 = 30 % RSOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 2
PDU-1Partial discharge, UHFPMN_TR_PD_UHFMETHOD = UHFFREQUENCY_BAND = 300-1500 MHzSENSITIVITY_PC = 5CHANNELS = 2OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 3
PDA-1Partial discharge, acousticPMN_TR_PD_AEMETHOD = AcousticFREQUENCY_BAND = 20-300 kHzSENSITIVITY_PC = 10CHANNELS = 4OUTPUT = Fibre opticLOCATION = Transformer T1 areaADDRESS = 4
BSH-1Bushing monitorPMN_TR_BUSHINGMEASURAND = Capacitance and tan deltaRANGE = tan delta 0-2 %ALARM_1 = 0.7 %ALARM_2 = 1.0 %OUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 5
WT-1Winding temp, fibre opticPMN_TR_WINDING_FORANGE_C = 0-200ALARM_C = 110SENSOR_TYPE = Fibre opticOUTPUT = RS-485MONITORED_ITEM = HV winding hot spotLOCATION = Transformer T1 areaADDRESS = 6
OT-1Top oil temperaturePMN_TR_TOP_OIL_TEMPRANGE_C = -20-120ALARM_C = 85SENSOR_TYPE = PT100OUTPUT = 4-20 mAMONITORED_ITEM = Top oilLOCATION = Transformer T1 areaADDRESS = 7
CL-1Cooler status monitorPMN_TR_COOLINGMEASURAND = Fan and pump statusRANGE = -ALARM_1 = Fan faultALARM_2 = Pump faultOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 8
OLTC-1Tap changer monitorPMN_TR_OLTCMEASURAND = Motor current and positionRANGE = 0-5 AALARM_1 = 3.5 AALARM_2 = 4.5 AOUTPUT = RS-485LOCATION = Transformer T1 areaADDRESS = 9
OL-1Oil level monitorPMN_TR_OIL_LEVELMEASURAND = Conservator oil levelRANGE = 0-100 %ALARM_1 = 20 %ALARM_2 = 10 %OUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 10
BR-1Gas relay monitorPMN_TR_BUCHHOLZMEASURAND = Gas relay alarm and tripRANGE = -ALARM_1 = Gas collectedALARM_2 = Oil surgeOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 11
PR-1Pressure relief monitorPMN_TR_PRV_MONMEASURAND = Pressure relief deviceRANGE = -ALARM_1 = -ALARM_2 = OperatedOUTPUT = Dry contactLOCATION = Transformer T1 areaADDRESS = 12
VB-1Vibration sensorPMN_TR_VIBRATIONMEASURAND = Tank vibrationRANGE = 0-50 mm/sALARM_1 = 15 mm/sALARM_2 = 25 mm/sOUTPUT = 4-20 mALOCATION = Transformer T1 areaADDRESS = 13
CG-1Core ground currentPMN_TR_CORE_GNDRATIO = 1000:1ACCURACY = 1INNER_DIAMETER_MM = 60CIRCUIT = Core earth strapTYPE = Split coreLOCATION = Transformer T1 area
IED-1Transformer monitoring IEDPMN_TR_IEDCHANNELS = 24SUPPLY_V = 110 V DCCOMMUNICATION = IEC 61850OUTPUTS = 4MOUNTING = Marshalling kioskLOCATION = Transformer T1 areaADDRESS = 14
AB-1Alarm beacon columnPMN_SYS_BEACONFUNCTION = Local alarm beaconPORTS = 1SUPPLY_V = 24 V DCPROTOCOL = Dry contactMOUNTING = PoleLOCATION = Transformer T1 areaADDRESS = 15
SW-1Network switchPMN_SYS_SWITCHFUNCTION = Ethernet switchPORTS = 8SUPPLY_V = 24 V DCPROTOCOL = IEC 61850MOUNTING = DIN railLOCATION = Transformer T1 areaADDRESS = 16
TS-1Time synchronisationPMN_SYS_TIME_SYNCFUNCTION = GPS time sourcePORTS = 2SUPPLY_V = 24 V DCPROTOCOL = PTP, IRIG-BMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 17
EG-1Edge gatewayPMN_SYS_EDGE_GWFUNCTION = Gateway to SCADAPORTS = 4SUPPLY_V = 24 V DCPROTOCOL = IEC 60870-5-104MOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 18
WS-1Monitoring workstationPMN_SYS_WORKSTATIONFUNCTION = Operator workstationPORTS = 2SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = DeskLOCATION = Transformer T1 areaADDRESS = 19
SV-1ServerPMN_SYS_SERVERFUNCTION = Monitoring serverPORTS = 4SUPPLY_V = 230 V ACPROTOCOL = OPC UAMOUNTING = RackLOCATION = Transformer T1 areaADDRESS = 20
FACP-1Fire alarm control panelPFP_FACPZONES = 8LOOPS = 2SUPPLY_V = 230 V AC, 24 V DCBATTERY_AH = 24COMMUNICATION = Serial link to gatewayLOCATION = Fire control roomADDRESS_RANGE = 1-250
LV-1Level mark, warningPMN_LEVEL_WARNINGTYPE = WarningRATING = Level 1LOCATION = Transformer T1 areaADDRESS = 21
LV-2Level mark, alarmPMN_LEVEL_ALARMTYPE = AlarmRATING = Level 2LOCATION = Transformer T1 areaADDRESS = 22
LV-3Level mark, tripPMN_LEVEL_TRIPTYPE = TripRATING = Level 3LOCATION = Transformer T1 areaADDRESS = 23

Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.

How to use it

  1. Open the sample drawing to see how layers, text and the title block are used, or open it in the browser first, nothing to install.
  2. Start your own drawing from the template (NEW, then pick the DWT file). Copy the CTB file to your plot styles folder if you want black-and-white plots.
  3. Insert blocks from the symbol library into your drawing. The blocks in the sample are copies; they do not change when a library changes.

Frequently asked questions

Can I use the drawing for a real project?
As a starting point for layout and layers, yes. The ratings, settings and cable sizes are made up, so the diagram has to be checked and changed for your project before it is used for design or construction.
Why are the layers coloured?
Colours and line weights follow the layers: power circuits are red and heavy, control is cyan, signal is green. The plot style table in the ZIP prints everything black and keeps the line weights, so you can plot in black and white as well.
Which CAD programs open it?
The drawing and the template are in AutoCAD 2018 format, which AutoCAD 2018 and later open, and so do other CAD programs that read this format. The browser viewer needs nothing installed.