CADXChange

ResourcesPower system secondary equipment symbols110 kV line bay secondary circuits

Trip and close circuits

Close circuit with anti-pumping, two independent trip circuits, a trip circuit supervision relay and position lamps on a 220 V DC supply.

Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)

Version 1.0 · updated November 25, 2026

This sample uses these resources

The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.

Layers, styles and sheet setup are the same for every drawing in the series; they are described on the series page: 110 kV line bay secondary circuits

Title block fields

The attributes of the title block.

AttributeField on the sheetValue in this sample
COMPANYCOMPANYCADXChange
PROJECTPROJECT110 kV Substation
AREAAREA110 kV line bay
SYSTEMSYSTEM220 V DC
CLIENTCLIENTSample
TITLEDRAWING TITLELine bay, trip and close circuits
DRAWING_NODRAWING NO.E-501
CONTRACT_NOCONTRACT NO.—
REVREVA
DRAWNDRAWN—
CHECKEDCHECKED—
APPROVEDAPPROVED—
DATEDATE2026-11-25
SCALESCALENTS
SHEETSHEET1
SHEET_OFOF1

Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).

Blocks in the drawing

The equipment list of the drawing: block name, symbol and how many times it is placed.

SymbolBlockPlaced
JunctionSEC_IEC_JUNCTION18
Push-button, NOSEC_IEC_PUSHBUTTON_NO3
Make contact (NO)SEC_IEC_CONTACT_NO3
Breaker aux contact, makeSEC_TC_AUX_NO3
Breaker aux contact, breakSEC_TC_AUX_NC2
Trip coilSEC_R_TRIP2
Signal lampSEC_IEC_LAMP2
Anti-pumping relaySEC_TC_ANTIPUMP1
Limit switch, NOSEC_IEC_LIMIT_NO1
Closing coilSEC_R_CLOSE1
Trip circuit supervisionSEC_TC_TCS1

Equipment schedule

One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.

TagDescriptionShown on the sheetFilled in, not shown
SB1Push-button, NOSEC_IEC_PUSHBUTTON_NOLEGEND = CLOSECONTACT_NO = 1 NOCOLOR = Black
F1Make contact (NO)SEC_IEC_CONTACT_NOCONTACT_NO = 79 CLOSERATING_A = 5
K1Anti-pumping relaySEC_TC_ANTIPUMPSETTING = 220 V DC
QF1Breaker aux contact, breakSEC_TC_AUX_NCFUNCTION = 52bSETTING = 10 A, 220 V DC
SQ1Limit switch, NOSEC_IEC_LIMIT_NOCONTACT_NO = SPRINGRATING_A = 6ACTUATOR = Closing spring camVOLTAGE = 220 V DC
YC1Closing coilSEC_R_CLOSESETTING = 220 V DC, 2.0 A
F1Make contact (NO)SEC_IEC_CONTACT_NOCONTACT_NO = TRIPRATING_A = 5
SB2Push-button, NOSEC_IEC_PUSHBUTTON_NOLEGEND = TRIPCONTACT_NO = 1 NOCOLOR = Black
QF1Breaker aux contact, makeSEC_TC_AUX_NOFUNCTION = 52aSETTING = 10 A, 220 V DC
YT1Trip coilSEC_R_TRIPSETTING = 220 V DC, 1.5 A
K2Trip circuit supervisionSEC_TC_TCSSETTING = 220 V DC, alarm after 3 s
F2Make contact (NO)SEC_IEC_CONTACT_NOCONTACT_NO = TRIPRATING_A = 5
SB3Push-button, NOSEC_IEC_PUSHBUTTON_NOLEGEND = TRIPCONTACT_NO = 1 NOCOLOR = Black
QF1Breaker aux contact, makeSEC_TC_AUX_NOFUNCTION = 52aSETTING = 10 A, 220 V DC
YT2Trip coilSEC_R_TRIPSETTING = 220 V DC, 1.5 A
QF1Breaker aux contact, makeSEC_TC_AUX_NOFUNCTION = 52aSETTING = 10 A, 220 V DC
HL1Signal lampSEC_IEC_LAMPCOLOR = REDVOLTAGE = 220 V DCPOWER = 2 W
QF1Breaker aux contact, breakSEC_TC_AUX_NCFUNCTION = 52bSETTING = 10 A, 220 V DC
HL2Signal lampSEC_IEC_LAMPCOLOR = GREENVOLTAGE = 220 V DCPOWER = 2 W

Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.

More drawings in this series