Trip and close circuits
Close circuit with anti-pumping, two independent trip circuits, a trip circuit supervision relay and position lamps on a 220 V DC supply.
Free to use and modify in your own projects, including commercial ones. The ZIP holds the sample drawing, a template, a plot style table and a README; no add-in needed. The data in the drawing is made up, so it is not for design or construction. Provided as is, without warranty. Library terms (CXL-1.0)
Version 1.0 · updated November 25, 2026
This sample uses these resources
The symbols are blocks from our own libraries, with their attributes filled in. The sheet and its title block come from our ISO A3 title block template. Download them to draw your own diagrams.
Layers, styles and sheet setup are the same for every drawing in the series; they are described on the series page: 110 kV line bay secondary circuits
Title block fields
The attributes of the title block.
| Attribute | Field on the sheet | Value in this sample |
|---|---|---|
| COMPANY | COMPANY | CADXChange |
| PROJECT | PROJECT | 110 kV Substation |
| AREA | AREA | 110 kV line bay |
| SYSTEM | SYSTEM | 220 V DC |
| CLIENT | CLIENT | Sample |
| TITLE | DRAWING TITLE | Line bay, trip and close circuits |
| DRAWING_NO | DRAWING NO. | E-501 |
| CONTRACT_NO | CONTRACT NO. | — |
| REV | REV | A |
| DRAWN | DRAWN | — |
| CHECKED | CHECKED | — |
| APPROVED | APPROVED | — |
| DATE | DATE | 2026-11-25 |
| SCALE | SCALE | NTS |
| SHEET | SHEET | 1 |
| SHEET_OF | OF | 1 |
Revision table: R1 to R4, each with REV, DATE, DESCRIPTION and BY (16 attributes, empty in this sample).
Blocks in the drawing
The equipment list of the drawing: block name, symbol and how many times it is placed.
| Symbol | Block | Placed |
|---|---|---|
| SEC_IEC_JUNCTION | 18 | |
| SEC_IEC_PUSHBUTTON_NO | 3 | |
| SEC_IEC_CONTACT_NO | 3 | |
| SEC_TC_AUX_NO | 3 | |
| SEC_TC_AUX_NC | 2 | |
| SEC_R_TRIP | 2 | |
| SEC_IEC_LAMP | 2 | |
| SEC_TC_ANTIPUMP | 1 | |
| SEC_IEC_LIMIT_NO | 1 | |
| SEC_R_CLOSE | 1 | |
| SEC_TC_TCS | 1 |
Equipment schedule
One row per placed symbol, read from the attributes of the blocks in the drawing: what is shown on the sheet, and the schedule attributes that were filled in but are not shown.
| Tag | Description | Shown on the sheet | Filled in, not shown |
|---|---|---|---|
| SB1 | Push-button, NOSEC_IEC_PUSHBUTTON_NO | LEGEND = CLOSE | CONTACT_NO = 1 NOCOLOR = Black |
| F1 | Make contact (NO)SEC_IEC_CONTACT_NO | CONTACT_NO = 79 CLOSE | RATING_A = 5 |
| K1 | Anti-pumping relaySEC_TC_ANTIPUMP | SETTING = 220 V DC | |
| QF1 | Breaker aux contact, breakSEC_TC_AUX_NC | FUNCTION = 52b | SETTING = 10 A, 220 V DC |
| SQ1 | Limit switch, NOSEC_IEC_LIMIT_NO | CONTACT_NO = SPRING | RATING_A = 6ACTUATOR = Closing spring camVOLTAGE = 220 V DC |
| YC1 | Closing coilSEC_R_CLOSE | SETTING = 220 V DC, 2.0 A | |
| F1 | Make contact (NO)SEC_IEC_CONTACT_NO | CONTACT_NO = TRIP | RATING_A = 5 |
| SB2 | Push-button, NOSEC_IEC_PUSHBUTTON_NO | LEGEND = TRIP | CONTACT_NO = 1 NOCOLOR = Black |
| QF1 | Breaker aux contact, makeSEC_TC_AUX_NO | FUNCTION = 52a | SETTING = 10 A, 220 V DC |
| YT1 | Trip coilSEC_R_TRIP | SETTING = 220 V DC, 1.5 A | |
| K2 | Trip circuit supervisionSEC_TC_TCS | SETTING = 220 V DC, alarm after 3 s | |
| F2 | Make contact (NO)SEC_IEC_CONTACT_NO | CONTACT_NO = TRIP | RATING_A = 5 |
| SB3 | Push-button, NOSEC_IEC_PUSHBUTTON_NO | LEGEND = TRIP | CONTACT_NO = 1 NOCOLOR = Black |
| QF1 | Breaker aux contact, makeSEC_TC_AUX_NO | FUNCTION = 52a | SETTING = 10 A, 220 V DC |
| YT2 | Trip coilSEC_R_TRIP | SETTING = 220 V DC, 1.5 A | |
| QF1 | Breaker aux contact, makeSEC_TC_AUX_NO | FUNCTION = 52a | SETTING = 10 A, 220 V DC |
| HL1 | Signal lampSEC_IEC_LAMP | COLOR = RED | VOLTAGE = 220 V DCPOWER = 2 W |
| QF1 | Breaker aux contact, breakSEC_TC_AUX_NC | FUNCTION = 52b | SETTING = 10 A, 220 V DC |
| HL2 | Signal lampSEC_IEC_LAMP | COLOR = GREEN | VOLTAGE = 220 V DCPOWER = 2 W |
Manufacturer, model and remarks are left empty on every block, ready for your data. The values are examples.