Heat exchanger (LMTD) calculator

Size the heat transfer area of an exchanger from the temperatures, the duty and the overall coefficient, and see its effectiveness.

Result

Heat transfer area
12.50 m²
Log mean temperature difference
40.00 K
Effectiveness ε
0.429
NTU
0.75
UA
12.50 kW/K
Hot side flow
3.982 kg/s
Cold side flow
3.982 kg/s

The area is for ideal counter or parallel flow. For shell-and-tube with several passes, multiply by the correction factor F from the manufacturer or TEMA charts, and add a fouling margin.

Working

  1. ΔT\Delta T(1)ΔT1=40.00 K,ΔT2=40.00 K\Delta T_{1} = 40{.}00\,\mathrm{K},\quad \Delta T_{2} = 40{.}00\,\mathrm{K}
  2. LMTD\mathrm{LMTD}(2)LMTD=ΔT1−ΔT2ln⁡(ΔT1ΔT2)=40.00−40.00ln⁡(40.0040.00)=40.00 K\begin{aligned}\mathrm{LMTD} &= \frac{\Delta T_{1} - \Delta T_{2}}{\ln \left(\frac{\Delta T_{1}}{\Delta T_{2}}\right)} \\ &= \frac{40{.}00 - 40{.}00}{\ln \left(\frac{40{.}00}{40{.}00}\right)} \\ &= 40{.}00\,\mathrm{K}\end{aligned}
  3. AA(3)A=QU×LMTD=500 0001000×40.00=12.50 m2\begin{aligned}A &= \frac{Q}{U \times \mathrm{LMTD}} \\ &= \frac{500\,000}{1000 \times 40{.}00} \\ &= 12{.}50\,\mathrm{m^{2}}\end{aligned}
  4. ε\varepsilon (4)ε=QCmin(Th,in−Tc,in)=0.429,NTU=UACmin=0.75\varepsilon = \frac{Q}{C_{\mathrm{min}}\left(T_{\mathrm{h,in}} - T_{\mathrm{c,in}}\right)} = 0{.}429,\quad \mathrm{NTU} = \frac{UA}{C_{\mathrm{min}}} = 0{.}75

Based on: LMTD method; ε-NTU method

How it is calculated

ΔT₁ and ΔT₂ are the temperature differences at the two ends: for counter-flow T_h,in − T_c,out and T_h,out − T_c,in. LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂).

Area A = Q / (U × LMTD). The capacity rates are C = Q/ΔT for each side, C_min is the smaller, effectiveness ε = Q / (C_min (T_h,in − T_c,in)) and NTU = UA / C_min.

With the specific heats you also get the flow rates on each side. For multi-pass shell and tube, correct the LMTD with the factor F and add a fouling allowance.

Questions

What is LMTD?
The log mean temperature difference: the average driving temperature difference over the exchanger, weighted for how it changes along the length.
Why is counter-flow better?
It allows the cold fluid to leave warmer than the hot fluid's outlet and gives a bigger LMTD for the same temperatures, so less area.
What U value should I use?
It depends on the fluids and the construction; the hint lists typical ranges. Use the manufacturer's value for the final design, with a fouling allowance.
What does a temperature cross mean?
The cold outlet would be hotter than the hot outlet in parallel flow, or the ends would have a zero or negative driving difference. The duty cannot be met in that arrangement.