Transformer size calculator

Pick the standard transformer rating for your load, and see the rated currents and the short-circuit current at the low-voltage terminals.

Standard

Result

Transformer rating
1,250 kVA
Loading today
56.9 %
Short-circuit current at secondary terminals
36.08 kA
Required rating
1,066.7 kVA
Maximum demand
711.1 kVA
Loading with future load
68.3 %
Primary rated current
72.17 A
Secondary rated current
1,804.2 A
Impedance used
5.00 %

No impedance given: the IEC 60076-5 minimum is used. Check the nameplate value.

Working

  1. Apparent power(1)S=Pcos⁡φ=8000.90=888.9 kVA\begin{aligned}S &= \frac{P}{\cos \varphi } \\ &= \frac{800}{0{.}90} \\ &= 888{.}9\,\mathrm{kVA}\end{aligned}
  2. Maximum demand(2)Sd=S×Kd=888.9×0.80=711.1 kVA\begin{aligned}S_{\mathrm{d}} &= S \times K_{\mathrm{d}} \\ &= 888{.}9 \times 0{.}80 \\ &= 711{.}1\,\mathrm{kVA}\end{aligned}
  3. With future load(3)Sg=Sd×(1+20 %)=853.3 kVA\begin{aligned}S_{\mathrm{g}} &= S_{\mathrm{d}} \times \left(1 + 20\,\%\right) \\ &= 853{.}3\,\mathrm{kVA}\end{aligned}
  4. Required rating(4)Sreq=Sg80 %=1066.7 kVA\begin{aligned}S_{\mathrm{req}} &= \frac{S_{\mathrm{g}}}{80\,\%} \\ &= 1066{.}7\,\mathrm{kVA}\end{aligned}
  5. Next standard rating(5)Sr=1250 kVA≥1066.7 kVAS_{\mathrm{r}} = 1250\,\mathrm{kVA} \ge 1066{.}7\,\mathrm{kVA}
  6. Primary current(6)I1=Sr3×U1=1 250 0003×10 000=72.17 A\begin{aligned}I_{1} &= \frac{S_{\mathrm{r}}}{\sqrt{3} \times U_{1}} \\ &= \frac{1\,250\,000}{\sqrt{3} \times 10\,000} \\ &= 72{.}17\,\mathrm{A}\end{aligned}
  7. Secondary current(7)I2=Sr3×U2=1 250 0003×400=1804.2 A\begin{aligned}I_{2} &= \frac{S_{\mathrm{r}}}{\sqrt{3} \times U_{2}} \\ &= \frac{1\,250\,000}{\sqrt{3} \times 400} \\ &= 1804{.}2\,\mathrm{A}\end{aligned}
  8. Transformer impedance(8)ZT=uk×U22Sr=5.00 %×40021 250 000=6.400 mΩ\begin{aligned}Z_{\mathrm{T}} &= \frac{u_{\mathrm{k}} \times U_{2}^{2}}{S_{\mathrm{r}}} \\ &= \frac{5{.}00\,\% \times 400^{2}}{1\,250\,000} \\ &= 6{.}400\,\mathrm{m\Omega }\end{aligned}
  9. Three-phase short-circuit current(9)Ik=U23×(ZT)=36.08 kA\begin{aligned}I_{\mathrm{k}} &= \frac{U_{2}}{\sqrt{3} \times \left(Z_{\mathrm{T}}\right)} \\ &= 36{.}08\,\mathrm{kA}\end{aligned}

Based on: IEC 60076-1; IEC 60076-5 Table 1; GB/T 6451

How it is calculated

Maximum demand is the connected load in kVA times the demand factor. Add the spare you want for future load, divide by the planned maximum loading, and the next standard rating up is chosen from the R10 series (IEC, GB) or the ANSI/IEEE series.

Rated current I = S / (√3 × U). The short-circuit current at the secondary terminals is I_k = U / (√3 × Z) with Z the transformer impedance u_k × U² / S, plus the upstream impedance when you give the fault level. Without a nameplate value the minimum impedance of IEC 60076-5 Table 1 is used.

Questions

How much spare capacity should a transformer have?
Many designs plan for a maximum loading of 75–85 % plus 15–25 % for future load. Your utility or client may set their own figures.
What is a demand factor?
The share of the connected load that is on at the same time. A building with many small loads rarely runs them all at once, so the factor is often 0.6–0.8.
Why does the short-circuit current matter?
The main switchboard and breakers must be rated for it. A larger transformer or a lower impedance gives a higher fault current.
Can I use it for single-phase transformers?
Yes. Choose single-phase; with the ANSI series the single-phase ratings are used.