How it is calculated
Continuity: Q = v × A with A = πD²/4. So the diameter is D = √(4Q / (πv)) and the velocity v = 4Q / (πD²).
The diameter is rounded up to the next nominal size (DN) in the list, and the velocity in that size is shown. The inside diameter of a real pipe differs a little from the nominal size, so check it against the pipe schedule.
The velocity range depends on the service (for example 1.5–3 m/s for pump discharge water, 20–40 m/s for saturated steam). These are common practice values, not a standard.
Questions
- What velocity should I use for water?
- About 0.5–1.5 m/s on pump suction and 1.5–3 m/s on discharge. Higher speeds raise pressure drop, noise and erosion; lower ones cost more in pipe.
- How do I convert m³/h to L/s?
- Divide by 3.6: 36 m³/h is 10 L/s. Both are shown in the results.
- What about steam or air?
- Choose the service and enter the actual flow at the operating pressure and temperature, not the normal flow. The density only affects the mass flow.
- Is the next DN always right?
- It gives a velocity inside the usual range for most cases. Check it against the actual inside diameter, the pressure drop and the cost.
Other calculators
- kW to amps calculator
- Voltage drop calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Lightning rod height calculator
- Power factor correction calculator
- Generator size calculator
- Lighting calculator
- Battery capacity calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator