CADXChange

Pipe flow, velocity and diameter calculator

Work out the pipe diameter for a flow and a velocity, the velocity in a given pipe, or the flow a pipe carries.

Result

Velocity
2.00 m/s
Volume flow
100.00 m³/h
Inside diameter
133.0 mm
Volume flow
27.78 L/s
Mass flow
27.728 kg/s
Flow area
138.9 cm²
Next nominal size
DN150
Velocity in that size (inside diameter taken as the nominal)
1.57 m/s
  • Velocity within the usual range for this service 1.5 m/s≤2.00 m/s≤3.0 m/s1{.}5\,\mathrm{m/s} \le 2{.}00\,\mathrm{m/s} \le 3{.}0\,\mathrm{m/s}OK

The velocity ranges are common practice, not a standard; follow your project specification and check noise, erosion and pressure drop.

Working

  1. DD(1)D=4Qπv=4×0.027778π×2.00=133.0 mm\begin{aligned}D &= \sqrt{\frac{4Q}{\pi v}} \\ &= \sqrt{\frac{4 \times 0{.}027778}{\pi \times 2{.}00}} \\ &= 133{.}0\,\mathrm{mm}\end{aligned}

Based on: Q = v · A (continuity); Velocity guidance: common practice, check the project specification

How it is calculated

Continuity: Q = v × A with A = πD²/4. So the diameter is D = √(4Q / (πv)) and the velocity v = 4Q / (πD²).

The diameter is rounded up to the next nominal size (DN) in the list, and the velocity in that size is shown. The inside diameter of a real pipe differs a little from the nominal size, so check it against the pipe schedule.

The velocity range depends on the service (for example 1.5–3 m/s for pump discharge water, 20–40 m/s for saturated steam). These are common practice values, not a standard.

Questions

What velocity should I use for water?
About 0.5–1.5 m/s on pump suction and 1.5–3 m/s on discharge. Higher speeds raise pressure drop, noise and erosion; lower ones cost more in pipe.
How do I convert m³/h to L/s?
Divide by 3.6: 36 m³/h is 10 L/s. Both are shown in the results.
What about steam or air?
Choose the service and enter the actual flow at the operating pressure and temperature, not the normal flow. The density only affects the mass flow.
Is the next DN always right?
It gives a velocity inside the usual range for most cases. Check it against the actual inside diameter, the pressure drop and the cost.

Other calculators