How it is calculated
Three-phase: ΔU = √3 × I × (R cos φ + X sin φ) × L. Single-phase and DC use 2 × I × … because the current flows out and back. L is the one-way length, n conductors in parallel divide the drop by n.
IEC and GB: resistance at service temperature R = ρ₁ / S with ρ₁ = 0.0225 Ω·mm²/m for copper and 0.036 Ω·mm²/m for aluminium, and reactance 0.08 mΩ/m, as given in Annex G of IEC 60364-5-52. NEC: DC resistance at 75 °C from Chapter 9 Table 8.
Limits: IEC 60364-5-52 Table G.52.1 gives 3 % for lighting and 5 % for other uses when supplied from the public low-voltage network. The NEC recommends 3 % for a branch circuit and 5 % in total. In China GB 50052 sets ±5 % at most equipment terminals.
Questions
- What voltage drop is acceptable?
- Commonly 3 % for lighting circuits and 5 % for other loads, measured from the origin of the installation. Check the rule that applies to your project.
- Do I enter the length one way or both ways?
- One way. The calculator already counts the return path for single-phase and DC.
- Does power factor matter?
- Yes for large cables, where reactance is a noticeable part of the impedance. For small cables the resistance dominates and the power factor makes little difference.
- How do I reduce voltage drop?
- Use a larger size, run conductors in parallel, shorten the route or raise the supply voltage. The result shows the longest run your current size allows.
Other calculators
- kW to amps calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Lightning rod height calculator
- Power factor correction calculator
- Generator size calculator
- Lighting calculator
- Battery capacity calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe flow and diameter calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator