How it is calculated
Q_c = P × (tan φ₁ − tan φ₂), where φ₁ and φ₂ are the angles before and after. Apparent power S = P / cos φ and current I = S / (√3 × U) for three phase.
Capacitance per phase: for a delta bank C = Q_c / (3ωU²), for a star bank C = Q_c / (ωU²). If the capacitors are rated for a higher voltage than the system, the nameplate kvar is the delivered kvar × (U_r/U)².
The bank is rounded up to a step of 5 kvar (25 kvar above 100). In a network with harmonics use detuned (reactor) banks.
Questions
- What power factor should I aim for?
- Utilities often charge a penalty below 0.9 to 0.95. Going above 0.98 saves little and risks overcompensation at light load.
- Why do I need a bigger bank with a higher capacitor voltage rating?
- Capacitor output falls with the square of the voltage. A 440 V unit on a 400 V system delivers about 83 % of its nameplate kvar.
- Does correction help the transformer and cable?
- Yes: less current for the same real power, so lower losses and room for more load. Correction at the load helps the whole path; at the main board it helps only the supply.
- What about harmonics?
- Capacitors can resonate with the network and be overloaded by harmonic currents. With variable-speed drives or rectifiers, use detuned banks.
Other calculators
- kW to amps calculator
- Voltage drop calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Lightning rod height calculator
- Generator size calculator
- Lighting calculator
- Battery capacity calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe flow and diameter calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator