How it is calculated
Three-phase: P = √3 × U × I × cos φ, where U is the line-to-line voltage. Single-phase: P = U × I × cos φ. DC: P = U × I.
Apparent power is S = P / cos φ and reactive power Q = S × sin φ. For a motor, the rating on the nameplate is shaft output; the supply delivers that divided by the efficiency, so enter the efficiency to get the current the cable actually carries.
Questions
- How many amps is 1 kW?
- At 230 V single-phase and power factor 1 it is about 4.3 A. At 400 V three-phase with power factor 0.85 it is about 1.7 A. The voltage, the number of phases and the power factor all change the answer.
- What is the difference between kW and kVA?
- kW is the real power that does work; kVA is what the cable and transformer have to carry. They differ by the power factor: kW = kVA × cos φ.
- Which voltage do I enter for three-phase?
- The line-to-line voltage, for example 400 V or 480 V, not the phase-to-neutral voltage.
- Why does the motor current come out higher than kW suggests?
- Because the nameplate kW is output. Losses in the motor and its power factor both add to the current taken from the supply.
Other calculators
- Voltage drop calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Lightning rod height calculator
- Power factor correction calculator
- Generator size calculator
- Lighting calculator
- Battery capacity calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe flow and diameter calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator