High-voltage short-circuit current calculator

Enter the network fault level, incoming line, main transformer, reactor and feeder to get the fault currents at three points at once, with every step shown.

Network feeder and incoming line

Main transformer

High-voltage motors on the busbar

Series reactor and outgoing feeder

Thermal rating and breaker check

Result

K1 HV busbar: fault current I″k
8.13 kA
K2 secondary busbar: fault current I″k
14.47 kA
K3 feeder end: fault current I″k
11.74 kA
K1 HV busbar: peak current i_p
17.73 kA
K1 HV busbar: thermal current I_th
8.19 kA
K1 HV busbar: fault level S″k
1,548.2 MVA
K1 HV busbar: per-unit impedance (S_b = 100 MVA)
0.0710
K2 secondary busbar: peak current i_p
36.96 kA
K2 secondary busbar: thermal current I_th
14.80 kA
K2 secondary busbar: fault level S″k
250.7 MVA
K2 secondary busbar: per-unit impedance (S_b = 100 MVA)
0.4388
K3 feeder end: peak current i_p
23.48 kA
K3 feeder end: thermal current I_th
11.81 kA
K3 feeder end: fault level S″k
203.3 MVA
K3 feeder end: per-unit impedance (S_b = 100 MVA)
0.5410
  • Fault current within the breaking current 14.47 kA≤31.5 kA14{.}47\,\mathrm{kA} \le 31{.}5\,\mathrm{kA}OK
  • Peak current within the making current 36.96 kA≤78.8 kA36{.}96\,\mathrm{kA} \le 78{.}8\,\mathrm{kA}OK

Current from generators is not included. Calculate it separately if a generator or power station is close by.

Working

  1. cc(1)c=1.10c = 1{.}10
  2. ZQZ_{\mathrm{Q}}(2)ZQ=c×Un2SkQ′′=1.10×11023000=4.4367 Ω(R=0.4415,  X=4.4146 Ω)\begin{aligned}Z_{\mathrm{Q}} &= \frac{c \times U_{\mathrm{n}}^{2}}{S''_{\mathrm{kQ}}} \\ &= \frac{1{.}10 \times 110^{2}}{3000} \\ &= 4{.}4367\,\mathrm{\Omega }\left(R = 0{.}4415,\; X = 4{.}4146\,\mathrm{\Omega }\right)\end{aligned}
  3. ZL1Z_{\mathrm{L1}}(3)RL1=r×Ln=1.3200 Ω,XL1=x×Ln=4.0000 ΩR_{\mathrm{L1}} = \frac{r \times L}{n} = 1{.}3200\,\mathrm{\Omega },\quad X_{\mathrm{L1}} = \frac{x \times L}{n} = 4{.}0000\,\mathrm{\Omega }
  4. ZK1Z_{\mathrm{K1}}(4)ZK1=R2+X2=1.76152+8.41462=8.5970 Ω\begin{aligned}Z_{\mathrm{K1}} &= \sqrt{R^{2} + X^{2}} \\ &= \sqrt{1{.}7615^{2} + 8{.}4146^{2}} \\ &= 8{.}5970\,\mathrm{\Omega }\end{aligned}
  5. Ik1′′I''_{\mathrm{k1}}(5)Ik1′′=c×Un3×ZK1=1.10×110 kV3×8.5970 Ω=8.126 kA\begin{aligned}I''_{\mathrm{k1}} &= \frac{c \times U_{\mathrm{n}}}{\sqrt{3} \times Z_{\mathrm{K1}}} \\ &= \frac{1{.}10 \times 110\,\mathrm{kV}}{\sqrt{3} \times 8{.}5970\,\mathrm{\Omega }} \\ &= 8{.}126\,\mathrm{kA}\end{aligned}
  6. κ1\kappa _{1}(6)κ1=1.02+0.98×e−3RX=1.02+0.98×e−3×0.209=1.543\begin{aligned}\kappa _{1} &= 1.02 + 0.98 \times e^{\frac{-3R}{X}} \\ &= 1.02 + 0.98 \times e^{-3 \times 0{.}209} \\ &= 1{.}543\end{aligned}
  7. ip1i_{\mathrm{p1}}(7)ip1=κ1×2×Ik1′′=1.543×1.4142×8.126=17.73 kA\begin{aligned}i_{\mathrm{p1}} &= \kappa _{1} \times \sqrt{2} \times I''_{\mathrm{k1}} \\ &= 1{.}543 \times 1.4142 \times 8{.}126 \\ &= 17{.}73\,\mathrm{kA}\end{aligned}
  8. Ith1I_{\mathrm{th1}}(8)Ith1=Ik1′′×m+n=8.126×0.0164+1=8.19 kA\begin{aligned}I_{\mathrm{th1}} &= I''_{\mathrm{k1}} \times \sqrt{m + n} \\ &= 8{.}126 \times \sqrt{0{.}0164 + 1} \\ &= 8{.}19\,\mathrm{kA}\end{aligned}
  9. ZTZ_{\mathrm{T}}(9)ZT=uk×UrT2SrT=10.50 %×10.5231.5=0.3675 Ω(RT=0.0164,  XT=0.3671 Ω)\begin{aligned}Z_{\mathrm{T}} &= \frac{u_{\mathrm{k}} \times U_{\mathrm{rT}}^{2}}{S_{\mathrm{rT}}} \\ &= \frac{10{.}50\,\% \times 10{.}5^{2}}{31{.}5} \\ &= 0{.}3675\,\mathrm{\Omega }\left(R_{\mathrm{T}} = 0{.}0164,\; X_{\mathrm{T}} = 0{.}3671\,\mathrm{\Omega }\right)\end{aligned}
  10. KTK_{\mathrm{T}}(10)KT=0.95×cmax1+0.6×xT=0.95×1.101+0.6×0.1049=0.9831\begin{aligned}K_{\mathrm{T}} &= \frac{0.95 \times c_{\mathrm{max}}}{1 + 0.6 \times x_{\mathrm{T}}} \\ &= \frac{0.95 \times 1{.}10}{1 + 0.6 \times 0{.}1049} \\ &= 0{.}9831\end{aligned}
  11. trt_{\mathrm{r}}(11)tr=UrHVUrLV=11010.5=10.476\begin{aligned}t_{\mathrm{r}} &= \frac{U_{\mathrm{rHV}}}{U_{\mathrm{rLV}}} \\ &= \frac{110}{10{.}5} \\ &= 10{.}476\end{aligned}
  12. ZnetZ_{\mathrm{net}}(12)Rnet=RK1tr2+KT×RTnT=0.0322 Ω,Xnet=XK1tr2+KT×XTnT=0.4376 ΩR_{\mathrm{net}} = \frac{R_{\mathrm{K1}}}{t_{\mathrm{r}}^{2}} + \frac{K_{\mathrm{T}} \times R_{\mathrm{T}}}{n_{\mathrm{T}}} = 0{.}0322\,\mathrm{\Omega },\quad X_{\mathrm{net}} = \frac{X_{\mathrm{K1}}}{t_{\mathrm{r}}^{2}} + \frac{K_{\mathrm{T}} \times X_{\mathrm{T}}}{n_{\mathrm{T}}} = 0{.}4376\,\mathrm{\Omega }
  13. ZK2Z_{\mathrm{K2}}(13)ZK2=R2+X2=0.03222+0.43762=0.4388 Ω\begin{aligned}Z_{\mathrm{K2}} &= \sqrt{R^{2} + X^{2}} \\ &= \sqrt{0{.}0322^{2} + 0{.}4376^{2}} \\ &= 0{.}4388\,\mathrm{\Omega }\end{aligned}
  14. Ik2′′I''_{\mathrm{k2}}(14)Ik2′′=c×Un3×ZK2=1.10×10 kV3×0.4388 Ω=14.474 kA\begin{aligned}I''_{\mathrm{k2}} &= \frac{c \times U_{\mathrm{n}}}{\sqrt{3} \times Z_{\mathrm{K2}}} \\ &= \frac{1{.}10 \times 10\,\mathrm{kV}}{\sqrt{3} \times 0{.}4388\,\mathrm{\Omega }} \\ &= 14{.}474\,\mathrm{kA}\end{aligned}
  15. κ2\kappa _{2}(15)κ2=1.02+0.98×e−3RX=1.02+0.98×e−3×0.074=1.806\begin{aligned}\kappa _{2} &= 1.02 + 0.98 \times e^{\frac{-3R}{X}} \\ &= 1.02 + 0.98 \times e^{-3 \times 0{.}074} \\ &= 1{.}806\end{aligned}
  16. ip2i_{\mathrm{p2}}(16)ip2=κ2×2×Ik2′′=1.806×1.4142×14.474=36.96 kA\begin{aligned}i_{\mathrm{p2}} &= \kappa _{2} \times \sqrt{2} \times I''_{\mathrm{k2}} \\ &= 1{.}806 \times 1.4142 \times 14{.}474 \\ &= 36{.}96\,\mathrm{kA}\end{aligned}
  17. Ith2I_{\mathrm{th2}}(17)Ith2=Ik2′′×m+n=14.474×0.0463+1=14.80 kA\begin{aligned}I_{\mathrm{th2}} &= I''_{\mathrm{k2}} \times \sqrt{m + n} \\ &= 14{.}474 \times \sqrt{0{.}0463 + 1} \\ &= 14{.}80\,\mathrm{kA}\end{aligned}
  18. ZL2Z_{\mathrm{L2}}(18)RL2=r×Ln=0.1250 Ω,XL2=x×Ln=0.0800 ΩR_{\mathrm{L2}} = \frac{r \times L}{n} = 0{.}1250\,\mathrm{\Omega },\quad X_{\mathrm{L2}} = \frac{x \times L}{n} = 0{.}0800\,\mathrm{\Omega }
  19. ZK3Z_{\mathrm{K3}}(19)ZK3=R2+X2=0.15722+0.51762=0.5410 Ω\begin{aligned}Z_{\mathrm{K3}} &= \sqrt{R^{2} + X^{2}} \\ &= \sqrt{0{.}1572^{2} + 0{.}5176^{2}} \\ &= 0{.}5410\,\mathrm{\Omega }\end{aligned}
  20. Ik3′′I''_{\mathrm{k3}}(20)Ik3′′=c×Un3×ZK3=1.10×10 kV3×0.5410 Ω=11.740 kA\begin{aligned}I''_{\mathrm{k3}} &= \frac{c \times U_{\mathrm{n}}}{\sqrt{3} \times Z_{\mathrm{K3}}} \\ &= \frac{1{.}10 \times 10\,\mathrm{kV}}{\sqrt{3} \times 0{.}5410\,\mathrm{\Omega }} \\ &= 11{.}740\,\mathrm{kA}\end{aligned}
  21. κ3\kappa _{3}(21)κ3=1.02+0.98×e−3RX=1.02+0.98×e−3×0.304=1.414\begin{aligned}\kappa _{3} &= 1.02 + 0.98 \times e^{\frac{-3R}{X}} \\ &= 1.02 + 0.98 \times e^{-3 \times 0{.}304} \\ &= 1{.}414\end{aligned}
  22. ip3i_{\mathrm{p3}}(22)ip3=κ3×2×Ik3′′=1.414×1.4142×11.740=23.48 kA\begin{aligned}i_{\mathrm{p3}} &= \kappa _{3} \times \sqrt{2} \times I''_{\mathrm{k3}} \\ &= 1{.}414 \times 1.4142 \times 11{.}740 \\ &= 23{.}48\,\mathrm{kA}\end{aligned}
  23. Ith3I_{\mathrm{th3}}(23)Ith3=Ik3′′×m+n=11.740×0.0113+1=11.81 kA\begin{aligned}I_{\mathrm{th3}} &= I''_{\mathrm{k3}} \times \sqrt{m + n} \\ &= 11{.}740 \times \sqrt{0{.}0113 + 1} \\ &= 11{.}81\,\mathrm{kA}\end{aligned}

Based on: IEC 60909-0; GB/T 15544.1; IEC 60909-0 3.3.3 (K_T); IEC 60909-0 3.8 (M); IEC 62271-100

How it is calculated

Equivalent impedance of a radial network: feeder Z_Q = c·U_n²/S″kQ, lines from their values per km, transformer Z_T = u_k·U_rT²/S_rT times the correction factor K_T, with the primary-side impedance referred to the secondary by the ratio squared. I″k = c·U_n/(√3·Z_k); above 1 kV the voltage factor c is 1.1 for maximum and 1.0 for minimum currents.

Peak factor κ = 1.02 + 0.98·e^(−3R/X) and peak current i_p = κ·√2·I″k. Motors become an equivalent impedance from their starting current ratio, in parallel with the network; the peak current is the sum of the two branches. Thermal equivalent current I_th = I″k·√(m + 1).

Follows IEC 60909-0 (GB/T 15544.1) for three-phase faults far from generators. Generators, meshed networks and unbalanced faults are not included. Decay of the motor current is ignored, so using I″k as the breaking current is on the safe side.

Questions

What is the fault level?
The apparent power √3·U_n·I″k at a point, in MVA. Utilities state it for their busbars, and it is the usual starting value for calculating further into your own network.
What if I don't know the network fault level?
Ask the utility for the maximum and minimum values. As an upper estimate you can use the breaking capacity of the incoming switchgear, which gives results on the high side.
What changes when transformers run in parallel?
Their impedances are in parallel, so the secondary fault current rises sharply. Enter 1 for split busbars. Select equipment for the highest arrangement that can occur.
The secondary fault current exceeds the breaker rating. What helps?
Run the busbars split, use a higher-impedance transformer, add a current-limiting reactor or choose a higher breaker rating. Change the values to see the effect.