How it is calculated
Energy from the battery: E = P × t / η. Nominal energy: E_nom = E / DoD × (1 + margin). Capacity: C = E_nom / U_dc.
Discharge current I = P / (η × U_dc) and the C-rate is I / C. Batteries in series = U_dc / U_battery (rounded up), strings in parallel = C / C_battery (rounded up).
This is the simple energy method. For lead-acid with a varying load, use the manufacturer's constant-power tables (IEEE 485 for stationary cells).
Questions
- How many batteries do I need for 4 hours of backup?
- Enter the load in watts and 4 hours with your battery voltage. The result is the capacity in Ah and the number of batteries to put in series and parallel.
- What depth of discharge should I use?
- About 50 % for lead-acid if you want a long life, 80–90 % for lithium iron phosphate. Deeper cycling wears batteries faster.
- Why is a discharge rate over 1 C a warning?
- Batteries lose usable capacity when discharged fast, especially lead-acid. Above 1 C check the discharge tables or choose more capacity.
- Does temperature matter?
- Yes: capacity drops in the cold. Add margin or use the temperature correction from the data sheet.
Other calculators
- kW to amps calculator
- Voltage drop calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Lightning rod height calculator
- Power factor correction calculator
- Generator size calculator
- Lighting calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe flow and diameter calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator