Battery capacity calculator

Size a battery bank (UPS, solar storage, telecom, DC systems) from the load, the hours of backup and the voltage, and see how many batteries to connect.

Result

Battery capacity needed
255 Ah
Nominal energy
12.22 kWh
Discharge current
46.3 A
Discharge rate (C)
0.18
Batteries in series
4
Strings in parallel
3
Batteries in total
12
  • Discharge rate within 1 C 0.18≤10{.}18 \le 1OK

Lead-acid capacity falls at high discharge rates (Peukert) and at low temperature; check the maker's discharge table for the actual rate and time.

Working

  1. EE(1)E=P×tη=2000×40.90=8.89 kWh\begin{aligned}E &= \frac{P \times t}{\eta } \\ &= \frac{2000 \times 4}{0{.}90} \\ &= 8{.}89\,\mathrm{kWh}\end{aligned}
  2. EnomE_{\mathrm{nom}}(2)Enom=EDoD×(1+δ)=8.890.80×1.10=12.22 kWh\begin{aligned}E_{\mathrm{nom}} &= \frac{E}{\mathrm{DoD}} \times \left(1 + δ\right) \\ &= \frac{8{.}89}{0{.}80} \times 1{.}10 \\ &= 12{.}22\,\mathrm{kWh}\end{aligned}
  3. Ah\mathrm{Ah}(3)C=EnomUdc=12 222.248=254.6 Ah\begin{aligned}C &= \frac{E_{\mathrm{nom}}}{U_{\mathrm{dc}}} \\ &= \frac{12\,222{.}2}{48} \\ &= 254{.}6\,\mathrm{Ah}\end{aligned}

Based on: IEEE 485 / IEEE 1115 (sizing method); E = P × t / (η × DoD)

How it is calculated

Energy from the battery: E = P × t / η. Nominal energy: E_nom = E / DoD × (1 + margin). Capacity: C = E_nom / U_dc.

Discharge current I = P / (η × U_dc) and the C-rate is I / C. Batteries in series = U_dc / U_battery (rounded up), strings in parallel = C / C_battery (rounded up).

This is the simple energy method. For lead-acid with a varying load, use the manufacturer's constant-power tables (IEEE 485 for stationary cells).

Questions

How many batteries do I need for 4 hours of backup?
Enter the load in watts and 4 hours with your battery voltage. The result is the capacity in Ah and the number of batteries to put in series and parallel.
What depth of discharge should I use?
About 50 % for lead-acid if you want a long life, 80–90 % for lithium iron phosphate. Deeper cycling wears batteries faster.
Why is a discharge rate over 1 C a warning?
Batteries lose usable capacity when discharged fast, especially lead-acid. Above 1 C check the discharge tables or choose more capacity.
Does temperature matter?
Yes: capacity drops in the cold. Add margin or use the temperature correction from the data sheet.