Low-voltage short-circuit current calculator

Find the initial short-circuit current, the peak current with its peak (impact) factor κ and the thermal equivalent current for a fault on a low-voltage system.

Result

Initial short-circuit current I″k
20.29 kA
Peak short-circuit current i_p
37.44 kA
Thermal equivalent current I_th
20.37 kA
Peak factor κ
1.305
R/X at the fault point
0.412
Breaking current I_b (far from generators)
20.29 kA
Short-circuit impedance Z_k
11.953 mΩ
Short-circuit power S″k
14.06 MVA

Running motors feed the fault and can raise I″k and i_p; add them when they total more than about 1 % of I″k.

Working

  1. cc(1)c=1.05c = 1{.}05
  2. ZQZ_{\mathrm{Q}}(2)ZQ=c×U2SkQ′′=1.05×4002500 000 000=0.336 mΩ(R=0.033,  X=0.334 mΩ)\begin{aligned}Z_{\mathrm{Q}} &= \frac{c \times U^{2}}{S''_{\mathrm{kQ}}} \\ &= \frac{1{.}05 \times 400^{2}}{500\,000\,000} \\ &= 0{.}336\,\mathrm{m\Omega }\left(R = 0{.}033,\; X = 0{.}334\,\mathrm{m\Omega }\right)\end{aligned}
  3. ZTZ_{\mathrm{T}}(3)ZT=uk×U2Sr=6.00 %×40021 000 000=9.600 mΩ(RT=1.600,  XT=9.466 mΩ)\begin{aligned}Z_{\mathrm{T}} &= \frac{u_{\mathrm{k}} \times U^{2}}{S_{\mathrm{r}}} \\ &= \frac{6{.}00\,\% \times 400^{2}}{1\,000\,000} \\ &= 9{.}600\,\mathrm{m\Omega }\left(R_{\mathrm{T}} = 1{.}600,\; X_{\mathrm{T}} = 9{.}466\,\mathrm{m\Omega }\right)\end{aligned}
  4. KTK_{\mathrm{T}}(4)KT=0.95×cmax1+0.6×xT=0.95×1.051+0.6×0.0592=0.9633\begin{aligned}K_{\mathrm{T}} &= \frac{0.95 \times c_{\mathrm{max}}}{1 + 0.6 \times x_{\mathrm{T}}} \\ &= \frac{0.95 \times 1{.}05}{1 + 0.6 \times 0{.}0592} \\ &= 0{.}9633\end{aligned}
  5. ZLZ_{\mathrm{L}}(5)RL=ρ×LS×n=2.976 mΩ,XL=x×Ln=1.600 mΩR_{\mathrm{L}} = \frac{\rho \times L}{S \times n} = 2{.}976\,\mathrm{m\Omega },\quad X_{\mathrm{L}} = \frac{x \times L}{n} = 1{.}600\,\mathrm{m\Omega }
  6. ZkZ_{\mathrm{k}}(6)Zk=R2+X2=4.5512+11.0532=11.953 mΩ\begin{aligned}Z_{\mathrm{k}} &= \sqrt{R^{2} + X^{2}} \\ &= \sqrt{4{.}551^{2} + 11{.}053^{2}} \\ &= 11{.}953\,\mathrm{m\Omega }\end{aligned}
  7. Ik′′I''_{\mathrm{k}}(7)Ik′′=c×U3×Zk=1.05×4003×11.953 mΩ=20.29 kA\begin{aligned}I''_{\mathrm{k}} &= \frac{c \times U}{\sqrt{3} \times Z_{\mathrm{k}}} \\ &= \frac{1{.}05 \times 400}{\sqrt{3} \times 11{.}953\,\mathrm{m\Omega }} \\ &= 20{.}29\,\mathrm{kA}\end{aligned}
  8. κ\kappa (8)κ=1.02+0.98×e−3RX=1.02+0.98×e−3×0.412=1.305\begin{aligned}\kappa &= 1.02 + 0.98 \times e^{\frac{-3R}{X}} \\ &= 1.02 + 0.98 \times e^{-3 \times 0{.}412} \\ &= 1{.}305\end{aligned}
  9. ipi_{\mathrm{p}}(9)ip=κ×2×Ik′′=1.305×1.4142×20.29=37.44 kA\begin{aligned}i_{\mathrm{p}} &= \kappa \times \sqrt{2} \times I''_{\mathrm{k}} \\ &= 1{.}305 \times 1.4142 \times 20{.}29 \\ &= 37{.}44\,\mathrm{kA}\end{aligned}
  10. mm(10)m=e4⋅f⋅Tk⋅ln⁡(κ−1)−12⋅f⋅Tk⋅ln⁡(κ−1)=0.0084,n=1m = \frac{e^{4\cdot f\cdot T_{\mathrm{k}}\cdot \ln \left(\kappa -1\right)} - 1}{2\cdot f\cdot T_{\mathrm{k}}\cdot \ln \left(\kappa -1\right)} = 0{.}0084,\quad n = 1
  11. IthI_{\mathrm{th}}(11)Ith=Ik′′×m+n=20.29×0.0084+1=20.37 kA\begin{aligned}I_{\mathrm{th}} &= I''_{\mathrm{k}} \times \sqrt{m + n} \\ &= 20{.}29 \times \sqrt{0{.}0084 + 1} \\ &= 20{.}37\,\mathrm{kA}\end{aligned}

Based on: IEC 60909-0; GB/T 15544.1; IEC 60909-0 3.3.3 (K_T); IEC 60909-0 4.3.1.1 (κ); IEC 60909-0 4.8 (m, n)

How it is calculated

The network is reduced to one impedance at the fault: the upstream source Z_Q = c·U²/S″kQ, the transformer Z_T = u_k·U²/S_r with the correction factor K_T, and the cable R and X. Then I″k = c·U / (√3·Z_k), with the voltage factor c = 1.05 (maximum) or 0.95 (minimum) for systems up to 1 kV.

The peak factor is κ = 1.02 + 0.98·e^(−3R/X); the peak current is i_p = κ·√2·I″k. The thermal equivalent current is I_th = I″k·√(m + n), with m from the fault duration and n = 1 far from generators.

Method of IEC 60909-0 (GB/T 15544.1) for three-phase faults far from generators. Motor contribution, generators and unbalanced faults are not included.

Questions

What is the impact (peak) factor?
The ratio of the highest instantaneous current in the first half cycle to the peak of the steady short-circuit current. It depends on R/X at the fault: close to 2 for a purely inductive circuit, close to 1 when resistance dominates, so long thin cables lower it.
Which value do I use to choose a breaker?
The breaking capacity must be at least I″k at the breaker's location with the maximum voltage factor, and the making capacity at least i_p. Use the minimum case to check that the protection still trips.
Why is the cable included?
Every metre of cable adds impedance and lowers the fault level; at the end of a long feeder it can be far below the level at the transformer. Enter the cable length to the point you are checking.
Do motors matter?
Large motors running at the time of the fault feed current back and raise I″k and i_p; add their contribution when their total rating is above a few percent of the transformer.