How it is calculated
Running load: S₁ = P / (cos φ × k), where k is the planned maximum loading of the set (70–80 % is common).
Motor start: the start current is a multiple of full-load current (about 6 direct, 2 star-delta, 3 soft starter, 1.5 drive); S_st = P_m / (η cos φ_m) × I_st/I_n. For an allowed dip ΔU the set must be at least S₂ = x′d × S_st × (1/ΔU − 1), from the sub-transient reactance of the alternator.
The result is the next standard set above the larger of S₁ and S₂. The set's active power is taken at 0.8 power factor (ISO 8528).
Questions
- How big a generator do I need for my building?
- Add up the loads that run at the same time, divide by their power factor and by the planned loading, then check the largest motor start. Enter both: the calculator shows which one decides.
- Why does one motor decide the size?
- A directly started motor draws about six times its rated current for a moment. The alternator has to hold the voltage through that, which can need a much bigger set than the running load.
- How can I reduce the generator size?
- Start the largest motors with a soft starter or drive, start them one at a time, or accept a larger voltage dip if the loads allow it.
- Does altitude or temperature matter?
- Yes: the set loses output above about 1000 m or 40 °C. Take the derating from the manufacturer and compare with the rating shown.
Other calculators
- kW to amps calculator
- Voltage drop calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Lightning rod height calculator
- Power factor correction calculator
- Lighting calculator
- Battery capacity calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe flow and diameter calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator