Generator size calculator

Choose the generator set rating from the running load and from the voltage dip when the largest motor starts, and take the larger of the two.

Result

Generator set rating
500 kVA
Active power at 0.8 power factor
400 kW
Loading in service
75 %
Required rating
468.8 kVA
By the running load
468.8 kVA
By motor starting
422.0 kVA
Voltage dip at the chosen rating
17.4 %
  • Start dip within the limit 17.4 %≤20 %17{.}4\,\% \le 20\,\%OK

Also check the set's step-load capability and the altitude and temperature derating on the data sheet.

Working

  1. S1S_{1}(1)S1=Pcos⁡φ×k=3000.80×0.80=468.8 kVA\begin{aligned}S_{1} &= \frac{P}{\cos \varphi \times k} \\ &= \frac{300}{0{.}80 \times 0{.}80} \\ &= 468{.}8\,\mathrm{kVA}\end{aligned}
  2. SstS_{\mathrm{st}}(2)Sst=Pmη×cos⁡φm×IstIn=550.92×0.85×6.0=422.0 kVA\begin{aligned}S_{\mathrm{st}} &= \frac{P_{\mathrm{m}}}{\eta \times \cos \varphi _{\mathrm{m}}} \times \frac{I_{\mathrm{st}}}{I_{\mathrm{n}}} \\ &= \frac{55}{0{.}92 \times 0{.}85} \times 6{.}0 \\ &= 422{.}0\,\mathrm{kVA}\end{aligned}
  3. S2S_{2}(3)S2=xd′×Sst×(1ΔU−1)=0.25×422.0×(10.20−1)=422.0 kVA\begin{aligned}S_{2} &= x'_{\mathrm{d}} \times S_{\mathrm{st}} \times \left(\frac{1}{\Delta U} - 1\right) \\ &= 0{.}25 \times 422{.}0 \times \left(\frac{1}{0{.}20} - 1\right) \\ &= 422{.}0\,\mathrm{kVA}\end{aligned}

Based on: ISO 8528-1; GB/T 2820.1; ΔU = x′d S_st / (S_g + x′d S_st)

How it is calculated

Running load: S₁ = P / (cos φ × k), where k is the planned maximum loading of the set (70–80 % is common).

Motor start: the start current is a multiple of full-load current (about 6 direct, 2 star-delta, 3 soft starter, 1.5 drive); S_st = P_m / (η cos φ_m) × I_st/I_n. For an allowed dip ΔU the set must be at least S₂ = x′d × S_st × (1/ΔU − 1), from the sub-transient reactance of the alternator.

The result is the next standard set above the larger of S₁ and S₂. The set's active power is taken at 0.8 power factor (ISO 8528).

Questions

How big a generator do I need for my building?
Add up the loads that run at the same time, divide by their power factor and by the planned loading, then check the largest motor start. Enter both: the calculator shows which one decides.
Why does one motor decide the size?
A directly started motor draws about six times its rated current for a moment. The alternator has to hold the voltage through that, which can need a much bigger set than the running load.
How can I reduce the generator size?
Start the largest motors with a soft starter or drive, start them one at a time, or accept a larger voltage dip if the loads allow it.
Does altitude or temperature matter?
Yes: the set loses output above about 1000 m or 40 °C. Take the derating from the manufacturer and compare with the rating shown.