How it is calculated
Lumen method: N = E × A / (Φ × UF × MF), with E the required lux, A the floor area, Φ the lumens per luminaire, UF the utilisation factor and MF the maintenance factor.
The room index is K = L × W / (H_m × (L + W)), where H_m is the height from the work plane to the luminaires. The utilisation factor is read from K and the reflectances; here a typical value is used unless you enter the one from the data sheet.
The luminaires are arranged in a grid close to the room's proportions. The spacing should not exceed about 1.5 times the mounting height, for uniform light. The method gives average illuminance only.
Questions
- How many lux do I need?
- It depends on the task: for example 100 lx for corridors, 300 for stores, 500 for offices and classrooms, 750 for drawing work. Check EN 12464-1 or GB 50034 for your room type.
- What is the maintenance factor?
- It allows for dirt and lamp ageing, so the room still meets the lux just before cleaning or replacement. 0.8 suits a clean office with LED.
- What utilisation factor should I use?
- The luminaire maker's table gives it for your room index and reflectances. The built-in value is an estimate for a typical LED luminaire in a light-coloured room.
- Does it check uniformity or glare?
- No. It gives the average. Use lighting design software for uniformity, glare and emergency lighting.
Other calculators
- kW to amps calculator
- Voltage drop calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Lightning rod height calculator
- Power factor correction calculator
- Generator size calculator
- Battery capacity calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe flow and diameter calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator