CADXChange

Lightning rod height calculator

Use the rolling sphere method to find the rod height needed to protect a roof or equipment, the radius one rod protects, or the protection between two rods.

Standard

Result

One rod cannot reach this far. Use more rods or a mesh. The largest radius it can cover is shown.

Working

  1. hrh_{\mathrm{r}}(1)hr=30 mh_{\mathrm{r}} = 30\,\mathrm{m}
  2. rxr_{\mathrm{x}}(2)rx=L2+W22=202+1022=11.18 m\begin{aligned}r_{\mathrm{x}} &= \frac{\sqrt{L^{2} + W^{2}}}{2} \\ &= \frac{\sqrt{20^{2} + 10^{2}}}{2} \\ &= 11{.}18\,\mathrm{m}\end{aligned}

How it is calculated

A sphere of radius h_r rolls over the structure. Anything the sphere cannot touch is protected. The radius depends on the protection class: GB 50057 uses 30, 45 and 60 m for classes 1 to 3; IEC 62305 uses 20, 30, 45 and 60 m for LPL I to IV.

One rod of height h protects, at height h_x, a circle of radius r_x = √(h(2h_r − h)) − √(h_x(2h_r − h_x)). The height needed for a given r_x is h = h_r − √(h_r² − (r_x + √(h_x(2h_r − h_x)))²).

Two rods a distance D apart: the sphere sags between them by h_r − √(h_r² − (D/2)²), so the boundary midway is at h₀ = h − h_r + √(h_r² − (D/2)²), and the half-width protected at h_x is √(h₀(2h_r − h₀)) − √(h_x(2h_r − h_x)).

Questions

Which protection class do I choose?
It comes from the risk assessment (GB 50057 or IEC 62305-2). Higher-risk structures take the smaller sphere: for example class 1 or LPL I for explosive or critical sites.
Is a taller rod always better?
Not beyond the sphere radius: above that height the protected area does not grow. At that point add rods or a mesh instead of a taller mast.
Can I use this for a flat roof?
Yes: enter the roof height as the object height and the roof as a rectangle with the rod at the centre. For several rods, use the two-rod mode between each pair and make sure the whole roof is covered.
Is this the only method?
The protection angle and the mesh method are also allowed by the standards. The rolling sphere is the most general and is usually the strictest for tall structures.

Other calculators

Drawing it up