How it is calculated
A sphere of radius h_r rolls over the structure. Anything the sphere cannot touch is protected. The radius depends on the protection class: GB 50057 uses 30, 45 and 60 m for classes 1 to 3; IEC 62305 uses 20, 30, 45 and 60 m for LPL I to IV.
One rod of height h protects, at height h_x, a circle of radius r_x = √(h(2h_r − h)) − √(h_x(2h_r − h_x)). The height needed for a given r_x is h = h_r − √(h_r² − (r_x + √(h_x(2h_r − h_x)))²).
Two rods a distance D apart: the sphere sags between them by h_r − √(h_r² − (D/2)²), so the boundary midway is at h₀ = h − h_r + √(h_r² − (D/2)²), and the half-width protected at h_x is √(h₀(2h_r − h₀)) − √(h_x(2h_r − h_x)).
Questions
- Which protection class do I choose?
- It comes from the risk assessment (GB 50057 or IEC 62305-2). Higher-risk structures take the smaller sphere: for example class 1 or LPL I for explosive or critical sites.
- Is a taller rod always better?
- Not beyond the sphere radius: above that height the protected area does not grow. At that point add rods or a mesh instead of a taller mast.
- Can I use this for a flat roof?
- Yes: enter the roof height as the object height and the roof as a rectangle with the rod at the centre. For several rods, use the two-rod mode between each pair and make sure the whole roof is covered.
- Is this the only method?
- The protection angle and the mesh method are also allowed by the standards. The rolling sphere is the most general and is usually the strictest for tall structures.
Other calculators
- kW to amps calculator
- Voltage drop calculator
- Cable size calculator
- Transformer size calculator
- Low-voltage short-circuit calculator
- High-voltage short-circuit calculator
- Earth resistance calculator
- Power factor correction calculator
- Generator size calculator
- Lighting calculator
- Battery capacity calculator
- PV string size calculator
- Pipe insulation thickness calculator
- Pipe flow and diameter calculator
- Pipe pressure drop calculator
- Pump power calculator
- Heat exchanger calculator