CADXChange

Cable size calculator

Find the smallest cable that carries the load after temperature and grouping factors, stays within your voltage drop and survives the short circuit.

Standard

Checks that the cable survives the fault until the device trips.

Result

Cable size
10 mm²
Current-carrying capacity
70.0 A
Voltage drop
3.20 %
Current
63.00 A
Total correction factor
1.000
Voltage drop
12.80 V
Decided by
current-carrying capacity
  • Capacity covers the load 70.0 A≥63.00 A70{.}0\,\mathrm{A} \ge 63{.}00\,\mathrm{A}OK
  • Voltage drop within the limit 3.20 %≤5.0 %3{.}20\,\% \le 5{.}0\,\%OK

Working

  1. Temperature and grouping factors(1)k=kT×kG=1.00×1.00=1.000\begin{aligned}k &= k_{\mathrm{T}} \times k_{\mathrm{G}} \\ &= 1{.}00 \times 1{.}00 \\ &= 1{.}000\end{aligned}
  2. Required current-carrying capacity(2)Iz=I0×k≥63.00 A1=63.00 AI_{\mathrm{z}} = I_{0} \times k \ge \frac{63{.}00\,\mathrm{A}}{1} = 63{.}00\,\mathrm{A}
  3. Smallest size by capacity(3)10mm2:Iz=70×1.000=70.0 A\begin{aligned}10m m^{2}:I_{\mathrm{z}} &= 70 \times 1{.}000 \\ &= 70{.}0\,\mathrm{A}\end{aligned}
  4. Smallest size by voltage drop(4)10mm2:ΔU=3.20 %10m m^{2}:\Delta U = 3{.}20\,\%
  5. Selected size(5)10mm210m m^{2}

Based on: IEC 60364-5-52 Table C.52.1; IEC 60364-5-52 Table B.52.14; IEC 60364-5-52 Table B.52.17; IEC 60364-5-52 Annex G

How it is calculated

Each size is checked three ways and the first that passes all of them is chosen: corrected current-carrying capacity at least the load (and the protective device, if given), voltage drop within the limit, and enough cross-section for the short circuit.

IEC and GB: capacities from the simplified tables of IEC 60364-5-52 Annex C (identical in GB/T 16895.6-2014), corrected by Tables B.52.14 to B.52.18 for temperature, grouping and soil. Short circuit: S ≥ I √t / k with k from IEC 60364-4-43 (115 for copper PVC, 143 for copper XLPE).

NEC: ampacity from Table 310.16, corrected by Table 310.15(B)(1)(1) and 310.15(C)(1), limited by the terminal rating (110.14(C)) and the small-conductor rule of 240.4(D). Continuous loads are taken at 125 %.

Questions

Which installation method should I choose?
The one that describes how the cable is run: in conduit in an insulated wall (A1, A2), in conduit on a wall (B1, B2), clipped to a wall (C), buried (D1, D2) or in free air and on perforated trays (E, F).
Why is a larger cable chosen than the table suggests?
Temperature above 30 °C, several circuits run together and long runs all push the size up. The result says which criterion decided the size.
Can I use aluminium?
Yes. Aluminium needs a larger cross-section for the same current and has higher resistance, so voltage drop decides sooner.
Is this enough for a final design?
It covers the usual checks. Final designs must also follow local rules, the manufacturer's data and the protective device's characteristics, and should be reviewed by a qualified engineer.