CADXChange

Pipe insulation thickness calculator

Find how much insulation a hot or cold pipe needs for a safe touch temperature, a heat-loss limit or to stay above the dew point, or the heat loss of a thickness you already have.

Result

Insulation thickness needed
12.1 mm
Heat loss per metre
130.6 W/m
Outer surface temperature
50.0 °C
Heat flux at the surface
300.0 W/m²
Bare pipe heat loss per metre
466.8 W/m
Saving against the bare pipe
72.0 %
Outside diameter with insulation
139 mm
Next 5 mm thickness
15 mm
Total heat loss of the pipe
13.06 kW
  • Surface at or below 60 °C 50.0 ∘C≤60∘C50{.}0\,{}^{\circ}\mathrm{C} \le 60{}^{\circ}\mathrm{C}OK

Steady state, one layer, the pipe wall and the inner film neglected. Real jobs add jacket, joints, supports and wind; use the manufacturer's data for the final design.

Working

  1. RinsR_{\mathrm{ins}}(1)Rins=ln⁡(r2r1)2πλ=ln⁡(69.357.2)2π×0.040=0.7658 m⋅K/W\begin{aligned}R_{\mathrm{ins}} &= \frac{\ln \left(\frac{r_{2}}{r_{1}}\right)}{2\pi \lambda } \\ &= \frac{\ln \left(\frac{69{.}3}{57{.}2}\right)}{2\pi \times 0{.}040} \\ &= 0{.}7658\,\mathrm{m\cdot K/W}\end{aligned}
  2. RsR_{\mathrm{s}}(2)Rs=1h×2πr2=110×2π×0.0693=0.2297 m⋅K/W\begin{aligned}R_{\mathrm{s}} &= \frac{1}{h \times 2\pi r_{2}} \\ &= \frac{1}{10 \times 2\pi \times 0{.}0693} \\ &= 0{.}2297\,\mathrm{m\cdot K/W}\end{aligned}
  3. qq(3)q=Tf−TaRins+Rs=150−200.7658+0.2297=130.59 W/m\begin{aligned}q &= \frac{T_{\mathrm{f}} - T_{\mathrm{a}}}{R_{\mathrm{ins}} + R_{\mathrm{s}}} \\ &= \frac{150 - 20}{0{.}7658 + 0{.}2297} \\ &= 130{.}59\,\mathrm{W/m}\end{aligned}
  4. TsT_{\mathrm{s}}(4)Ts=Ta+q×Rs=20+130.59×0.2297=50.0 ∘C\begin{aligned}T_{\mathrm{s}} &= T_{\mathrm{a}} + q \times R_{\mathrm{s}} \\ &= 20 + 130{.}59 \times 0{.}2297 \\ &= 50{.}0\,{}^{\circ}\mathrm{C}\end{aligned}

Based on: ISO 12241; GB/T 8175; GB 50264; ASTM C680

How it is calculated

Heat flow per metre of pipe: q = (T_f − T_a) / (R_ins + R_s), with R_ins = ln(r₂/r₁) / (2πλ) the resistance of the insulation and R_s = 1 / (h × 2π r₂) the resistance of the outer surface. The surface temperature is T_s = T_a + q × R_s.

Thickness for a target is found by increasing r₂ until the surface temperature, heat loss or dew-point condition is met. For condensation, the dew point comes from the air temperature and humidity (Magnus formula).

Steady state, one layer, round pipe. The pipe wall and the film inside are neglected, which is accurate for steel pipes with moving fluid. Compare ISO 12241, GB/T 8175 and GB 50264.

Questions

How thick should pipe insulation be?
It depends on the fluid temperature, the pipe size, the insulation and the goal: personnel protection (surface at or below about 50–60 °C), a heat-loss limit, or condensation control. Enter your goal and the calculator solves for the thickness.
What conductivity do I enter?
The value of the insulation at its mean temperature from the data sheet. Mineral wool is about 0.04 W/(m·K) near 50 °C and rises with temperature.
How do I stop a cold pipe sweating?
The outer surface has to stay above the dew point of the surrounding air. Use the condensation mode with the air temperature and the highest humidity you expect, and add a vapour barrier.
Does the result include the jacket and supports?
No. Jacketing, joints and supports add loss, so treat the figure as the calculation for the insulation layer alone.